6 Installation

Installer and user reference guide

17

FFA25~60A2VEB(9)
Split system air conditioners
4P550955-4 – 2018.08

6.4.2

Precautions when connecting the
electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

6.4.3

Guidelines when connecting the electrical
wiring

Keep the following in mind:

▪ If  stranded  conductor  wires  are  used,  install  a  round  crimp-style

terminal  on  the  end  of  the  wire.  Place  the  round  crimp-style
terminal on the wire up to the covered part and fasten the terminal
with the appropriate tool.

b

a

a

Stranded conductor wire

b

Round crimp-style terminal

▪ Use the following methods for installing wires:

Wire type

Installation method

Single-core wire

c b

c

a

a

A

AA´

a

 Curled single-core wire

b

 Screw

c

 Flat washer

Stranded conductor
wire with round
crimp-style terminal

c b

b

a

c

a

B

B

a

 Terminal

b

 Screw

c

 Flat washer

O

 Allowed

X

 NOT allowed

Tightening torques

Wiring

Screw size

Tightening torque

(N•m)

Interconnection
cable
(indoor↔outdoor)

M4

1.18~1.44

Wiring

Screw size

Tightening torque

(N•m)

User interface cable

M3.5

0.79~0.97

6.4.4

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

Minimum cable section of

2.5 mm² and applicable for

230 V

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

Maximum 500 m

6.4.5

To connect the electrical wiring on the
indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For instructions on how to connect the decoration panel

and  the  sensor  kit,  see  the  wiring  instruction  sheet
(delivered with the unit, inside the accessory bag).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

5

Reattach the service cover.

Pair type or multi-system.

 1 user interface controls 1 indoor unit.

Summary of Contents for FFA50A2VEB9

Page 1: ...ser reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FFA25A2VEB FFA35A2VEB FFA50A2VEB FFA60A2VEB FFA25A2VEB9 FFA35A2VEB9 FFA50A2VE...

Page 2: ...electrical wiring 17 6 4 4 Specifications of standard wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 19 8 1...

Page 3: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Page 4: ...ed Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmospheres In places where there is machinery that emits...

Page 5: ...5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 4...

Page 6: ...n Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing clo...

Page 7: ...head and make proper tightening impossible Over tightening the terminal screws may break them WARNING After finishing the electrical work confirm that each electrical component and terminal inside th...

Page 8: ...ter describes what you have to do after the box with the indoor unit is delivered on site Keep the following in mind At delivery the unit MUST be checked for damage Any damage MUST be reported immedia...

Page 9: ...5 46 C DB 9 21 C DB 10 15 C WB 18 37 C DB 12 28 C WB 10 27 C DB RXS25 60 10 46 C DB 15 24 C DB 16 18 C WB 18 32 C DB 10 30 C DB Outdoor units Cooling Heating 2MXS50 10 46 C DB 15 24 C DB 16 18 C WB 1...

Page 10: ...ance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial en...

Page 11: ...ce to the floor see below C 295 mm In case of installation with BYFQ60B 300 mm In case of installation with BYFQ60C a Indoor unit b Lighting the figure shows ceiling mounted lighting but recessed ligh...

Page 12: ...or installation INFORMATION This chapter only describes installation instructions specific to the indoor unit For the other instructions see The installation manual of the outdoor unit The installatio...

Page 13: ...5 mm 595 mm 10 mm 12 5 mm A Ceiling opening B Distance between the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Level Make sure the unit is level at a...

Page 14: ...6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f...

Page 15: ...refrigerant to be used Only use installation tools e g manifold gauge set that are exclusively used for R32 or R410A installations to withstand the pressure and to prevent foreign materials e g minera...

Page 16: ...tions Insulation Insulate the refrigerant piping on the indoor unit as follows A B a d c e f b b a d c e f b b 2 4 3 g 1 2 3 4 g A B 1 A Gas piping B Liquid piping a Insulation material field supply b...

Page 17: ...30 V User interface cable Vinyl cords with 0 75 to 1 25 mm sheath or cables 2 core wires Maximum 500 m 6 4 5 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delive...

Page 18: ...t they correspond with the actual installation setup and with the needs of the user Ceiling height Air flow direction Air volume when thermostat control is OFF Time to clean air filter Setting Ceiling...

Page 19: ...power consumption NOTICE Before starting up the system the unit MUST be energised for at least 6 hours The crankcase heater needs to heat up the compressor oil to avoid oil shortage and compressor bre...

Page 20: ...it first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B by removing the stem cap and turning counte...

Page 21: ...hase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The...

Page 22: ...ESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MA...

Page 23: ...ce see the operation manual of the installed user interface 13 Before operation WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been...

Page 24: ...n It may take longer to reach the set temperature for general heating operation than for cooling operation The following operation is performed in order to prevent the heating capacity from dropping o...

Page 25: ...lades while the swing flap is in operation Fingers may become caught or the unit may break down NOTICE The movable limit of the flap is changeable Contact your dealer for details only for double flow...

Page 26: ...result in burnout of these components 16 1 Cleaning the air filter suction grille air outlet and outside panels 16 1 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6...

Page 27: ...in order to dry the interior of the units Refer to 14 2 2 About cooling heating fan only and automatic operation on page 24 for details on fan only operation Turn off the power The user interface dis...

Page 28: ...face and switches 25 000 hours Drain pan 8 years Expansion valve 20 000 hours Solenoid valve 20 000 hours The table assumes the following conditions of use Normal use without frequent starting and sto...

Page 29: ...N OFF button on the user interface is pressed If the operation lamp lights the system is in normal condition To prevent overloading of the compressor motor the air conditioner starts 5 minutes after i...

Page 30: ...s is to prevent refrigerant from remaining in the compressor The unit will stop after 5 to 10 minutes 18 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requir...

Page 31: ......

Page 32: ...4P550955 4 2018 08 Copyright 2017 Daikin...

Reviews: