17 Troubleshooting

Installer and user reference guide

28

FFA25~60A2VEB(9)

Split system air conditioners

4P550955-4 – 2018.08

16.5

After-sales service and warranty

16.5.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

16.5.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe  and  non-toxic.  R410A  is  a  non-combustible
refrigerant,  and  R32  is  a  mildly  flammable  refrigerant,
but  they  will  generate  a  toxic  gas  when  they
accidentally  leak  into  a  room  where  combustible  air
from  fan  heaters,  gas  cookers,  etc.  is  present.  Always
have  qualified  service  personnel  confirm  that  the  point
of  leakage  has  been  repaired  or  corrected  before
resuming operation.

16.5.3

Recommended maintenance and
inspection cycles

Be  aware  that  the  mentioned  maintenance  and  replacement  cycles
do not relate to the warranty period of the components.

Component

Inspection

cycle

Maintenance cycle

(replacements and/or

repairs)

Electric motor

1 year

20,000 hours

PCB

25,000 hours

Heat exchanger

5 years

Sensor (thermistor, etc.)

5 years

User interface and switches

25,000 hours

Drain pan

8 years

Expansion valve

20,000 hours

Solenoid valve

20,000 hours

The table assumes the following conditions of use:

▪ Normal  use  without  frequent  starting  and  stopping  of  the  unit.

Depending  on  the  model,  we  recommend  not  starting  and
stopping the machine more than 6 times/hour.

▪ Operation  of  the  unit  is  assumed  to  be  10  hours/day  and

2,500 hours/year.

NOTICE

▪ The  table  indicates  main  components.  Refer  to  your

maintenance and inspection contract for more details.

▪ The  table  indicates  recommended  intervals  of

maintenance cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be  required  sooner.  Recommended  intervals  can  be
used  for  appropriate  maintenance  design  in  terms  of
budgeting 

maintenance 

and 

inspection 

fees.

Depending  on  the  content  of  the  maintenance  and
inspection contract, inspection and maintenance cycles
may in reality be shorter than listed.

16.5.4

Shortened maintenance and replacement
cycles

Shortening of "maintenance cycle" and "replacement cycle" needs to
be considered in following situations:

The unit is used in locations where:

▪ Heat and humidity fluctuate out of the ordinary.

▪ Power fluctuation is high (voltage, frequency, wave distortion, etc.)

(the  unit  cannot  be  used  if  power  fluctuation  is  outside  the
allowable range).

▪ Bumps and vibrations are frequent.

▪ Dust,  salt,  harmful  gas  or  oil  mist  such  as  sulphurous  acid  and

hydrogen sulfide may be present in the air.

▪ The machine is started and stopped frequently or operation time is

long (sites with 24 hour air-conditioning).

Recommended replacement cycle of wear parts

Component

Inspection

cycle

Maintenance cycle

(replacements and/or

repairs)

Air filter

1 year

5 years

High efficiency filter

1 year

Fuse

10 years

Pressure containing parts

In case of corrosion,

contact your local dealer.

NOTICE

▪ The  table  indicates  main  components.  Refer  to  your

maintenance and inspection contract for more details.

▪ The  table  indicates  recommended  intervals  of

replacement cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be  required  sooner.  Recommended  intervals  can  be
used  for  appropriate  maintenance  design  in  terms  of
budgeting  maintenance  and  inspection  fees.  Contact
your dealer for details.

INFORMATION

Damage due to taking apart or cleaning interiors of units by
anyone  other  than  our  authorised  dealers  may  not  be
included in the warranty.

17

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

Summary of Contents for FFA25A2VEB9

Page 1: ...ser reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FFA25A2VEB FFA35A2VEB FFA50A2VEB FFA60A2VEB FFA25A2VEB9 FFA35A2VEB9 FFA50A2VE...

Page 2: ...electrical wiring 17 6 4 4 Specifications of standard wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 19 8 1...

Page 3: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Page 4: ...ed Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmospheres In places where there is machinery that emits...

Page 5: ...5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 4...

Page 6: ...n Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing clo...

Page 7: ...head and make proper tightening impossible Over tightening the terminal screws may break them WARNING After finishing the electrical work confirm that each electrical component and terminal inside th...

Page 8: ...ter describes what you have to do after the box with the indoor unit is delivered on site Keep the following in mind At delivery the unit MUST be checked for damage Any damage MUST be reported immedia...

Page 9: ...5 46 C DB 9 21 C DB 10 15 C WB 18 37 C DB 12 28 C WB 10 27 C DB RXS25 60 10 46 C DB 15 24 C DB 16 18 C WB 18 32 C DB 10 30 C DB Outdoor units Cooling Heating 2MXS50 10 46 C DB 15 24 C DB 16 18 C WB 1...

Page 10: ...ance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial en...

Page 11: ...ce to the floor see below C 295 mm In case of installation with BYFQ60B 300 mm In case of installation with BYFQ60C a Indoor unit b Lighting the figure shows ceiling mounted lighting but recessed ligh...

Page 12: ...or installation INFORMATION This chapter only describes installation instructions specific to the indoor unit For the other instructions see The installation manual of the outdoor unit The installatio...

Page 13: ...5 mm 595 mm 10 mm 12 5 mm A Ceiling opening B Distance between the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Level Make sure the unit is level at a...

Page 14: ...6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f...

Page 15: ...refrigerant to be used Only use installation tools e g manifold gauge set that are exclusively used for R32 or R410A installations to withstand the pressure and to prevent foreign materials e g minera...

Page 16: ...tions Insulation Insulate the refrigerant piping on the indoor unit as follows A B a d c e f b b a d c e f b b 2 4 3 g 1 2 3 4 g A B 1 A Gas piping B Liquid piping a Insulation material field supply b...

Page 17: ...30 V User interface cable Vinyl cords with 0 75 to 1 25 mm sheath or cables 2 core wires Maximum 500 m 6 4 5 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delive...

Page 18: ...t they correspond with the actual installation setup and with the needs of the user Ceiling height Air flow direction Air volume when thermostat control is OFF Time to clean air filter Setting Ceiling...

Page 19: ...power consumption NOTICE Before starting up the system the unit MUST be energised for at least 6 hours The crankcase heater needs to heat up the compressor oil to avoid oil shortage and compressor bre...

Page 20: ...it first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B by removing the stem cap and turning counte...

Page 21: ...hase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The...

Page 22: ...ESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MA...

Page 23: ...ce see the operation manual of the installed user interface 13 Before operation WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been...

Page 24: ...n It may take longer to reach the set temperature for general heating operation than for cooling operation The following operation is performed in order to prevent the heating capacity from dropping o...

Page 25: ...lades while the swing flap is in operation Fingers may become caught or the unit may break down NOTICE The movable limit of the flap is changeable Contact your dealer for details only for double flow...

Page 26: ...result in burnout of these components 16 1 Cleaning the air filter suction grille air outlet and outside panels 16 1 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6...

Page 27: ...in order to dry the interior of the units Refer to 14 2 2 About cooling heating fan only and automatic operation on page 24 for details on fan only operation Turn off the power The user interface dis...

Page 28: ...face and switches 25 000 hours Drain pan 8 years Expansion valve 20 000 hours Solenoid valve 20 000 hours The table assumes the following conditions of use Normal use without frequent starting and sto...