6 Installation

Installer and user reference guide

15

FFA25~60A2VEB(9)
Split system air conditioners
4P550955-4 – 2018.08

When electrical wiring is finished already

1

Start  cooling  operation  (see 

"8.4  To  perform  a  test  run"  on

page 20

).

2

Gradually  pour  approximately  1  l  of  water  through  the  air
discharge  outlet,  and  check  for  leaks  (see 

"When  electrical

wiring is not finished yet" on page 14

).

6.3

Connecting the refrigerant piping

6.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the indoor unit

▪ Connecting the refrigerant piping to the outdoor unit

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Using the stop valves

6.3.2

Precautions when connecting the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF BURNING

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

NOTICE

Take  the  following  precautions  on  refrigerant  piping  into
account:

▪ Avoid  anything  but  the  designated  refrigerant  to  get

mixed into the refrigerant cycle (e.g. air).

▪ Only use R32 or R410A when adding refrigerant. Refer

to  the  outdoor  unit  specifications  for  the  type  of
refrigerant to be used.

▪ Only use installation tools (e.g. manifold gauge set) that

are  exclusively  used  for  R32  or  R410A  installations  to
withstand the pressure and to prevent foreign materials
(e.g.  mineral  oils  and  moisture)  from  mixing  into  the
system.

▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to

mechanical stress.

▪ Protect the piping as described in the following table to

prevent dirt, liquid or dust from entering the piping.

▪ Use  caution  when  passing  copper  tubes  through  walls

(see figure below).

Unit

Installation period

Protection method

Outdoor unit

>1 month

Pinch the pipe

<1 month

Pinch or tape the pipe

Indoor unit

Regardless of the
period

INFORMATION

Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.

6.3.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ ALWAYS use 2 wrenches together when loosening a flare nut.

▪ ALWAYS use a spanner and torque wrench together to tighten the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø6.4

15~17

8.7~9.1

R=0.4~0.8

45° ±2

90°±2

A

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

6.3.4

Pipe bending guidelines

Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).

Summary of Contents for FFA25A2VEB9

Page 1: ...ser reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FFA25A2VEB FFA35A2VEB FFA50A2VEB FFA60A2VEB FFA25A2VEB9 FFA35A2VEB9 FFA50A2VE...

Page 2: ...electrical wiring 17 6 4 4 Specifications of standard wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 19 8 1...

Page 3: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Page 4: ...ed Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmospheres In places where there is machinery that emits...

Page 5: ...5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 4...

Page 6: ...n Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing clo...

Page 7: ...head and make proper tightening impossible Over tightening the terminal screws may break them WARNING After finishing the electrical work confirm that each electrical component and terminal inside th...

Page 8: ...ter describes what you have to do after the box with the indoor unit is delivered on site Keep the following in mind At delivery the unit MUST be checked for damage Any damage MUST be reported immedia...

Page 9: ...5 46 C DB 9 21 C DB 10 15 C WB 18 37 C DB 12 28 C WB 10 27 C DB RXS25 60 10 46 C DB 15 24 C DB 16 18 C WB 18 32 C DB 10 30 C DB Outdoor units Cooling Heating 2MXS50 10 46 C DB 15 24 C DB 16 18 C WB 1...

Page 10: ...ance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial en...

Page 11: ...ce to the floor see below C 295 mm In case of installation with BYFQ60B 300 mm In case of installation with BYFQ60C a Indoor unit b Lighting the figure shows ceiling mounted lighting but recessed ligh...

Page 12: ...or installation INFORMATION This chapter only describes installation instructions specific to the indoor unit For the other instructions see The installation manual of the outdoor unit The installatio...

Page 13: ...5 mm 595 mm 10 mm 12 5 mm A Ceiling opening B Distance between the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Level Make sure the unit is level at a...

Page 14: ...6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f...

Page 15: ...refrigerant to be used Only use installation tools e g manifold gauge set that are exclusively used for R32 or R410A installations to withstand the pressure and to prevent foreign materials e g minera...

Page 16: ...tions Insulation Insulate the refrigerant piping on the indoor unit as follows A B a d c e f b b a d c e f b b 2 4 3 g 1 2 3 4 g A B 1 A Gas piping B Liquid piping a Insulation material field supply b...

Page 17: ...30 V User interface cable Vinyl cords with 0 75 to 1 25 mm sheath or cables 2 core wires Maximum 500 m 6 4 5 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delive...

Page 18: ...t they correspond with the actual installation setup and with the needs of the user Ceiling height Air flow direction Air volume when thermostat control is OFF Time to clean air filter Setting Ceiling...

Page 19: ...power consumption NOTICE Before starting up the system the unit MUST be energised for at least 6 hours The crankcase heater needs to heat up the compressor oil to avoid oil shortage and compressor bre...

Page 20: ...it first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B by removing the stem cap and turning counte...

Page 21: ...hase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The...

Page 22: ...ESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MA...

Page 23: ...ce see the operation manual of the installed user interface 13 Before operation WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been...

Page 24: ...n It may take longer to reach the set temperature for general heating operation than for cooling operation The following operation is performed in order to prevent the heating capacity from dropping o...

Page 25: ...lades while the swing flap is in operation Fingers may become caught or the unit may break down NOTICE The movable limit of the flap is changeable Contact your dealer for details only for double flow...

Page 26: ...result in burnout of these components 16 1 Cleaning the air filter suction grille air outlet and outside panels 16 1 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6...

Page 27: ...in order to dry the interior of the units Refer to 14 2 2 About cooling heating fan only and automatic operation on page 24 for details on fan only operation Turn off the power The user interface dis...

Page 28: ...face and switches 25 000 hours Drain pan 8 years Expansion valve 20 000 hours Solenoid valve 20 000 hours The table assumes the following conditions of use Normal use without frequent starting and sto...

Page 29: ...N OFF button on the user interface is pressed If the operation lamp lights the system is in normal condition To prevent overloading of the compressor motor the air conditioner starts 5 minutes after i...

Page 30: ...s is to prevent refrigerant from remaining in the compressor The unit will stop after 5 to 10 minutes 18 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requir...

Page 31: ......

Page 32: ...4P550955 4 2018 08 Copyright 2017 Daikin...

Reviews: