Application Information
1) Indoor Installation Clearance
Clearance must be provided for the indoor unit from wall and obstacles as shown in
fi
gure below.
Bea
m
Max.
0.3
m
Min 0.5 m
Min 0.5 m
Max.
3.0
m
Min 0.5 m
Floor
Obstacles
The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or more.
2) Outdoor Installation Clearance
Outdoor unit must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth
air
fl
ow. Select the coolest possible place where intake air should not hotter than the outside temperature
(Max. 45°C).
ALL MODELS
A
B
C
D
Minimum Distance
300 mm
1000 mm
300 mm
500 mm
If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil re
fi
nery plant), such substances
may lead to failure the unit.