background image

2

I

NSTALLATION

 

EXAMPLE

;;;;

;;;;

5

2

3

4

1

1. Ceiling slab.

4. Suspension bolt.

2. Anchor.

5. Indoor unit.

3. Long nut or turn-buckle.

Note:

 Mentioned parts are field supplied.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories, refer to the instruction manual
of each optional accessory. Depending on the field conditions, it
may be easier to install optional accessories before the indoor unit
is installed.
1. Install the indoor unit temporarily.

• Attach the hanger bracket to the suspension bolt. Be sure to

fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket.

2

1

2

3

A liquid line and gas line must be provided between the
condensing and the air conditioning unit.

• The outdoor unit is charged with refrigerant.
• Use a pipe cutter and flare suitable for the used refrigerant.
• The liquid line must be connected to the air conditioning unit via

a flare connection. The gas line must be welded directly to the
air conditioning unit piping. In case of a FDY125 unit, both the
liquid line and the gas line must be connected to the air
conditioning via a flare connection.

• In case of flare connections, flare the pipe end neatly to avoid

refrigerants leaks.

• Be sure to use both a spanner and torque wrench together when

connecting or disconnecting pipes to/from the unit (Refer to
Fig. 4).

• Refer to the table below for the dimensions of flare nut spaces.

• If R407C refrigerant is used, apply ether or ester oil around the

flare portions before connecting.

• Refer to the table above to determine the proper tightening

torque. (Overtightening may damage the flare and cause leaks.)

• Check the pipe connector for gas leaks.
• Wrap only the gas line side of the insulation for fitting (union) with

the sealing pad (attached).

V

ACUUM

 

DRYING

 

OF

 

INSTALLATION

Refer to the installation manual of the outdoor unit.

D

RAIN

 

PIPING

 

WORK

 Caution

• The drain hose must slope downward to the outdoor side.
• Do not use a trap in the drain piping.
• Never put the end of the drain in to water.

Coat here with refrigerating machine oil.

1. Field procurement.
2. Washer for hanger bracket.
3. Tighten (double nut).

2. Do not install the unit tilted.

(If the unit is tilted against condensate flow, water can drip out of
the drain pan).
Check if the unit is levelled at all four corners with a water level
(1) or a water-filled vinyl tube (2)( Refer to Fig. 3).

3. Tighten the upper nut.
4. An air filter is installed to prevent dust accumulation on the heat

exchanger this will prolong the lifetime of the unit.

5. Connect the air inlet to the air inlet ducting and the air outlet to

the air outlet ducting. Always provide a flexible connection
between the ducting flanges of the air conditioner and the ducts
to prevent vibrations and noise generation.

 Caution

Ensure that a protective guard is installed in front of the air
outlet to prevent that the fan blades be touched. The protection
must comply with relevant local and national regulations.

R

EFRIGERANT

 

PIPING

 

WORK

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and national
regulations.

For refrigerant piping of outdoor unit, see the installation manual
attached to the outdoor unit.

R = 0.4~0.8

45

° ±

2

90

°±

0.5

A

Pipe size

Tightening torque (N

cm)

12.0 ~ 12.4

3270 ~ 3990 N•cm

(333 ~ 407 kgf•cm)

Ø 9.5

A (mm)

Flare shape

15.4 ~ 15.8

4950 ~ 6030 N•cm

(504 ~ 616 kgf•cm)

Ø 12.7

18.6 ~ 19.0

6180 ~ 7540 N•cm

(630 ~ 770 kgf•cm)

Ø 15.9

22.9 ~ 23.3

9720 ~ 11860 N•cm

(990 ~ 1210 kgf•cm)

Ø 19.1

Summary of Contents for FDY125B7V1

Page 1: ...English Split System air conditioners INSTALLATION MANUAL Installation manual Split System air conditioners FDY125B7V1 FDY200B7V1 FDY250B7V1 FDYP125B7V1 FDYP200B7V1 FDYP250B7V1...

Page 2: ...f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er...

Page 3: ...H 1 2 3 N L P1 P2 X1M X10A X1A X27A X33A X11A X18A X19A A1P X21A X5A X31A X10A X1A X27A X33A X11A X18A X19A A1P X21A X5A X31A C L M H 1 2 3 N L P1 P2 X1M X10A X1A X27A X33A X11A X18A X19A A1P X21A X5A...

Page 4: ...1 2 3 L N P1 P1 P2 1 2 3 P2 1 2 3 L N P1 1 3 2 3 2 3 2 4 5 2 3 6 1 4 5 2 3 1 4 5 2 3 C L M H 1 2 3 N L P1 P2 4PW05089 1A H C L M 1 C M H 1 C L H 1 L M 7 8 11 9 10 M S M S M S 1 P1 P2 1 2 3 P2 P1 P2 1...

Page 5: ...nado da s rie Split Installationsve jled ning Klimaanlag i opdelt sys tem FDY125F7V1 FDY200F7V1 FDY250F7V1 Installation manual Operation manual NOTE TO THE INSTALLER Be sure to instruct the customer h...

Page 6: ...connector for gas leaks Wrap only the gas line side of the insulation for fitting union with the sealing pad attached VACUUM DRYING OF INSTALLATION Refer to the installation manual of the outdoor unit...

Page 7: ...nect the interconnection wiring from outdoor to indoor to the 1 2 3 terminal 1 using a separate power supply wire to connect to power supply of the indoor unit fan motor to the L N terminal Remote con...

Page 8: ...r part of the remote controller 2 Turn the main sub changeover switch on one of the two remote controller PC boards to S see figure 11 Leave the switch of the other remote controller set to M 1 Remote...

Page 9: ...EN K1F Magnetic contactor M1F M1F Motor Fan R1T Thermistor air R2T Thermistor Coil RC Signal receiver circuit RyF1 Magnetic relay fan SS1 Selector switch Emergency T1R Transformer only for FDYP125 200...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10621 1...

Reviews: