6 Installation

Installer reference guide

13

FDXM25~60F3V1B(9)
Split system air conditioners
4P550955-1 – 2018.07

NOTICE

Take  the  following  precautions  on  refrigerant  piping  into
account:

▪ Avoid  anything  but  the  designated  refrigerant  to  get

mixed into the refrigerant cycle (e.g. air).

▪ Only use R32 or R410A when adding refrigerant. Refer

to  the  outdoor  unit  specifications  for  the  type  of
refrigerant to be used.

▪ Only use installation tools (e.g. manifold gauge set) that

are  exclusively  used  for  R32  or  R410A  installations  to
withstand the pressure and to prevent foreign materials
(e.g.  mineral  oils  and  moisture)  from  mixing  into  the
system.

▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to

mechanical stress.

▪ Protect the piping as described in the following table to

prevent dirt, liquid or dust from entering the piping.

▪ Use  caution  when  passing  copper  tubes  through  walls

(see figure below).

Unit

Installation period

Protection method

Outdoor unit

>1 month

Pinch the pipe

<1 month

Pinch or tape the pipe

Indoor unit

Regardless of the
period

INFORMATION

Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.

6.3.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ ALWAYS use 2 wrenches together when loosening a flare nut.

▪ ALWAYS use a spanner and torque wrench together to tighten the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø6.4

15~17

8.7~9.1

R=0.4~0.8

45° ±2

90°±2

A

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

6.3.4

Pipe bending guidelines

Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).

6.3.5

To flare the pipe end

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

1

Cut the pipe end with a pipe cutter.

2

Remove  burrs  with  the  cut  surface  facing  down  so  that  the
chips do NOT enter the pipe.

a

b

a

Cut exactly at right angles.

b

Remove burrs.

3

Remove  the  flare  nut  from  the  stop  valve  and  put  the  flare  nut
on the pipe.

4

Flare  the  pipe.  Set  exactly  at  the  position  as  shown  in  the
following figure.

A

Flare tool for

R410A or R32

(clutch type)

Conventional flare tool

Clutch type

(Ridgid-type)

Wing nut type

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

5

Check that the flaring is properly made.

a

b

c

a

Flare’s inner surface MUST be flawless.

b

The pipe end MUST be evenly flared in a perfect circle.

c

Make sure the flare nut is fitted.

6.3.6

To connect the refrigerant piping to the
indoor unit

CAUTION

Install refrigerating pipe or components in a position where
they  are  unlikely  to  be  exposed  to  any  substance  which
may corrode refrigerant containing components, unless the
components  are  constructed  of  materials  which  are
inherently  resistant  to  being  corroded  or  are  suitably
protected against being so corroded.

Summary of Contents for FDXM35F3V1B

Page 1: ...reference guide Split system air conditioners English Installer reference guide Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDX...

Page 2: ...eaks 14 6 4 Connecting the electrical wiring 14 6 4 1 About connecting the electrical wiring 14 6 4 2 Precautions when connecting the electrical wiring 14 6 4 3 Guidelines when connecting the electric...

Page 3: ...ace at the product Instructions for shutting down the system in case of an emergency Name and address of fire department police and hospital Name address and day and night telephone numbers for obtain...

Page 4: ...110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 410 420 430 440 450 460 470 480 490 500 510 520 530 540 550 1 8 2 2 2 2 4 2 6 2...

Page 5: ...legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplat...

Page 6: ...ncy electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of different thicknesses to the power terminal block sl...

Page 7: ...to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box Keep the foll...

Page 8: ...t are designed to provide reasonable protection against such interference However there is no guarantee that interference will not occur in a particular installation It is therefore recommended to ins...

Page 9: ...ckness t a 6 4 mm 1 4 Annealed O 0 8 mm t 9 5 mm 3 8 12 7 mm 1 2 a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thic...

Page 10: ...uidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the optional equipment Depending on the field condition...

Page 11: ...re used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct work The ducting is to be field su...

Page 12: ...to discharge the water if the drain pump is not used or before maintenance Insert and remove the drain plug gently Excessive force may deform the drain socket of the drain pan Pull out the plug Do NOT...

Page 13: ...wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque...

Page 14: ...ed joints soap water may contain ammonia which causes a corrosive effect between the brass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 k...

Page 15: ...e the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Wrap the cables with the sealing material accessory to prevent water from enter...

Page 16: ...hen using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION...

Page 17: ...phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA T...

Page 18: ...GH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR...

Page 19: ...ecified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to i...

Page 20: ...4P550955 1 2018 07 Copyright 2017 Daikin...

Reviews: