background image

6 Installation

Installer reference guide

12

FDXM25~60F3V1B(9)

Split system air conditioners

4P550955-1 – 2018.07

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check  for  water  leaks  (see 

"To  check  for  water  leaks"  on

page 12

).

4

Install the insulation piece (drain pipe).

5

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with cable ties.

6

Connect the drain piping to the drain hose.

≤4 mm

A

A'

A-A'

A

A'

f

6

5

2

c

e

4

b

a

d

b

a

d

c

3

1

2~6

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Insulation piece (drain pipe) (accessory)

f

Drain piping (field supply)

NOTICE

▪ Do NOT remove the drain pipe plug. Water might leak

out.

▪ Use  the  drain  outlet  only  to  discharge  the  water  if  the

drain pump is not used or before maintenance.

▪ Insert  and  remove  the  drain  plug  gently.  Excessive

force may deform the drain socket of the drain pan.

Pull out the plug.

▪ Do NOT wiggle the plug up and down.

a

Push in the plug.

▪ Set the plug and push it in using a Phillips screwdriver.

a

b

a

Drain plug

b

Phillips screwdriver

To check for water leaks

Gradually  pour  approximately  1  l  of  water  in  the  drain  pan,  and
check for water leaks.

e

d

a

b

c

a

Air outlet

b

Portable pump

c

Bucket

d

Refrigerant pipes

e

Drain outlet

6.3

Connecting the refrigerant piping

6.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the outdoor unit

▪ Connecting the refrigerant piping to the indoor unit

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Brazing

▪ Using the stop valves

6.3.2

Precautions when connecting the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF BURNING

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

Summary of Contents for FDXM35F3V1B

Page 1: ...reference guide Split system air conditioners English Installer reference guide Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDX...

Page 2: ...eaks 14 6 4 Connecting the electrical wiring 14 6 4 1 About connecting the electrical wiring 14 6 4 2 Precautions when connecting the electrical wiring 14 6 4 3 Guidelines when connecting the electric...

Page 3: ...ace at the product Instructions for shutting down the system in case of an emergency Name and address of fire department police and hospital Name address and day and night telephone numbers for obtain...

Page 4: ...110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 410 420 430 440 450 460 470 480 490 500 510 520 530 540 550 1 8 2 2 2 2 4 2 6 2...

Page 5: ...legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplat...

Page 6: ...ncy electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of different thicknesses to the power terminal block sl...

Page 7: ...to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box Keep the foll...

Page 8: ...t are designed to provide reasonable protection against such interference However there is no guarantee that interference will not occur in a particular installation It is therefore recommended to ins...

Page 9: ...ckness t a 6 4 mm 1 4 Annealed O 0 8 mm t 9 5 mm 3 8 12 7 mm 1 2 a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thic...

Page 10: ...uidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the optional equipment Depending on the field condition...

Page 11: ...re used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct work The ducting is to be field su...

Page 12: ...to discharge the water if the drain pump is not used or before maintenance Insert and remove the drain plug gently Excessive force may deform the drain socket of the drain pan Pull out the plug Do NOT...

Page 13: ...wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque...

Page 14: ...ed joints soap water may contain ammonia which causes a corrosive effect between the brass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 k...

Page 15: ...e the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Wrap the cables with the sealing material accessory to prevent water from enter...

Page 16: ...hen using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION...

Page 17: ...phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA T...

Page 18: ...GH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR...

Page 19: ...ecified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to i...

Page 20: ...4P550955 1 2018 07 Copyright 2017 Daikin...

Reviews: