8.  DUCT WORK

Pay the utmost attention to the following items and 

conduct the duct work.

• 

Check that the duct is not in excess of the setting range of 
external static pressure for the unit. (Refer to the technical 
datasheet for the setting range.)

• 

Attach a canvas duct each to the air outlet and air inlet so 
that the vibration of the equipment will not be transmitted to 
the duct or ceiling.  
Use a sound-absorbing material (insulation material) for the 
lining of the duct and apply vibration insulation rubber to the 
suspension bolts.

• 

At the time of duct welding, perform the curing of the duct so 
that the sputter will not come in contact with the drain pan for 

the filter.

• 

If the metal duct passes through a metal lath, wire lath, or 
plate of a wooden structure, separate the duct and wall 
electrically.

• 

Be sure to heat insulate the duct for the prevention of 
dew condensation. (Material: Glass wool or styrene foam; 
Thickness: 1 inch (25mm))

• 

Be sure to attach the field supply air filter to the air inlet of the 
unit or field supply inlet in the air passage on the air suction 
side. (Be sure to select an air filter with a duct collection 
efficiency of 50 weight percent.)

• 

Explain the operation and washing methods of the locally 

procured components (i.e., the air filter, air inlet grille, and air 

outlet grille) to the user.

• 

Locate the air outlet grille on the indoor side for the 
prevention of drafts in a position where indirect contact with 
people.

• 

The air conditioner incorporates a function to adjust the fan 
to rated speed automatically. 

(10. FIELD SETTING) 

Therefore, do not use booster fans midway in the duct.

Connection method of ducts on air inlet and outlet sides.

• 

Connect the field supply duct in alignment with the inner side 
of the flange.

• 

Connect the flange and unit with the duct flange connection 

screw (3).

• 

Wrap aluminium tape around the flange and duct joint in 

order to prevent air leakage.

Unit

Insulation material 

(field supply)

Canvas duct 
(field supply)

Flange on air inlet side 
(provided with the unit)

Insulation material 

(field supply)

Air inlet

Air outlet

Duct flange 
connection
screws (3)

Duct flange 
connection
screws (3)

Flange on air outlet side 
(provided with the unit)

Fig. 19

 CAUTION

Connect the flange and unit with the flange connection screw 

(3) regardless of whether the duct is connected to the air 
inlet side.

9.  ELECTRIC WIRING WORK

9-1  GENERAL INSTRUCTIONS

• 

Make certain that all electric wiring work is carried out by 

qualified personnel according to the applicable legislation 

and this installation manual, using a separate dedicated 
circuit. 

Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shock or a fire.

• 

Make sure to install a ground fault circuit interrupter. 

Failure to do so may cause electric shock and a fire.

• 

Do not turn on the power supply (branch switch, branch 

overcurrent circuit breaker) until all the works are finished.

• 

Multiple number of indoor units are connected to one 
outdoor unit. Name each indoor unit as A-unit, B-unit ….. and 
the like. When these indoor units are wired to the outdoor 
unit, always wire the indoor unit to the terminal indicated 
with the same symbol on the terminal block. If the wiring and 
the piping are connected to the different indoor units and 
operated, it will result in malfunction.

• 

Make sure to ground the air conditioner. 
Grounding resistance should be according to applicable 
legislation.

• 

Do not connect the ground wiring to gas or water pipings, 
lightning conductor or telephone ground wiring.

• 

Gas piping .................Ignition or explosion may occur if 
the gas leaks.

• 

Water piping ..............Hard vinyl tubes are not effective 
grounds.

• 

Lightning conductor or telephone ground wiring ...............
 Electric potential may rise abnormally if struck by a 
lightning bolt.

• 

For electric wiring work, refer to also the “WIRING 
DIAGRAM” attached to the electrical wiring box cover.

• 

Carry out wiring between the outdoor units, indoor units and 
the remote controllers according to the wiring diagram.

• 

Carry out installation and wiring of the remote controller 
according to the “installation manual” attached to the remote 
controller.

• 

Do not touch the Printed Circuit Board assembly. It may 
cause malfunction.

 WARNING

• 

Do not use tapped wires, extension cords, or starburst 
connections, as they may cause overheating, electric 

shock, or fire.

• 

Do not use locally purchased electrical parts inside the 
product. (Do not branch the power for the drain pump, 
etc., from the terminal block.) Doing so may cause electric 

shock or fire.

• 

Do not connect the power wire to the indoor unit. Doing so 

may cause electric shock or fire.

 CAUTION

• 

When clamping wiring, use the included clamping 
material to prevent outside pressure being exerted on 

the wiring connections and clamp firmly. When doing the 

wiring, make sure the wiring is neat and does not cause 
the electrical wiring box cover to stick up, then close the 

cover firmly.

• 

Outside the unit, separate the low voltage wiring 
(remote controller wiring) and high voltage wiring (wiring 
between units, ground, and other power wiring) at least 
2 in. so that they do not pass through the same place 
together. Proximity may cause electrical interference, 
malfunctions, and breakage.

11 English

01_EN_3P500432-1.indd   11

10/24/2017   18:32:35

Summary of Contents for FDMQ09RVJU

Page 1: ...NDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación MODELS FDMQ09RVJU FDMQ12RVJU FDMQ15RVJU FDMQ18RVJU FDMQ24RVJU English Français Español Manuel dinstallation ...

Page 2: ...s and other metal or wood parts including plastic packing materials used for transportation may cause injuries or death by suffocation WARNING Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take measur...

Page 3: ...nsmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the following locati...

Page 4: ...for hanger bracket Quantity 4 2 8 Shape Small Gray Name 12 Conduit mounting plate Others Quantity 1 Operation manual Installation manual Warranty Shape 2 2 OPTIONAL ACCESSORIES A remote controller is required for the indoor unit Select a remote controller from the table below according to user request and install in an appropriate place Remote controller type Wired type BRC1E73 Wireless type BRC08...

Page 5: ...especially operating different functions and adjusting the temperature by having them carry out operations while looking at the manual 3 CHOOSING AN INSTALLATION SITE Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacked and do not apply force to the piping refrigerant and drain and air outlet flange If the temperature and humidity in the ceiling is likely to exc...

Page 6: ...and inspection port 2 on the bottom of the product Fig 4 arrow A 1 3 Inspection port 3 on the bottom of the product and on the bottom side of the electrical wiring box Fig 4 arrow A 2 Electrical wiring box 11 13 16 300 or more Ceiling Inspection port In the case of 1 1 unit inch mm Fig 3 1 Electrical wiring box 31 1 2 800 7 7 8 200 or less C B D Suspension bolt pitch Suspension bolt 4 24 13 16 630...

Page 7: ...ts before installing the indoor unit Secure a sufficient maintenance space for the filter chamber and peripheral components before installing the indoor unit Suction flange Replacement Chamber cover Fig 5 5 INDOOR UNIT INSTALLATION Depending on the optional parts it may be easier to attach them before installing the indoor unit Refer to also the installation manual attached to the optional parts As...

Page 8: ...e Wing nut type Imperial type Conventional flare tool Flaring Die WARNING Do not apply mineral oil to the flare Prevent mineral oil from getting into the system as this would reduce the service life of the units Never use piping which has been used for previous installations Only use parts which are delivered with this unit Never install a dryer to this R410A unit in order to guarantee its service ...

Page 9: ...ng insulation 4 and 5 flare nut section both the gas and liquid piping Make sure to bring the seam of fitting insulation 4 and 5 to the top Gas piping Liquid piping Fitting insulation 4 Liquid Piping Insulation Procedure Unit Unit Clamp 8 Clamp 8 Piping insulating material field supply Gas Piping Insulation Procedure Fitting insulation 5 Piping insulating material unit Bring the seam to the top Fla...

Page 10: ...in hose 2 the socket or the clamp metal 1 may be damaged Wrap the vinyl tape around the end of the clamp metal 1 so that the sealing pad Large 6 to be used at the next process may not be damaged with the clamp end or bend the tip of the clamp metal 1 inward as shown Refer to Fig 14 In case of sticking vinyl tape Tightened part approx 90 Stick vinyl tape without tearing the sealing pad Large 6 Viny...

Page 11: ...g grounding must be carried out by a qualified electrician If a qualified person is not present after the electric wiring work is finished check the drainage accord ing to the method specified in When the electric wiring work is finished 1 Open the electrical wiring box cover and connect the ground wiring to the ground terminal 2 Make sure the electrical wiring box cover is closed before turning o...

Page 12: ...ation and this installation manual using a separate dedicated circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shock or a fire Make sure to install a ground fault circuit interrupter Failure to do so may cause electric shock and a fire Do not turn on the power supply branch switch branch overcurrent circuit breaker until all the wor...

Page 13: ...OR WIRING For connection to the terminal block use ring type crimp style terminals with insulation sleeve or insulate the wirings properly Insulation sleeve Ring type crimp style terminals Wiring Fig 21 Connect the terminal as shown in Fig 22 When installing a single core wire Do not carry out soldering finish when stranded wirings are used Otherwise the loosening of wiring may result in abnormal ...

Page 14: ...oor units and ground wiring Match the numbers Connection method of wiring between the indoor and outdoor units Terminal block X1M for wiring between the indoor and outdoor units Power supply terminals X1M Indoor unit 1 2 3 1 2 3 Connect the wiring through the electrical wiring box up to the sheathed part Wiring between the indoor and outdoor units high voltage Ground wiring high voltage Remote con...

Page 15: ...for the setting range of external static pressure 1 Check that the electrical wiring and duct work have been completed If the closing damper is set midway be sure to check that the damper is opened Furthermore check that the air passage on the suction side is provided with an air filter field supply 2 If air conditioner has more than one air outlet and air inlet be sure to make adjustments so that...

Page 16: ...0 20 0 01 More contaminated Approx 1250 hrs 02 With indication 3 01 No indication 02 Use No indication setting when cleaning indication is not necessary such as the case of periodical clean ing being carried out 10 4 REMOTE CONTROL SETTINGS In the case of using a wireless remote controller In the case of using a wireless remote controller address settings for the wireless remote controller are req...

Page 17: ...ettings menu is displayed 6 Select Test Operation in the service settings menu and press Menu OK button Basic screen returns and normal operation is conducted Test operation will stop automatically after 15 30 minutes To stop the operation press On Off button Basic screen 1 2 Cool Return Clean the filter Set to Cool 68F Press and hold Cancel button for 4 seconds or longer during backlight lit Servi...

Page 18: ... up to 90 seconds following the application of power to the indoor unit This is normal and does not indicate a malfunction Diagnose with the display on the liquid crystal display remote controller With the wired remote controller When the operation stops due to a malfunction operation lamp blinks and the malfunction code is indicated on the liquid crystal display In such a case diagnose the fault ...

Page 19: ...r condition CJ Remote controller air thermistor malfunction Remote controller thermo does not function but body thermo operation is enabled E0 Action of safety device Outdoor unit E1 Outdoor Printed Circuit Board failure Outdoor unit E5 Compressor motor lock malfunction Outdoor unit E6 Compressor motor lock by over current Outdoor unit E7 Outdoor fan motor lock malfunction Outdoor unit Outdoor fan...

Page 20: ...rror System setting error of the simultaneous on off multi split type UE Transmission error between indoor unit and centralized remote controller UC Remote controller address setting error CAUTION After test operation is completed check the items mentioned in the clause 2 2 Items to be checked at time of delivery on page 4 If the interior finish work is not completed when the test operation is fin...

Page 21: ...English English 20 ...

Page 22: ...The two dimensional bar code is a manufacturing code 3P500432 1 M17B179 1711 HT ...

Reviews: