4.6
Finishing the outdoor unit
installation
4.6.1
To finish the outdoor unit installation
1
Insulate and fix the refrigerant piping and interconnection cable
as follows:
f
b
a
e
d
c
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
2
Install the service cover.
4.6.2
To check the insulation resistance of the
compressor
NOTICE
If, after installation, refrigerant accumulates in the
compressor, the insulation resistance over the poles can
drop, but if it is at least 1 MΩ, then the unit will not break
down.
▪ Use a 500 V mega-tester when measuring insulation.
▪ Do not use a mega-tester for low-voltage circuits.
1
Measure the insulation resistance over the poles.
If
Then
≥1 MΩ
Insulation resistance is OK. This procedure
is finished.
<1 MΩ
Insulation resistance is not OK. Go to the
next step.
2
Turn ON the power and leave it on for 6 hours.
Result:
The compressor will heat up and evaporate any
refrigerant in the compressor.
3
Measure the insulation resistance again.
5
Commissioning
Please provide the eco design data according to (EU)2016/2281 to
the customer. This data can be found in the installer reference guide
or via the Daikin website.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.
5.1
Checklist before commissioning
After the installation of the unit, first check the items listed below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.
You read the complete installation instructions, as
described in the
installer reference guide
.
The
indoor units
are properly mounted.
In case a wireless user interface is used: The
indoor unit
decoration panel
with infrared receiver is installed.
The
outdoor unit
is properly mounted.
The following
field wiring
has been carried out according
to this document and the applicable legislation:
▪ Between the local supply panel and the outdoor unit
▪ Between the outdoor unit and the indoor unit (master)
▪ Between the indoor units
There are NO
missing phases
or
reversed phases
.
The system is properly
earthed
and the earth terminals
are tightened.
The
fuses
or locally installed protection devices are
installed according to this document, and have NOT been
bypassed.
The
power supply voltage
matches the voltage on the
identification label of the unit.
There are NO
loose connections
or damaged electrical
components in the switch box.
The
insulation resistance
of the compressor is OK.
There are NO
damaged components
or
squeezed
pipes
on the inside of the indoor and outdoor units.
There are NO
refrigerant leaks
.
The correct pipe size is installed and the
pipes
are
properly insulated.
The
stop valves
(gas and liquid) on the outdoor unit are
fully open.
5.2
To perform a test run
This task is only applicable when using the BRC1E52 or BRC1E53
user interface. When using any other user interface, see the
installation manual or service manual of the user interface.
NOTICE
Do not interrupt the test run.
INFORMATION
Backlight.
To perform an ON/OFF action on the user
interface, the backlight does not need to be lit. For any
other action, it needs to be lit first. The backlight is lit for
±30 seconds when you press a button.
1
Perform introductory steps.
#
Action
1
Open the liquid stop valve and gas stop valve by
removing the cap and turning counterclockwise with a
hex wrench until it stops.
2
Close the service cover to prevent electric shocks.
3
Turn ON power for at least 6 hours before starting
operation to protect the compressor.
4
On the user interface, set the unit to cooling operation
mode.
2
Start the test run
#
Action
Result
1
Go to the home menu.
Cool
Set to
28
°C
3
0
Summary of Contents for FDMF48AVMK
Page 1: ...FDMF48AVMK FDMF54AVMK RZF48AYMK RZF54AYMK 3P640554 1 KA...
Page 2: ...1 FDMF48AVMK FDMF54AVMK a certain product or domain against unsafe practices...
Page 3: ...2...
Page 4: ...3...
Page 5: ...4 8...
Page 6: ...5 48 54 48 54 1500 1538 1800 8 8 8 7...
Page 7: ...6...
Page 9: ...8...
Page 10: ...9...
Page 11: ...10...
Page 12: ...11 48 54...
Page 13: ...12...
Page 14: ...13...
Page 15: ...14...
Page 16: ...15 48 54...
Page 17: ...16...
Page 18: ...17...
Page 19: ...18...
Page 21: ...20...
Page 34: ...33...
Page 35: ...34 FDMF48AVMK FDMF54AVMK RZF48AYMK RZF54AYMK...
Page 36: ...35...
Page 37: ...36...
Page 38: ...37...
Page 39: ...38...
Page 40: ...39 RZF48AYMK RZF54AYMK...
Page 41: ...40...
Page 42: ...41...
Page 43: ...42...
Page 44: ...43...
Page 45: ...44...
Page 46: ...45...
Page 47: ......
Page 49: ......
Page 50: ......
Page 51: ...3P640554 1 KB...
Page 52: ...44...
Page 53: ...43...
Page 54: ...42...
Page 55: ...41...
Page 56: ...40...
Page 57: ...39...
Page 58: ...38...
Page 59: ...37...
Page 60: ...36...
Page 61: ...35...
Page 62: ...34...
Page 63: ...33...
Page 64: ...32...
Page 65: ...31...
Page 66: ...30...
Page 67: ...29...
Page 68: ...28...
Page 69: ...27...
Page 70: ...26...
Page 71: ...25...
Page 72: ...24...
Page 73: ...23...
Page 74: ...22...
Page 75: ...21...
Page 76: ...20...
Page 77: ...19...
Page 78: ...18...
Page 79: ...17...
Page 80: ...16...
Page 81: ...15...
Page 82: ...14...
Page 83: ...13...
Page 84: ...12...
Page 85: ...11...
Page 86: ...10...
Page 87: ...9...
Page 88: ...8...
Page 89: ...7...
Page 90: ...6...
Page 91: ...5...
Page 92: ...4...
Page 93: ...3...
Page 94: ...2...
Page 95: ...1...