25
NOTICE
Make sure to use a recommended bubble test solution
from your wholesaler. Do not use soap water, which may
cause cracking of flare nuts (soap water may contain salt,
which absorbs moisture that will freeze when the piping
gets cold), and/or lead to corrosion of flared joints (soap
water may contain ammonia which causes a corrosive
effect between the brass flare nut and the copper flare).
1
Charge the system with nitrogen gas up to a gauge pressure of
at least
200
kPa
(2
bar). It is recommended to pressurize to
3000 kPa (30 bar) in order to detect small leaks.
2
Check for leaks by applying the bubble test solution to all
connections.
3
Discharge all nitrogen gas.
4.3.3
To perform vacuum drying
NOTICE
▪ Connect the vacuum pump to
both
the service port of
the gas stop valve and the service port of the liquid
stop valve to increase efficiency.
▪ Make sure that the gas stop valve and liquid stop valve
are firmly closed before performing the leak test or
vacuum drying.
1
Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).
2
Leave as is for 4-5 minutes and check the pressure:
If the pressure…
Then…
Does not change
There is no moisture in the
system. This procedure is
finished.
Increases
There is moisture in the
system. Go to the next step.
3
Vacuum the system for at least
2
hours to a manifold pressure
of −0.1 MPa (−1 bar).
4
After turning the pump OFF, check the pressure for at least
1 hour.
5
If you do NOT reach the target vacuum or CANNOT maintain
the vacuum for 1 hour, do the following:
▪ Check for leaks again.
▪ Perform vacuum drying again.
NOTICE
Make sure to open the stop valves after installing the
refrigerant piping and performing vacuum drying. Running
the system with the stop valves closed may break the
compressor.
4.4
Charging refrigerant
4.4.1
About charging refrigerant
The outdoor unit is factory charged with refrigerant, but in some
cases the following might be necessary:
What
When
Charging additional refrigerant
When the total liquid piping
length is more than specified
(see later).
Completely recharging refrigerant
Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's
external
refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists
of the following stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is
done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's
external
refrigerant piping is checked (leak
test, vacuum drying).
3 Vacuum drying on the outdoor unit's
internal
refrigerant piping is
performed.
NOTICE
Before completely recharging, perform vacuum drying on
the outdoor unit's
internal
refrigerant piping as well.
NOTICE
To perform vacuum drying or a complete recharge of the
outdoor unit’s internal refrigerant piping it is necessary to
activate the vacuum mode (see
"To activate/deactivate the
vacuum mode field
setting"
on
page
12
) which will open
required valves in the refrigerant circuit so the vacuuming
process or recharge of refrigerant can be done properly.
▪ Before vacuum drying or recharging, activate field
setting "vacuum mode".
▪ After finishing vacuum drying or recharging, deactivate
field setting "vacuum mode".
WARNING
Some sections of the refrigerant circuit may be isolated
from other sections caused by components with specific
functions (e.g. valves). The refrigerant circuit therefore
features additional service ports for vacuuming, pressure
relief or pressurizing the circuit.
In case it is required to perform
brazing
on the unit, ensure
that there is no pressure remaining inside the unit. Internal
pressures need to be released with ALL the service ports
indicated on the figures below opened. The location is
depending on model type.
Summary of Contents for FDMF48AVMK
Page 1: ...FDMF48AVMK FDMF54AVMK RZF48AYMK RZF54AYMK 3P640554 1 KA...
Page 2: ...1 FDMF48AVMK FDMF54AVMK a certain product or domain against unsafe practices...
Page 3: ...2...
Page 4: ...3...
Page 5: ...4 8...
Page 6: ...5 48 54 48 54 1500 1538 1800 8 8 8 7...
Page 7: ...6...
Page 9: ...8...
Page 10: ...9...
Page 11: ...10...
Page 12: ...11 48 54...
Page 13: ...12...
Page 14: ...13...
Page 15: ...14...
Page 16: ...15 48 54...
Page 17: ...16...
Page 18: ...17...
Page 19: ...18...
Page 21: ...20...
Page 34: ...33...
Page 35: ...34 FDMF48AVMK FDMF54AVMK RZF48AYMK RZF54AYMK...
Page 36: ...35...
Page 37: ...36...
Page 38: ...37...
Page 39: ...38...
Page 40: ...39 RZF48AYMK RZF54AYMK...
Page 41: ...40...
Page 42: ...41...
Page 43: ...42...
Page 44: ...43...
Page 45: ...44...
Page 46: ...45...
Page 47: ......
Page 49: ......
Page 50: ......
Page 51: ...3P640554 1 KB...
Page 52: ...44...
Page 53: ...43...
Page 54: ...42...
Page 55: ...41...
Page 56: ...40...
Page 57: ...39...
Page 58: ...38...
Page 59: ...37...
Page 60: ...36...
Page 61: ...35...
Page 62: ...34...
Page 63: ...33...
Page 64: ...32...
Page 65: ...31...
Page 66: ...30...
Page 67: ...29...
Page 68: ...28...
Page 69: ...27...
Page 70: ...26...
Page 71: ...25...
Page 72: ...24...
Page 73: ...23...
Page 74: ...22...
Page 75: ...21...
Page 76: ...20...
Page 77: ...19...
Page 78: ...18...
Page 79: ...17...
Page 80: ...16...
Page 81: ...15...
Page 82: ...14...
Page 83: ...13...
Page 84: ...12...
Page 85: ...11...
Page 86: ...10...
Page 87: ...9...
Page 88: ...8...
Page 89: ...7...
Page 90: ...6...
Page 91: ...5...
Page 92: ...4...
Page 93: ...3...
Page 94: ...2...
Page 95: ...1...