8

English

Installation is possible when ceiling opening dimensions is as follows

When installing the unit within the frame for fixing false ceiling.

NOTE

Installation is possible with a ceiling dimension of 35-7/8in. (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 13/16in., the spacing between the ceiling and the unit should be 1-3/8in. or 
less. If the spacing between ceiling and the unit is over 1-3/8in., attach ceiling material to

part or 

recover the ceiling.

(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)

Refer to the paper pattern for installation (5) for ceiling opening dimensions.

Create the ceiling opening required for installation. From the side of the opening to the casing outlet, 
implement the refrigerant and drain piping and wiring for remote controller (unnecessary for wireless 
type) and indoor-outdoor unit casing outlet. Refer to “6. REFRIGERANT PIPING WORK”, “7. DRAIN 
PIPING WORK” and “8. ELECTRIC WIRING WORK”.

After making an opening in the ceiling, it may be necessary to reinforce ceiling beams to keep the ceiling 
level and to prevent it from vibrating. Consult the builder for details.

(3) Install the suspension bolts.

(Use either a M8~M10 size bolt or the equivalent)
Use a hole-in anchor for existing ceilings, and a 
sunken insert, sunken anchor or other field sup-
plied parts for new ceilings to reinforce the ceiling 
to bear the weight of the unit. Adjust clearance 
(2-4in.) from the ceiling before proceeding 
further.

NOTE

All the above parts are field supplied.

(Dimension inside fr

ame)

33-1/16

35-7/8

35-7/8

(Dimension inside frame)

33-1/16

Fig. 6

33-7/8

(Opening dimension inside 
the flame for ceiling)

Frame

13/16

33-7/8 – *35-7/8

(Ceiling-panel 
overlapping dimension)

False 
ceiling

(Ceiling opening dimension)

13/16

Fig. 7

(Unit: in.)

Ceiling material

1-3/8

Fig. 8

1-3/8

(Unit: in.)

2-4

Ceiling slab

Suspension bolt

Long nut or turn-buckle

Anchor

False ceiling

<installation example>

Fig. 9

(Unit: in.)

01_EN_3P161684-6K.fm  Page 8  Friday, September 16, 2011  10:00 PM

Summary of Contents for FCQ18PAVJU

Page 1: ...tions carefully before installation Keep this manual in a handy place for future reference Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ul...

Page 2: ...jury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may resul...

Page 3: ...g Before touching electrical parts turn off the unit Be sure to install a ground fault circuit interrupter if one is not already available This helps prevent electrical shocks or fire Securely fasten...

Page 4: ...nimals making contact with electrical parts can cause malfunctions smoke or fire Instruct the customer to keep the area around the unit clean NOTE Install the power supply and control wires for the in...

Page 5: ...air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 ACCESSORIES Check the following accessories a...

Page 6: ...outdoor unit fully installed The unit may malfunction or the compo nents burn out Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may d...

Page 7: ...s approval which matches the following conditions A location from which cool warm air will reach the whole room A location with no objects blocking the air passage A location where drainage can be don...

Page 8: ...have to be shut off if two three or four corner shut off directions are selected See the shut off materials sold separately instal lation manual for details 4 Use suspension bolts for installation Ch...

Page 9: ...to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 8 ELECTRIC WIRING WORK After making an opening in the ceiling it may be necessary to reinforce ceiling beams to keep the ceiling level and to prev...

Page 10: ...uilder or carpenter for details The center of the ceiling opening is indicated on the paper pattern for installation The center of the unit is indicated on the triangular mark to the unit bottom and o...

Page 11: ...and 1 3 in 1 For new ceilings 2 3 Perform steps 1 4 1 5 in 1 For new ceilings 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit...

Page 12: ...ecting pipes to from the unit Refer to Fig 14 Refer to Table 3 for the dimensions of flare nut spaces When connecting the flare nut apply ester oil or ether oil to the flare section outside only and s...

Page 13: ...ine Exposed piping may cause condensation or burns on contact Pipe size Further tightening angle Recommended arm length of tool 1 4 60 to 90 degrees Approx 6in 3 8 60 to 90 degrees Approx 8in 1 2 30 t...

Page 14: ...ig 17 7 DRAIN PIPING WORK 1 Rig drain piping As for drain work perform piping in such a manner that water can be drained properly Employ a pipe with either the same diameter or with the diameter large...

Page 15: ...stall according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 After piping work is finished check if drainage flows smooth...

Page 16: ...ater into the drain pan through the blow off mouth on the left hand side of the drain socket Make sure not to pour water over the drain pump or any electric parts including those of the drain pump Whe...

Page 17: ...apable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire con nected to the o...

Page 18: ...ound wire to the ground terminal In doing this pull the wires inside through the hole and fix the wires securely with the included clamp 4 2 points Remote controller wires not necessary for slave unit...

Page 19: ...ectrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block...

Page 20: ...rminal block for remote controller Control box cover P1 P2 Wiring diagram Backside of control box cover Remote controller wiring Power supply terminal block Insulation tube 16 3P Remote controller wir...

Page 21: ...er supply ground and other power wiring at least 2in so that they do not pass through the same place together Proximity may cause electrical interference malfunctions and breakage 9 2 Wiring example W...

Page 22: ...P2 F1 F2 T1 T2 Power supply 208 230V 1 60Hz Control box Outdoor unit Indoor unit Remote controller L1 L2 Fig 30 P1 P2 P1 P2 For use with 2 remote controllers L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 F1 F2 T1...

Page 23: ...off the upper part The remote controller PC board is attached to the upper part of remote controller Refer to Fig 31 2 Turn the main sub changeover switch on one of the two remote controller PC board...

Page 24: ...11 FIELD SETTING and 12 TEST RUN first Refer to the installation manual attached to the decoration panel After installing the decoration panel ensure that there is no space between the unit body and...

Page 25: ...2 The figure of the ceiling height is for the all round outlet For the settings for four direction part of corner closed off three direction and two direction outlets see the installation manual supp...

Page 26: ...e 6 is displayed there may be a problem with the wiring or power supply so check the wiring again Table 6 If the decoration panel is installed on the indoor unit during the test run check the operatio...

Page 27: ...3P161684 6K EM11A061 1110 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA info daikinac com www daikinac com HT 00_CV_3P161684 6K fm Page 2 Friday September 2 2011 4 00 PM...

Reviews: