1. THE AIR CONDITIONER DOES NOT OPERATE

The air conditioner does not restart immediately 

after the ON/OFF button is pressed.
The air conditioner does not restart immediately 

when TEMPERATURE SETTING button is returned 

to the former position after pushing the button.

If the OPERATION lamp lights, the air conditioner is in 

normal condition.

It does not restart immediately because a safety device 

operates to prevent overload of the air conditioner.

After approx. 3 minutes, the air conditioner will turn on 

again automatically.
The air conditioner does not start when the display 

shows “            ” and it flashes for few seconds after 

pressing an operation button.
This is because the air conditioner is under centralized 

control.

Flashes on the display indicates that the air conditioner 

cannot be controlled by the remote controller.
HEATING OPERATION within 6 hours after the 

power is supplied to the air conditioner.
Some models perform the following operation to protect 

the devices.

If the HEATING OPERATION is performed within 

6 hours after the power is supplied to the air conditioner, 

the indoor fan stops for about 10 minutes during the 

outdoor unit operation to protect the devices.

The above operation is performed not only at the time 

of installation, but every time the power circuit breaker 

is turned off/on.

For comfortable use, do not turn off the power circuit 

breaker during seasonal use of the HEATING 

OPERATION.

9

6. Reattach the air filter.

Refer to “HOW TO CLEAN THE AIR FILTER”.
(Refer to Fig. 2)

7. Reattach the suction grille.

Refer to item No. 2.

8. Fit the string of the suction grille.

Fit in the reverse order of the procedure 2.

9. Close the suction grille.

Refer to item No. 1.

Confirm the following.

Check that the air inlet and outlet of indoor and 

outdoor unit are not blocked.

Remove any obstacle.

Obstacles may cause a reduction in the fan speed, 

which may decrease functionality, cause an increase 

in operation noise, or a malfunction of the equipment.

Clean the air filter and outside panel

After cleaning the air filter, make sure to attach it.

(Refer to “

8. MAINTENANCE” on page 7.)

For information on how to install, remove, or clean 

a optional sold air filter, refer to the user’s manual 

attached to the air filter.
After cleaning, perform FILTER SIGN RESET after 

turning on the power.

Turn on the power circuit breaker at least 6 hours 
before operation.

This is required in order to activate the air conditioner 

smoothly, and to protect air conditioner.
The display on the remote controller will be 

shown when the power circuit breaker is turned on.

HEATING OPERATION within 6 hours after the power 
is supplied to the air conditioner.

Turn on FAN OPERATION for a half day on the fine 
day and dry the indoor unit.

Some models perform the following operation to 

protect the devices.

If the HEATING OPERATION is performed within 

6 hours after the power is supplied to the air 

conditioner, the indoor fan stops for about 10 minutes 

during the outdoor unit operation to protect the devices.

The above operation is performed not only at the time 

of installation, but every time the power circuit breaker 

is turned off/on.

For comfortable use, do not turn off the power circuit 

breaker during seasonal use of the HEATING 

OPERATION.

This can prevent the causes of mould.

Turn off the power circuit breaker.

During the power circuit breaker is turned on, some 

watts of electricity is being used even if the air 

conditioner is not operating.

Turn off the power circuit breaker for saving energy.
The display on the remote controller will vanish when 

the power circuit breaker is turned off.

Clean the air filter and outside panel

Be sure to replace the air filter to its original place after 

cleaning. (Refer to “

8. MAINTENANCE” on page 7.)

For information on how to install, remove, or clean an 

optional sold air filter, refer to the user’s manual 

attached to the air filter.

HEATING OPERATION within 6 hours after the power 

is supplied to the air conditioner.

Some models perform the following operation to protect 

the devices.

If the HEATING OPERATION is performed within 

6 hours after the power is supplied to the air conditioner, 

the indoor fan stops for about 10 minutes during the 

outdoor unit operation to protect the devices. The above 

operation is performed not only at the time of installation, 

but every time the power circuit breaker is turned off/on.

For comfort heating, it is recommended not to turn off 

the power circuit breaker during the HEATING 

OPERATION.

The inside of the air conditioner may become contaminated 

after several seasons of use, potentially causing 

performance degradation and water leakage.

Ask your local dealer for details on cleaning the inside of 

the indoor unit. This operation requires a qualified service 

person.

WHAT TO DO TO STOP THE AIR 
CONDITIONER FOR A LONG PERIOD

9. NOT MALFUNCTION OF THE 
  AIR CONDITIONER

The following symptoms do not indicate air conditioner 

malfunction.

CLEANING BEFORE AND AFTER 
SEASONAL USE

WHAT TO DO WHEN START UP AFTER 
A LONG STOP

NOTE 

9. NOT MALFUNCTION OF THE 
  AIR CONDITIONER

Summary of Contents for FCA100CVMA

Page 1: ...dipasang di langit langit Model aliran deteksi baru FCA50CVMA FCA60CVMA FCA71CVMA FCA85CVMA FCA100CVMA FCA125CVMA FCA140CVMA FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM FCF50CVM4 FCF60CVM...

Page 2: ......

Page 3: ...an bersama panduan pengoperasian untuk unit luar ruang Setelah membaca panduan simpanlah untuk referensi kelak Thank you for purchasing this Daikin air conditioner Carefully read this operation manual...

Page 4: ...keluarkan dari remote control dan dibuang terpisah sesuai dengan peraturan daerah dan nasional yang terkait DISPOSAL REQUIREMENTS Disposal requirements Your air conditioning product is marked with thi...

Page 5: ...SAFETY PRECAUTIONS The appliance must be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pier...

Page 6: ...conditioner is not operating Therefore switch off the main power switch to save energy When resuming operation to ensure smooth running turn on the main power switch 6 hours before operating the air...

Page 7: ...ol and two remote controller control systems Please do not change the combination and settings for the group operation and two remote controllers control systems by yourself but be sure to ask your lo...

Page 8: ...of the air conditioner consult your dealer Regarding drainage of drain pipe Is the drain pipe executed to perform complete drainage If Operation procedure Read the operation manual attached to the re...

Page 9: ...unit turn on The remote controller displays the fan speed that is set After maximum 10 minutes of the DEFROST OPERATION the air conditioner returns to the HEATING OPERATION The airflow direction becom...

Page 10: ...oid excessive heating or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Keep doors and windows closed If the doors and windows remain open ro...

Page 11: ...or rods in the air inlet air outlet or air blade The fan is rotating at high speed so you would get injured Do not wash the air conditioner with water It may cause electric shocks or a fire due to lea...

Page 12: ...may cause discoloration and deformation When drying the filter do not heat it with fire It may cause burning Do not use such as gasoline benzine thinner polishing powder and liquid insecticide sold i...

Page 13: ...moothly and to protect air conditioner The display on the remote controller will be shown when the power circuit breaker is turned on HEATING OPERATION within 6 hours after the power is supplied to th...

Page 14: ...door unit starts This sound is generated when the motors for driving the horizontal blades are working It will quiet down after about a minute A low continuous flow Shuh sound which is heard when the...

Page 15: ...ice person to clean the air filters A decrease in the airflow volume of the air conditioner will result and the performance of the air conditioner will be degraded and power consumption will increase...

Page 16: ...h If the ON OFF switch does not properly work Measure Turn off the main power switch If water leaks from the indoor unit Measure Stop the operation If a malfunction occurs either one of the following...

Page 17: ...gakibatkan kerusakan sengatan listrik atau bahaya kebakaran Tanyakan kepada dealer di daerah Anda tentang pekerjaan pemasangan Mengerjakannya sendiri dapat mengakibatkan kebocoran air sengatan listrik...

Page 18: ...n hewan atau karya seni karena dapat menyebabkan efek samping yang merugikan pada kinerja kualitas dan atau ketahanan benda tersebut Jangan melepas pelindung kipas pada unit dalam ruang Pelindung ters...

Page 19: ...ang lemah atau anak anak tanpa pengawasan Dapat mengakibatkan kerusakan fungsi tubuh dan membahayakan kesehatan Anak anak harus diawasi untuk memastikan bahwa mereka tidak bermain dengan unit atau rem...

Page 20: ...luaran pembuangan terpasang Membuang embun dalam ruang yang dihilangkan Selama operasi pendinginan Pipa pembuangan Nama model pelat nama model Bilah horizontal di saluran keluar udara Pemipaan refrige...

Page 21: ...ian tanyakan kepada dealer Anda tentang tudung pelindung salja dll Mengenai pengkabelan Semua pengkabelan harus dilakukan oleh teknisi listrik resmi Untuk pengkabelan mintalah dealer Anda melakukannya...

Page 22: ...urangi kelembapan tanpa menurunkan suhu dalam ruang Suhu dalam ruang bila tombol pengoperasian ditekan akan menjadi suhu yang diatur Pada saat ini kecepatan kipas dan suhu diatur secara otomatis sehin...

Page 23: ...ngsung ke arah orang Suhu ruangan perlu waktu untuk mencapai suhu yang telah diatur Kami menyarankan memulai pengoperasian sebelum mengoperasikan pengatur waktu PERINGATAN Jangan menggunakan gas yang...

Page 24: ...dan perubahan bentuk Pasang filter udara Lihat item No 2 Tutuplah jeruji penghisap Pelan pelan dorong ke atas jeruji penghisap kemudian kaitkan dengan erat ke panel dekorasi sambil menekan kedua kenop...

Page 25: ...50 C atau lebih Ini dapat menyebabkan warnanya luntur dan perubahan bentuk Saat mengeringkan jeruji penghisap jangan memanaskannya dengan api Ini dapat menyebabkan hangus Jangan gunakan bensin benzena...

Page 26: ...m setelah listrik mengalir ke AC Beberapa model melakukan pengoperasian berikut untuk melindungi perangkat Jika OPERASI PEMANASAN dilakukan dalam waktu 6 jam setelah listrik mengalir ke AC kipas dalam...

Page 27: ...dalam ruang akan menggunakan angin lembut Butuh waktu hingga kecepatan kipas berubah Naikkan suhu yang telah diatur Beberapa saat kemudian kecepatan kipas akan berubah 7 KEBISINGAN PENDINGIN UDARA Ad...

Page 28: ...tau kotoran Selain itu hal ini dapat menyebabkan pengembunan pada saluran keluar udara Lihat 8 PEMELIHARAAN pada halaman 7 Periksa apakah suhu yang telah diatur tidak sesuai Aturlah ke suhu kecepatan...

Page 29: ...ikut akan muncul di layar Basic pada remote control berkabel selama pengoperasian Error Push Menu button Kesalahan Tekan tombol Menu Lampu pengoperasian akan berkedip Warning Push Menu button Kesalaha...

Page 30: ...14 CATATAN...

Page 31: ......

Page 32: ...3P459579 1D M16N053C 1902 HT The two dimensional bar code is a manufacturing code...

Reviews: