background image

7

Stop the horizontal flaps at a position where you can 
hold the tabs and adjust it left and right.

NOTE

Only make adjustments after you have stopped 
the air flow direction swing in a position where 
adjustments are possible. Your hand may get 
caught if you attempt to make adjustments while 
the unit is swinging.

Operate in the following order.

The timer is operated in the following two ways.

Programming the stop time  (

) .... 

The system stops operating after the set time has 
elapsed.

Programming the start time (

) .... 

The system starts operating after the set time has 
elapsed. 

The timer can be programmed a maximum of 72 
hours.

The start and the stop time can be simultaneously 
programmed.

TIMER MODE START/STOP

Press the TIMER MODE START/STOP button 
several times and select the mode on the 
display.

The display flashes.
For setting the timer stop .... “

For setting the timer start .... “

PROGRAMMING TIME

Press the PROGRAMMING TIME button and 
set the time for stopping or starting the sys-
tem.

When this button is pressed, the time
advances by 1 hour.

When this button is pressed, the time
goes backward by 1 hour.

TIMER ON/OFF

Press the TIMER ON/OFF button.

The timer setting procedure ends. 
The display “  

or  

” changes from flash-

ing light to a constant light.

 Refer to figure 4 on page [1] 

PROGRAM TIMER OPERATION

1

2

3

NOTE

When setting the timer Off and On at the same 
time, repeat the above procedure from  

 to 

 

once again.

When the timer is programmed to stop the system 
after 3 hours and start the system after 4 hours, the 
system will stop after 3 hours and then 1 hour later 
the system will start.

After the timer is programmed, the display shows 
the remaining time.

Press the TIMER ON/OFF button once again to 
cancel programming. The display vanishes.

Observe the following precautions to ensure the 
system operates.

Adjust the room temperature properly for a com-
fortable environment. Avoid excessive heating or 
cooling.

Prevent direct sunlight from entering a room dur-
ing cooling operation by using curtains or blinds.

Ventilate the room regularly.
Using the unit for long periods of time requires 
attentive ventilation of the room.

Do not place items that might be damaged by 
water under the indoor unit.
Water may condensate and drip if the humidity 
reaches 80% or if the drain exit gets clogged.

Keep doors and windows closed. If the doors and 
windows remain open, room air will flow out and 
cause to decrease the effect of cooling and heat-
ing.

Do not place other heaters directly below the 
indoor unit.
They may deform due to the heat.

Never place objects near the air inlet and the air 
outlet of the unit. It may cause deterioration in the 
effect or stop in the operation.

Turn off the main power supply switch when it is 
not used for long periods of time. When the main 
power switch is turned on, some watts of electric-
ity is being used even if the system is not operat-
ing. Turn off the main power supply switch for 
saving energy. When reoperating, turn on the 
main power supply switch 6hours before opera-
tion for smooth running (Refer to MAINTE-
NANCE).

When the display shows “

 

 (TIME TO CLEAN 

AIR FILTER), ask a qualified service person to 
clean the filters (Refer to MAINTENANCE).

7. OPTIMUM OPERATION

1

3

01_EN_3P141308-4F.fm  Page 7  Thursday, October 13, 2005  3:02 PM

Summary of Contents for FAQ71CV4A

Page 1: ...SPLIT SYSTEM Air Conditioner OPERATION MANUAL MODELS Wall mounted type FAQ71CV4A FAQ90CV4A 00_CV_3P141308_4F_1 fm Page 1 Thursday October 13 2005 2 55 PM...

Page 2: ...3 4 2 TEST C hr hr TEST NOT AVAILABLE L H 2 10 11 3 1 4 5 6 7 8 14 15 16 17 18 19 20 21 22 12 9 13 RZQ71 90 b d f k e i h a j d f g e c C hr H 00_CV_3P141308_4F_2 fm Page 1 Thursday October 13 2005 2...

Page 3: ...oner It will tell you how to use the unit properly and help you if any trouble occurs This manual explains about the indoor unit only Use it along with the opera tion manual for the outdoor unit After...

Page 4: ...r unit PRECAUTIONS FOR GROUP CONTROL SYSTEM OR TWO REMOTE CONTROLLER CONTROL SYSTEM This system provides two other control systems beside individual control one remote controller con trols one indoor...

Page 5: ...be installed in a small room it is necessary to take proper mea sures so that the amount of any leaked refriger ant does not exceed the limiting concentration even when it leaks If the refrigerant le...

Page 6: ...RA TURE C HUMIDITY HEAT PUMP TYPE D B 18 to 35 80 or below D B 5 to 46 W B 12 to 25 HEATING DB Dry bulb temperature WB Wet bulb temperature The setting temperature range of the remote con troller is 1...

Page 7: ...he INSPECTION TEST OPERATION BUTTON is pressed the display shows the system mode is in 7 DISPLAY PROGRAMMED TIME This display shows the PROGRAMMED TIME of the system start or stop 8 DISPLAY SET TEMPER...

Page 8: ...outdoor unit increase heating effect decreases and the system goes into DEFROST OPERATION The indoor unit fan stops and the remote control ler display shows After 6 to 8 minutes maximum 10 minutes of...

Page 9: ...nditions micro computer con trols the air flow direction so it may be different from the display NOTE If you try cooling or programmed drying while the flaps are facing downward air flow direction may...

Page 10: ...3 hours and then 1 hour later the system will start After the timer is programmed the display shows the remaining time Press the TIMER ON OFF button once again to cancel programming The display vanis...

Page 11: ...ying filter with photocat alytic deodorizing function Press the top of the air cleaning filter onto the tabs 3 tabs at top Then press the bottom of the filter up slightly and press it onto the tabs 3...

Page 12: ...Place your fingers on the panel protrusions on the left and right sides of the main unit and open until the panel stops 2 Remove the front panel Push the axes on either side of the front panel toward...

Page 13: ...tes the system will turn on again automatically The system does not start when the display shows UNDER CENTRALIZED CONTROL and it flashes for few seconds after pressing an operation button This is bec...

Page 14: ...the outlet and contact your dealer Continued operation under such circumstances may result in a failure electric shock and fire 10 TROUBLE SHOOTING If a safety device such as a fuse a breaker or an e...

Page 15: ...button is set to LOW SPEED Refer to ADJUSTMENT If the air flow angle is not proper Refer to AIR FLOW DIRECTION ADJUST If the doors or the windows are open Shut doors or windows to prevent wind from co...

Page 16: ...3P141308 4F M04B014B 0512 HT 00_CV_3P141308_4F_3 fm Page 1 Thursday October 13 2005 3 05 PM...

Reviews: