D-EOMHP01405-21_02EN 32/35
▪
Check pump inverter wiring
connection
▪
Contact your local dealer
U016
UnitOffDHWAlarm
Domestic Hot Water Alarms
▪
Check [19.05] DHW Alarm Code
value
▪
Check Domestic Hot Water 3WV
status
▪
Check 3WV wiring connection
▪
Contact your local dealer
Circuit 1
C101
C1Cmp1 OffPrRatioLo
Pressure ratio under minimum
limit
▪
Contact your local dealer
C102
C1 OffNoPressChgStart
No pressure delta detected by
UC
▪
Contact your local dealer
C103
C1Fan OffVfdCommFail
Bad fan inverter communication
▪
Check fan inverter wiring
connection
▪
Contact your local dealer
C104
C1Cmp1 OffVfdCommFail
Bad compressor inverter
communication
▪
Check compressor inverter wiring
connection
▪
Contact your local dealer
C105
C1Cmp1 OffEvpPressLo
Evaporating pressure under
minimum limit
▪
Contact your local dealer
C106
C1Cmp1 OffCndPressHi
Condensing pressure over
maximum limit
▪
Contact your local dealer
C107
C1Cmp1 OffDischTmpHi
Discharge temperature over
maximum limit
▪
Contact your local dealer
C108
C1Cmp1 OffMtrAmpsHi
Compressor current over
maximum limit
▪
Contact your local dealer
C109
C1 OffStartFailEvpPrLo
No evaporating or condensing
pressure detected at start
▪
Check sensors wiring connection
▪
Contact your local dealer
C110
C1Cmp1 EvapPressSen
Pressure sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C111
C1Cmp1 CondPressSen
Pressure sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C112
C1Cmp1 OffMotorTempHi
Motor temperature over
maximum limit
▪
Check wiring connection
▪
Contact your local dealer
C113
C1Cmp1 OffSuctTempSen
Temperature sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C114
C1Cmp1 OffDischTmpSen
Temperature sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C115
C1 Failed Pumpdown
Pumpdown procedure exedes
maximum time
▪
Contact your local dealer
C116
C1Cmp1 OffVfdFault
Detected compressor inverter
alarm
▪
Contact your local dealer
C117
C1 FanAlm
Detected fan inverter alarm
▪
Contact your local dealer
C118
-
-
-
C119
C1Cmp1 OffLowDiscSH
Discharge super heat under
minimum limit
▪
Contact your local dealer
C120
C1Cmp1 OffMechPressHi
Condensing pressur over
mechanical pressure switch
▪
Mechanical reset of switch
▪
Contact your local dealer
Circuit 2
C201
C2Cmp1 OffPrRatioLo
Pressure ratio under minimum
limit
▪
Contact your local dealer
C202
C2 OffNoPressChgStart
No pressure delta detected by
UC
▪
Contact your local dealer
C203
C2Fan OffVfdCommFail
Bad fan inverter communication
▪
Check fan inverter wiring
connection
▪
Contact your local dealer
C204
C2Cmp1 OffVfdCommFail
Bad compressor inverter
communication
▪
Check compressor inverter wiring
connection
▪
Contact your local dealer
C205
C2Cmp1 OffEvpPressLo
Evaporating pressure under
minimum limit
▪
Contact your local dealer
C206
C2Cmp1 OffCndPressHi
Condensing pressure over
maximum limit
▪
Contact your local dealer
C207
C2Cmp1 OffDischTmpHi
Discharge temperature over
maximum limit
▪
Contact your local dealer
C208
C2Cmp1 OffMtrAmpsHi
Compressor current over
maximum limit
▪
Contact your local dealer
C209
C2 OffStartFailEvpPrLo
No evaporating or condensing
pressure detected at start
▪
Check sensors wiring connection
▪
Contact your local dealer
C210
C2Cmp1 EvapPressSen
Pressure sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C211
C2Cmp1 CondPressSen
Pressure sensor not detected
▪
Check sensor wiring connection
▪
Contact your local dealer
C212
C2Cmp1 OffMotorTempHi
Motor temperature over
maximum limit
▪
Check wiring connection
▪
Contact your local dealer