Operation manual

5

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22685-1

Safety devices

The unit is equipped with three kinds of safety devices:

1

General safety devices

General safety devices shut down all circuits and stop the whole
unit. For this reason the unit has to be manually put on again
after a general safety occurred.

2

Circuit safety devices

Circuit safety devices shut down the circuit they protect. For this
reason the unit does not need to be manually put on again after
a circuit safety occurred.

3

Part safety devices

Part safety devices shut down the part they protect.

An overview of all safety devices is given below.

Overcurrent relay
The overcurrent relays (K*S) are located in the switchbox of the
unit and protect the compressor motors in case of overload,
phase failure or too low voltage. The relays are factory-set and
may not be adjusted. When activated, they must be reset
manually, followed by a reset of the controller.

Compressor thermal protectors
The compressor motors are equipped with thermal protectors
(Q*M). The protectors are activated when the compressor motor
temperature becomes too high.
When temperature returns to normal, the protectors reset
automatically, but the controller needs to be reset manually.

Flowswitch
The unit is protected by a flowswitch (S8L). 
When the water flow becomes lower than the minimum allowed
water flow, the flowswitch shuts down the unit. When the water
flow becomes normal, the protection resets automatically but the
controller still needs to be reset manually.

Discharge thermal protectors
The unit is equipped with discharge thermal protectors (S*T).
The protectors are activated when the temperature of the
refrigerant leaving the compressor becomes too high. When the
temperature returns to normal the protector resets automatically
and the controller needs to be reset manually.

Freeze-up protection
The freeze-up protection  prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller shuts down the circuit.
When the outlet water temperature returns to normal, the unit
can start up again. 
When freeze-up protection occurs several times in a certain
period, the freeze-up alarm will be activated and the unit will be
shut down. The cause of freezing up should be investigated and
after outlet water temperature has risen enough, the alarm
indicator on the controller needs to be reset manually.

Low pressure safety
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.

Pressure relief safety valve
The safety valve is activated when the pressure in the refrigerant
circuit becomes too high. If this occurs, shut down the unit and
contact your local dealer.

High pressure switch
Each circuit is protected by two high pressure switches (S*PH)
which measure the condenser pressure (pressure at the outlet
of the compressor). They are installed in the compressor
housing of the circuit. When the pressure becomes too high, the
pressure switches are activated and the circuit stops. 
The switches are factory-set and may not be adjusted. When
activated, they must be reset by means of a screwdriver. The
controller still needs to be reset.

Reverse phase protector
The reverse phase protectors (R*P) prevent the screw
compressors from running in the wrong direction. If the
compressors do not start, two phases of the power supply must
be inverted.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:

A1,A2..........** ....... Current transfo circuit 1, circuit 2

A1P........................ PCB-controller

A2P,A3P................. PCB-EEV driver circuit 1, circuit 2

A11P...................... Expansion board controller

(only for EWWD360~540)

B1P,B4P................. Low pressure transmitter for circuit 1, circuit 2

B2P,B5P................. High pressure transmitter for circuit 1, circuit 2

B3P,B6P................. Low pressure transmitter EEV for circuit 1 (A2P), 

circuit 2 (A3P)

C11,C21 ................ Capacitor for capacity control 

(only for EWWD360~540)

E1HC,E2HC .......... Crankcase heater compressor circuit 1, circuit 2

F1R,F2R ................ Fuses for reverse phase protector circuit 1, 

circuit 2

F1U~F3U ....# ........ Main fuses

F6B,F11B .............. Fuse for primary of TR1

F7B ........................ Fuse for secondary of TR1

F8B ........................ Fuse for EEV driver

F8U........................ Surge proof fuse for A1P

F9B ........................ Surge proof fuse for secondary of TR2

F10B,F14B ............ Autofuse for secondary of TR2

F10S,F11S ............ Circuit breakers with fuses for circuit 1, circuit 2 

(only for EWWD360~540)

F11U~F13U ........... Main fuses (only for EWWD360~540)

F21U~F23U ........... Main fuses (only for EWWD360~540)

H1P.............*......... Indication lamp general operation

H2P.............*......... Indication lamp alarm

H3P.............*......... Indication lamp operation compressor 1

H4P.............*......... Indication lamp operation compressor 2 

(only for EWWD360~540)

H4P,H5P .....*......... Changeable output (only for EWWD120~280)

H5P,H6P .....*......... Changeable output (only for EWWD360~540)

J1........................... Power supply

J2,J3,J6,J20 .......... Analog input

J4........................... Analog output

J5,J7,J8,J19 .......... Digital input

J11......................... RS485 connection

J12~J18,J21,J22 ... Digital output

K1A,K4A ................ Auxiliary relay for safeties circuit 1, circuit 2

K1M,K4M............... Linecontactor for circuit 1, circuit 2

K2A,K5A ................ Auxiliary relay compressor thermal protector 

circuit 1, circuit 2

K2M,K5M............... Deltacontactor for circuit 1, circuit 2

K3A,K6A ................ Auxiliary relay for discharge thermal protector 

circuit 1, circuit 2

K3M,K6M............... Starcontactor for circuit 1, circuit 2

K7A,K8A ................ Auxiliary relay for high pressure circuit 1, circuit 2

K17S,K18S ............ Overcurrent relay for circuit 1, circuit 2

L1,L2,L3................. Main supply terminals 

M1C,M2C .............. Compressor motor circuit 1, circuit 2

Summary of Contents for EWWD120MBYNN

Page 1: ...OPERATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Page 2: ...Y KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation m...

Page 3: ...0 Condensor Type shell tube Qtyxmodel 2x CDEW400 1x CDEW400 1x CDEW450 2x CDEW450 Evaporator Type brased plate heatexchanger Qtyxmodel 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250EQ NP162 2x AC250EQ NP...

Page 4: ...harge stopvalve 3 Condenser 19 Condensor entering water temperature sensor 4 Switchbox 20 Digital display controller 5 Compressor switchbox 21 Emergency stop 6 Air purge condenser 22 Power supply inta...

Page 5: ...ion of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection...

Page 6: ...essure relief safety valve The safety valve is activated when the pressure in the refrigerant circuit becomes too high If this occurs shut down the unit and contact your local dealer High pressure swi...

Page 7: ...ield wiring Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual according to the wiring...

Page 8: ...phanumeric display may decrease at low temperatures OPERATION The EWWD120 540 units are equipped with a digital controller offering a user friendly way to set up use and maintain the unit This part of...

Page 9: ...tialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller does not...

Page 10: ...frigerant in circuit 1 respectively circuit 2 The first number stands for the pressure in bar the second number stands for the saturation temperature in degrees Celsius low pressure of the refrigerant...

Page 11: ...rcuits The red LED inside the p key lights up and the buzzer inside the controller is activated When a circuit safety occurs the compressor of the corresponding circuit is shut down The screen of the...

Page 12: ...n the first screen of the network menu To consult information about the outlet water temperature of the evaporator of circuit 1 and 2 only for EWWD360 540 To consult information about the unit status...

Page 13: ...information about the network safety which caused the shutdown To consult information about the dual pump wich caused the shutdown To check the time and control mode at the moment of the unit shutdown...

Page 14: ...evaporator and or condenser entering water temperature to control the capacity of the unit outlet control mode uses the evaporator leaving water temperature to control the capacity of the unit To chec...

Page 15: ...their setting needs to be reset to See User settings menu on page 11 The screen of the user settings menu allows the user to define the schedule timer settings Each day of the week can be appointed to...

Page 16: ...rd each time he wants to change the setpoint Defining BMS control allows the user to control the unit from a supervisory system The screen and screen of the service menu have to be used to set BMS par...

Page 17: ...the latest shutdown To check the safety info and the unit status proceed as follows 1 Enter the Refer to the chapter How to enter a menu on page 8 The controller enters the last screen which contains...

Page 18: ...e g and h keys 6 Press q to confirm the new password When the new password has been confirmed the controller will ask to enter the new password a second time for safety reasons The cursor is positione...

Page 19: ...panel or measure the supply voltage Voltage too low Measure the supply voltage Overload of motor Reset If the failure persists call your local dealer RESET Push the blue button on the over current rel...

Page 20: ...apacity of the unit is too low Call your local dealer Water flow is too high Recalculate the water flow The circuit is limited Check the enable disable capacity limitation remote contact POSSIBLE CAUS...

Page 21: ...perly and that the earth terminals are tightened Refrigerant circuit Check for leaks inside the unit In case a leak is detected call your local dealer Check the working pressure of the unit Refer to p...

Page 22: ...to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings in the holiday group All group settings of gro...

Page 23: ...1 1 q h q q g h h h g h g h g h g h h g h g 2 0 1 1 1 1 g g h g g h g h g h g h g h g h g g h g h g h g h h g g 1 f 3 3 1 4 3 3 1 3 3 3 3 3 3 3 3 3 2 3 3 3 3 g h g h g h q h h g q h g h g h g h g h g...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22685 1...

Reviews: