background image

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22685-1

Operation manual

10

Adjusting the temperature setpoint

The unit provides definition and selection of four or two independent
temperature setpoints.

In cooling operation, two setpoints are reserved for inlet control, the
other two are reserved for outlet control.

 

: inlet water temperature of evaporator, setpoint 1,

 

: inlet water temperature of evaporator, setpoint 2.

 

: outlet water temperature of evaporator, setpoint 1,

 

: outlet water temperature of evaporator, setpoint 2.

In heating operation, two setpoints are reserved for inlet control.

 

: inlet water temperature of condenser, setpoint 1,

 

: inlet water temperature of condenser, setpoint 2.

In double thermostat operation, two setpoints are reserved for inlet
control of the evaporator and two others are reserved for inlet control
of the condenser.

 

: inlet water temperature of evaporator, setpoint 1,

 

: inlet water temperature of evaporator, setpoint 2.

 

: inlet water temperature of condenser, setpoint 1,

 

: inlet water temperature of condenser, setpoint 2.

The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.

If the manual control mode is selected (refer to 

"User settings menu"

on page 11

), none of the above-mentioned setpoints will be active.

To adjust a setpoint, proceed as follows:

1

Enter the setpoints menu. Refer to the chapter 

"How to enter a

menu" on page 8

.

If the user password is disabled for setpoint modifications (refer
to the 

"User settings menu" on page 11

), the controller will

immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the 

h

  and 

keys (refer to the 

"User

password menu" on page 13

). Press 

q

 to confirm the password

and to enter the setpoints menu.

2

Select the setpoint to be adjusted using the 

q

 key.

A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The "

" sign indicates the actual active temperature setpoint.

3

Press the 

h

 and 

keys to adjust the temperature setting.

The default, limit and step values for the cooling (evaporator)
and heating (condenser) temperature setpoints are:

4

Press 

q

 to save the adjusted temperature setpoint.

When the setting has been confirmed, the cursor switches to the
next setpoint. When the setting has been cancelled, the cursor
returns to the upper left corner of the screen.

5

To adjust other setpoints, repeat from instruction 2 onwards.

Resetting the unit

The units are equipped with three kinds of safety devices: unit
safeties, circuit safeties and network safeties.

When a unit safety occurs, all compressors are shut down. The
safeties menu will indicate which safety is activated. The 

  screen of the readout menu will indicate 

 

 for all circuits. The red LED inside the 

p

 key lights up and

the buzzer inside the controller is activated.

When a circuit safety occurs, the compressor of the corresponding
circuit is shut down. The 

 

 screen of the readout menu

will indicate 

   

 for the circuit concerned. The

red LED inside the 

p

  key  lights up and the buzzer inside the

controller is activated.

When a network safety occurs in a DICN configuration, the slaves not
detected by the network will function as stand alone units.

If the master is not detected by the network, all units will work as
stand alone units.

If a slave unit can not be found by the network, the red light
inside the 

p

 key of the master lights up and the buzzer inside

the control is activated.

If the master can not be found by the network, the red light
inside the 

p

 key of all the slaves light up and the buzzer inside

their controls are activated.

If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.

To reset the unit, proceed as follows:

1

Press the 

p

 key to acknowledge the alarm.

The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or circuit safety.

2

Find the cause of shutdown and correct.
Refer to 

"Listing activated safeties and checking the unit status"

on page 16

 and the chapter 

"Troubleshooting" on page 17

.

When a safety can be reset, the LED under the 

p

  key  starts

blinking.

3

Press the 

p

 key to reset the safeties that are no longer active.

If required, enter the 

 

  or the 

.  (Refer to the installation manual “Setting the

password for safety reset”.)
Once all safety devices are disactivated and reset, the LED
under the 

p

 key goes out. If one of the safeties is still active, the

LED under the 

p

  key  goes on again. In this case, return to

instruction 2.

4

It will only be necessary to switch the 

o

 key on again if a unit

safety occurs.

NOTE

The customer is also allowed to define a setpoint in
function of an analog input.

NOTE

Refer to “Customization in the service menu” chapter
“Setting of the changeable inputs and outputs” in the
installation manual

                      

default value

!

"!

#$!

limit values

(a)

(a) For glycol units the lower limit of the cooling temperature

setpoint can be adapted in the factory. The following
values apply:

 

: 5°C, 3°C, –2°C, –7°C

 

: 2°C, 0°C, –5°C, –10°C

"

 --> 

#!

%

 --> 

&!

'

--> 

'$!

step value

$!

$!

$!

NOTE

When a setpoint on a unit in a DICN system is set, this
setpoint will be transferred to all other units.

NOTE

Also consult 

"Defining the schedule timer" on page 14

and 

"Defining the display settings" on page 14

.

NOTE

To be able to reset the 

   

 circuit error

several precautions have to be taken. Refer to
“Resetting the 

   

  alarm” in the

installation manual.

If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.

NOTE

The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.

Summary of Contents for EWWD120MBYNN

Page 1: ...OPERATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Page 2: ...Y KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation m...

Page 3: ...0 Condensor Type shell tube Qtyxmodel 2x CDEW400 1x CDEW400 1x CDEW450 2x CDEW450 Evaporator Type brased plate heatexchanger Qtyxmodel 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250EQ NP162 2x AC250EQ NP...

Page 4: ...harge stopvalve 3 Condenser 19 Condensor entering water temperature sensor 4 Switchbox 20 Digital display controller 5 Compressor switchbox 21 Emergency stop 6 Air purge condenser 22 Power supply inta...

Page 5: ...ion of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection...

Page 6: ...essure relief safety valve The safety valve is activated when the pressure in the refrigerant circuit becomes too high If this occurs shut down the unit and contact your local dealer High pressure swi...

Page 7: ...ield wiring Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual according to the wiring...

Page 8: ...phanumeric display may decrease at low temperatures OPERATION The EWWD120 540 units are equipped with a digital controller offering a user friendly way to set up use and maintain the unit This part of...

Page 9: ...tialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller does not...

Page 10: ...frigerant in circuit 1 respectively circuit 2 The first number stands for the pressure in bar the second number stands for the saturation temperature in degrees Celsius low pressure of the refrigerant...

Page 11: ...rcuits The red LED inside the p key lights up and the buzzer inside the controller is activated When a circuit safety occurs the compressor of the corresponding circuit is shut down The screen of the...

Page 12: ...n the first screen of the network menu To consult information about the outlet water temperature of the evaporator of circuit 1 and 2 only for EWWD360 540 To consult information about the unit status...

Page 13: ...information about the network safety which caused the shutdown To consult information about the dual pump wich caused the shutdown To check the time and control mode at the moment of the unit shutdown...

Page 14: ...evaporator and or condenser entering water temperature to control the capacity of the unit outlet control mode uses the evaporator leaving water temperature to control the capacity of the unit To chec...

Page 15: ...their setting needs to be reset to See User settings menu on page 11 The screen of the user settings menu allows the user to define the schedule timer settings Each day of the week can be appointed to...

Page 16: ...rd each time he wants to change the setpoint Defining BMS control allows the user to control the unit from a supervisory system The screen and screen of the service menu have to be used to set BMS par...

Page 17: ...the latest shutdown To check the safety info and the unit status proceed as follows 1 Enter the Refer to the chapter How to enter a menu on page 8 The controller enters the last screen which contains...

Page 18: ...e g and h keys 6 Press q to confirm the new password When the new password has been confirmed the controller will ask to enter the new password a second time for safety reasons The cursor is positione...

Page 19: ...panel or measure the supply voltage Voltage too low Measure the supply voltage Overload of motor Reset If the failure persists call your local dealer RESET Push the blue button on the over current rel...

Page 20: ...apacity of the unit is too low Call your local dealer Water flow is too high Recalculate the water flow The circuit is limited Check the enable disable capacity limitation remote contact POSSIBLE CAUS...

Page 21: ...perly and that the earth terminals are tightened Refrigerant circuit Check for leaks inside the unit In case a leak is detected call your local dealer Check the working pressure of the unit Refer to p...

Page 22: ...to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings in the holiday group All group settings of gro...

Page 23: ...1 1 q h q q g h h h g h g h g h g h h g h g 2 0 1 1 1 1 g g h g g h g h g h g h g h g h g g h g h g h g h h g g 1 f 3 3 1 4 3 3 1 3 3 3 3 3 3 3 3 3 2 3 3 3 3 g h g h g h q h h g q h g h g h g h g h g...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22685 1...

Reviews: