background image

D-EIMAC01207-15EN - 12/22 

 

G EWAQ~G SR 

model 

Minimum water 

flow 

l/s

 

Maximum 

water flow 

l/s

 

EWAQ075G-SR 

1.98 

3.96 

EWAQ085G-SR 

2.28 

4.56 

EWAQ100G-SR 

2.64 

5.28 

EWAQ110G-SR 

2.88 

5.76 

EWAQ120G-SR 

3.12 

6.24 

EWAQ140G-SR 

3.72 

7.44 

EWAQ155G-SR 

4.14 

8.28 

 

 

 

EWAQ~G XS 

m

odel 

 

 

 

EWAQ080G-XS 

2.28 

4.56 

EWAQ090G-XS 

2.58 

5.16 

EWAQ105G-XS 

3.00 

6.00 

EWAQ115G-XS 

3.36 

6.72 

EWAQ130G-XS 

3.78 

7.56 

EWAQ150G-XS 

4.26 

8.52 

 

 

 

EWAQ~G XR 

model

 

 

 

EWAQ080G-XR 

2.16 

4.32 

EWAQ090G-XR 

2.46 

4.92 

EWAQ105G-XR 

2.88 

5.76 

EWAQ115G-XR 

3.18 

6.36 

EWAQ130G-XR 

3.60 

7.20 

EWAQ150G-XR 

4.02 

8.04 

 

To ensure correct operation of the unit, the flow of water 
in  the  evaporator  must  fall  within  the  operating  sphere 
specified  in  the  preceding  table  and  there  must  be  a 
minimum volume of water in the system. 
The distribution circuits of the cold water should have a 
minimum  content  of  water  to  avoid  an  excessive 
number  of  start-up  and  shut-downs  of  the  compressor. 
Every  time  the  compressor  goes  into  operation,  an 
excessive  amount  of  oil  from  the  compressor  starts 
circulating in the refrigerant circuit and at the same time 
there  is  an  increase  of  the  temperature  of  the 
compressor  stator,  generated  by  the  inrush  current  of 
the  start-up.    Therefore,  to  avoid  damage  to  the 
compressors,  the  application  of  a  device  has  been 
planned  to  limit  frequent  shut-downs  and  start-ups:  in 
one  hour,  there  will  only  be  6  start-ups  of  the 
compressor.                
The  system  where  the  unit  is  installed  must  therefore 
ensure  that  the  overall  content  of  water  allows  the  unit 
to  operate  continuously  and  therefore  offers  greater 
environmental comfort. The minimum water content per 
unit  must  be  calculated  approximately  using  the 
following formula: 
 

For 2 compressor units: 
 

M (litres) = (12.153 x DT (°C) 

– 22.168) x P(kW) 

 
Where: 
M  =  minimum  content  of  water  per  unit  expressed  in 
litres 
P = refrigerating capacity of the unit express in kW 
ΔT  =  difference  in  temperature  of  the  incoming  and 
outgoing water, expressed in °C. 
 
This  formula  is  valid  with  the  standard  parameters  of 
the  microprocessor.  To  determine  most  accurately  the 
quantity  of  water,  we  recommend  contacting  the 
designer of the system. 

Anti-freeze protection for evaporators and recovery 
exchangers  

When  the  entire  system  of  the  cooling  installation  is 
being designed, two or more of the following anti-freeze 
protection  methods  should  be  considered  at  the  same 
time: 
1.  Continuous  circulation  of  water  flow  inside  the 

exchangers 

2.  Additional  heat  insulation  and  heating  of  exposed 

piping 

3.  Emptying  and  cleaning  the  heat  exchanger  when  it 

is not in use  and its maintenance in an anti-oxidant 
atmosphere (nitrogen). 

 

As  an  alternative,  it  is  possible  to  add  an 
appropriate  amount  of  glycol  (antifreeze)  to  the 
water circuit. 

 
The  installer  and/or  local  personnel  in  charge  of 
maintenance,  must  make  sure  that  anti-freeze 
protection  methods  are  in  use  and  ensure  that  the 
appropriate  maintenance  operations  of  the  antifreeze 
protection  devices  are  always  carried  out.  Failing  to 
follow  the  instructions  above  could  result  in  damage  to 
the unit. Damage caused by freezing is not covered by 
the guarantee.  
 

Electrical system General specifications 

The  units  must  be  connected  to  a  TN  power  supply 
system. 
If  the  units  must  be  connected  to  a  different  type  of 
power  system,  for  example  the  IT  system,  please 
contact the factory. 

 

All  the  electrical  connections  to  the  unit  must 
be carried out in compliance with national laws 
and  European  directives  and  regulations  in 
force. 
 

All installation, running and maintenance activities must 
be carried out by qualified personnel. 
Refer  to  the  specific  wiring  diagram  for  the  unit 
purchased. Should the wiring diagram not be on the unit 
or  should  it  have  been  lost,  please  contact  the 
manufacturer's  representative  who  will  send  you  a 
copy. 
In  the  event  of  any  discrepancies  between  what  is 
written on the wiring diagram and a visual check of the 
electric  wires  of  the  command  and  control  panel, 
contact the manufacturer representative. 
Use  only  copper  conductors  to  avoid  overheating  or 
corrosion in the connection points, with resulting risk of 
damage to the unit. 
To  avoid  interference,  all  the  command  and  control 
cables  must  be  connected  separately  from  the  power 
cables,  using  more  than  one  cable  duct  for  this 
purpose. 
Before carrying out servicing work on the unit, close the 
general disconnection switch located on the main power 
supply. 
 

WARNING

: If the unit is off but the disconnection switch 

is  in  the  open  position,  the  circuits  not  being  used  are 
still live. 
Never open the compressor terminal board without first 
having disconnected the unit main switch. 

Summary of Contents for EWAQ~G-SS

Page 1: ...EWAQ G SS Standard Efficiency Standard Noise SR Standard Efficiency Reduced Noise XS High Efficiency Standard Noise XR High Efficiency Reduced Noise Refrigerant R410A Original Instructions Installati...

Page 2: ...it connection 10 Water treatment 11 Water flow and volume 11 Anti freeze protection for evaporators and recovery exchangers 12 Electrical system General specifications 12 Wiring at the installation si...

Page 3: ...h the unit In case of doubt contact the manufacturer s representative The aim of this manual is to make sure that the installer and the qualified operator can properly commission operate and maintain...

Page 4: ...es may be in different positions depending on the model and options on the unit Figure 2 Operating limits EWAQ G SS Standard efficiency Standard noise Water temperature at outlet C 1 Slack electrical...

Page 5: ...C01207 15EN 5 22 EWAQ G SR Standard efficiency Reduced noise Water temperature at outlet C EWAQ G XS High efficiency Standard noise Water temperature at outlet C Ambient temperature C Ambient temperat...

Page 6: ...Water temperature at outlet C Water temperature at evaporator outlet C A Operating with glycol B Operating with fan speed mode selected C Operating at maximum fan speed Table 1 Evaporator Difference i...

Page 7: ...orm of insulation Never access electrical components if water and or moisture are present Always disconnect the power supply by closing the main switch before carrying out any work on the cooling fans...

Page 8: ...cooling condenser Both these conditions can cause an increase in condenser pressure which can lead to poor energy efficiency and refrigerating capacity If two or more units are positioned alongside e...

Page 9: ...use lifting hooks fitted with appropriate locking devices The hooks must be safely fastened before performing the handling 3 Fork lift truck Sound protection When sound levels require special control...

Page 10: ...o the heat exchangers Pipe insulation The complete water circuit including all pipes must be insulated to avoid condensate from forming and reducing cooling capacity Protect water pipes from freezing...

Page 11: ...ter The manufacturer is not responsible for any damage or malfunctions of the equipment The quality of the water must comply with the specifications listed in the following table The water pressure mu...

Page 12: ...system of the cooling installation is being designed two or more of the following anti freeze protection methods should be considered at the same time 1 Continuous circulation of water flow inside th...

Page 13: ...nals The power supply cables must be supported by adequate systems The wires connected to the switch must comply with the insulation distance and the distance of surface insulation between the active...

Page 14: ...unit In addition to reading this manual the user must study the microprocessor operating manual and the wiring diagram in order to understand the start up sequence operation shutdown sequence and ope...

Page 15: ...evel full X Check for a load loss in filter dryer where present X Analyse the compressor vibrations X Check the safety valve Note 5 X Heat exchangers Check that the heat exchangers are clean Note 6 X...

Page 16: ...ronic components All these components must be disposed of in accordance with relevant current national and European legislative requirements Lead batteries must be collected and sent to specific waste...

Page 17: ...n Secondary Temperature Sensor M S BC Main Secondary Connection Box D L Request Limit DI Digital Inputs DO Digital Outputs DSP Double Setting Point EF External failure EFS Evaporator flow switch GA Ge...

Page 18: ...D EIMAC01207 15EN 18 22 A Typical refrigerant circuit The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 19: ...15EN 19 22 B Typical refrigerant circuit with partial heat recovery The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water...

Page 20: ...15EN 20 22 C Typical refrigerant circuit with total heat recovery The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water...

Page 21: ...4 Evaporator water outlet connection 15 Heat recovery water inlet connection 16 Heat recovery water outlet connection 17 Low pressure safety valve 18 High pressure safety valve EP Low pressure transdu...

Page 22: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: