D-EIMAC01207-15EN - 10/22 

 

The water system must have: 

1. 

Anti-vibrating 

pipes 

which 

reduce 

the 

transmission of vibrations to the structures. 

2. 

Isolating  valves  to  isolate  the unit  from  the  water 
system  of  the  installation  during  service 
operations.   

3.    Manual  or  automatic  air  venting  device  at  the 

system’s  highest  point.;  drain  device  at  the 
system’s lowest point.  

4.    Neither  the  evaporator  nor  the  heat  recovery 

device must be positioned at the system’s highest 
point. 

5. 

 

A  suitable  device  that  can  maintain  the  water 
system under pressure. 

6. 

 

Water  temperature  and  pressure  indicators  to 
assist 

the 

operator 

during 

service 

and 

maintenance. 

7. A water filter or a device that can remove particles 

from  the  liquid  and  is  mandatory  at  the  entry  of 
the evaporator.  
The filter can be installed at the pump inlet when 
it is placed on the evaporator water inlet pipe but 
only  if  the  cleanliness  of  the  water  installation 
between  the  pump  and  the  evaporator  is 
guaranteed. Any waste in the evaporator will void 
the unit guarantee.  

8. 

 

If the unit is being replaced, empty and clean the 
entire  water  system  before  installing  a  new  one 
and  prior  to  starting  it,  carry  out  adequate  tests 
and chemical treatments of the water. 

9.    If  glycol  is  added  to  the  water  system  to  provide 

anti-freeze protection, the performance of the unit 
will decrease. All unit-protection systems, such as 
anti-freeze, and low-pressure protection will need 
to be readjusted to offset the low pressure.        

10.  Before  insulating  water  piping,  check  that  there 

are no leaks. 

11.

 

Check  that  the  pressure  of  the  water  does  not 
exceed  the  design  pressure  of  the  water  side 
heat exchangers and install a safety valve on the 
pipe of the water. 

12. Install a suitable expansion tank.

 

 

CAUTION 

To avoid damage, install an inspectionable filter 

on the water pipes at the entry to the heat 

exchangers. 

 

Pipe insulation  

The  complete  water  circuit,  including  all  pipes,  must 
be  insulated  to  avoid  condensate  from  forming  and 
reducing cooling capacity. 
Protect  water  pipes  from  freezing  during  the  winter 
(using  for  example  a  glycol  solution  or  a  heating 
cable).  
 

Installing the flow switch 

To  guarantee  sufficient  water  flow  to  the  entire 
evaporator,  it  is  vital  that  a  flow  switch  be  installed  on 
the  water  circuit  which  can  be  positioned  on  the 
incoming  or  outgoing  water  pipes.  The  purpose  of  the 
flow switch is to stop the unit in the event of interrupted 
water flow, thus protecting the evaporator from freezing. 
The  manufacturer  may  offer  a  flow  switch  specially 
selected for this purpose.  
This  paddle-type  flow  switch  is  suitable  for  heavy-duty 
applications and 2 1/2" pipe diameters. 

It  has  a  clean  contact  that  is  electrically  connected  to 
the terminals shown in the wiring diagram, and must be 
calibrated  so  that  it  intervenes  when  the  flow  of  the 
water of the evaporator drops below 80% of the nominal 
flow  and  in  any  case  within  the  limits  listed  in  the 
following table. 
 

Preparing and checking the water circuit connection  

The  units  have  a  water  input  and  output  for  the 
connection  of  the  chiller  to  water  circuit  of  the  system. 
This  circuit  must  be  connected  to  the  unit  by  an 
authorised  technician  and  must  comply  with  all  the 
current  national  and  European  regulations  on  the 
subject.  
 

NOTE  -

  The  components  listed  below  are  not  included 

with  the  unit,  but  are  supplied  upon  request, 

also  if 

their installation is compulsory.

 

 

 

If  dirt  penetrates  the  water  circuit,  there  could 

be  problems.  Therefore  always  remember  the 
following when connecting the water circuit:  

1.

 

Only use pipes that are clean inside. 

 2.

 

Keep  the end  of  the  pipe  facing  downward 

when removing any burrs.  

 

3.

 

Cover the end of the pipe when inserting it 
through a wall to avoid dust and dirt getting 
in.  

 4. 

Clean  the  pipes  of  the  system  located 
between  the  filter  and  the  unit,  with  running 
water, before connecting it to the system. 

Summary of Contents for EWAQ~G-SR

Page 1: ...EWAQ G SS Standard Efficiency Standard Noise SR Standard Efficiency Reduced Noise XS High Efficiency Standard Noise XR High Efficiency Reduced Noise Refrigerant R410A Original Instructions Installati...

Page 2: ...it connection 10 Water treatment 11 Water flow and volume 11 Anti freeze protection for evaporators and recovery exchangers 12 Electrical system General specifications 12 Wiring at the installation si...

Page 3: ...h the unit In case of doubt contact the manufacturer s representative The aim of this manual is to make sure that the installer and the qualified operator can properly commission operate and maintain...

Page 4: ...es may be in different positions depending on the model and options on the unit Figure 2 Operating limits EWAQ G SS Standard efficiency Standard noise Water temperature at outlet C 1 Slack electrical...

Page 5: ...C01207 15EN 5 22 EWAQ G SR Standard efficiency Reduced noise Water temperature at outlet C EWAQ G XS High efficiency Standard noise Water temperature at outlet C Ambient temperature C Ambient temperat...

Page 6: ...Water temperature at outlet C Water temperature at evaporator outlet C A Operating with glycol B Operating with fan speed mode selected C Operating at maximum fan speed Table 1 Evaporator Difference i...

Page 7: ...orm of insulation Never access electrical components if water and or moisture are present Always disconnect the power supply by closing the main switch before carrying out any work on the cooling fans...

Page 8: ...cooling condenser Both these conditions can cause an increase in condenser pressure which can lead to poor energy efficiency and refrigerating capacity If two or more units are positioned alongside e...

Page 9: ...use lifting hooks fitted with appropriate locking devices The hooks must be safely fastened before performing the handling 3 Fork lift truck Sound protection When sound levels require special control...

Page 10: ...o the heat exchangers Pipe insulation The complete water circuit including all pipes must be insulated to avoid condensate from forming and reducing cooling capacity Protect water pipes from freezing...

Page 11: ...ter The manufacturer is not responsible for any damage or malfunctions of the equipment The quality of the water must comply with the specifications listed in the following table The water pressure mu...

Page 12: ...system of the cooling installation is being designed two or more of the following anti freeze protection methods should be considered at the same time 1 Continuous circulation of water flow inside th...

Page 13: ...nals The power supply cables must be supported by adequate systems The wires connected to the switch must comply with the insulation distance and the distance of surface insulation between the active...

Page 14: ...unit In addition to reading this manual the user must study the microprocessor operating manual and the wiring diagram in order to understand the start up sequence operation shutdown sequence and ope...

Page 15: ...evel full X Check for a load loss in filter dryer where present X Analyse the compressor vibrations X Check the safety valve Note 5 X Heat exchangers Check that the heat exchangers are clean Note 6 X...

Page 16: ...ronic components All these components must be disposed of in accordance with relevant current national and European legislative requirements Lead batteries must be collected and sent to specific waste...

Page 17: ...n Secondary Temperature Sensor M S BC Main Secondary Connection Box D L Request Limit DI Digital Inputs DO Digital Outputs DSP Double Setting Point EF External failure EFS Evaporator flow switch GA Ge...

Page 18: ...D EIMAC01207 15EN 18 22 A Typical refrigerant circuit The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 19: ...15EN 19 22 B Typical refrigerant circuit with partial heat recovery The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water...

Page 20: ...15EN 20 22 C Typical refrigerant circuit with total heat recovery The number of compressors and water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water...

Page 21: ...4 Evaporator water outlet connection 15 Heat recovery water inlet connection 16 Heat recovery water outlet connection 17 Low pressure safety valve 18 High pressure safety valve EP Low pressure transdu...

Page 22: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: