Daikin EWAD-CZ Installation, Operation And Maintenance Manual Download Page 9

D - EIMAC00607-11EU - 9/156 

ENGLISH - ORIGINAL INSTRUCTIONS 

This manual is an important supporting document for qualified personnel but it is not intended to replace such personnel.

Thank you for purchasing this chiller 

READ 

THIS 

MANUAL 

CAREFULLY 

BEFORE 

INSTALLING AND STARTING UP THE UNIT.  
IMPROPER  INSTALLATION  COULD  RESULT  IN 
ELECTRIC  SHOCK,  SHORT-CIRCUIT,  LEAKS,  FIRE 
OR  OTHER  DAMAGE  TO  THE  EQUIPMENT  OR 
INJURE TO PEOPLE. 
THE 

UNIT 

MUST 

BE 

INSTALLED 

BY 

PROFESSIONAL OPERATOR/TECHNICIAN  
UNIT  STARTUP  HAS  TO  BE  PERFORMED  BY 
AUTHORIZED AND TRAINED PROFESSIONAL 
ALL  ACTIVITIES  HAVE  TO  BE  PERFORMED 
ACCORDING TO LOCAL LAWS AND REGULATION. 

UNIT 

INSTALLATION 

AND 

START 

UP 

IS 

ABOSOLUTELY  FORBIDDEN  IF  ALL  INSTRUCTION 
CONTAINED IN THIS MANUAL ARE NOT CLEAR.

IF 

CASE 

OF 

DOUBT 

CONTACT 

THE 

MANUFACTURER  REPRESENTATIVE  FOR  ADVICE 
AND INFORMATION. 

Description

The unit you bought is an “air cooled chiller”, a machine aimed 
to  cool  water  (or  water-glycol  mixture)  within  the  limits 
described  in  the  following.  The  unit  operazion  is  based  on 
vapour compression, condensation and evaporation according 
to reverse Carnot cycle.The main components are: 

Screw compressor to rise the refrigerant vapour pressure 
from evaporation pressure to condensation pressure 

Evaporator,  where  the  low  pressure  liquid  reqrigerant 
evaporates so cooling the water 

Condenser,  where  high  pressure  vapour  condensate 
rejecting  heat  removed  from  the  chilled  water  in  the 
atmosphere thanks to an air cooled heat exchanger. 

Expansion  valve  allowing  to  reduced  the  pressure  of 
condensed  liquid  from  coinsensation  pressue  to 
evaporation pressure 

General Information

All  units  are  delivered  with 

wiring  diagrams

certified 

drawings, nameplate

;  and 

DOC  (Declaration  Of 

Conformity)

;  these  documents  show  all  technical  data 

for  the  unit  you  have  bought  and  they 

MUST  BE 

CONSIDERED  ESSENTIAL  DOCUMENTS  OF  THIS 
MANUAL

In  case  of  any  discrepancy  between  this  manual  and  the 
equipment’s  documents  please  refer  to  on  board  documents. 
In case of any doubt contact the manufacturer representative.. 

The  purpose  of  this  manual  is  to  allow  the  installer  and  the 
qualified operator to ensure proper installation, commissioning 
and  maintenance  of  the  unit,  without  any  risk  to  people, 
animals and/or objects. 

Receiving the unit

The  unit  must  be  inspected  for  any  possible  damage 
immediately  upon  reaching  final  place  of  installation.  All 
components described in the delivery note must be inspected 
and checked.  
Should  the  unit  be  damaged,  do  not  remove  the  damaged 
material  and  immediately  report  the  damage  to  the 
transportation company and request  they inspect the unit..  
Immediately  report  the  damage  to  the  manufacturer 
representative, a set of photographs are helpful in recognizing 
responsibility 
Damage  must  not  be  repaired  before  the  inspection  of  the 
transportation company representative. 
Before  installing  the  unit,  check  that  the  model  and  power 
supply  voltage  shown  on  the  nameplate  are  correct. 
Responsibility  for  any  damage  after  acceptance  of  the  unit 
cannot be attributed to the manufacturer. 

Operating limits

Storing 

Environmental conditions must be within the following limits: 
Minimum ambient temperature 

-20°C 

Maximum ambient temperature  : 

57°C 

Maximum R.H. 

95% not condensing 

Storing below the minimum temperature may cause damage to 
components. Storing above the maximum temperature causes 
opening  of  safety  valves.  Storing  in  condensing  atmosphere 
may damage electronic components.

Operation 

Operation is allowed within the limits mentioned in Figure 2. 
The unit must be operated with an evaporator water flow rate 
between  50%  and  140%  of  nominal  flow  rate  (at  standard 
operating conditions). 
Operation out of the mentioned limits may damage the unit. 
In case of doubts contact manufacturer representative. 

Figure 1 - Description of the labels applied to the electrical panel 

Label Identification 

1

 – Non flammable gas symbol  

6

 – Electrical hazard symbol  

2

 – Gas type  

7

 – Hazardous Voltage warning  

3

 – Unit nameplate data  

8

 – Cable tightening warning  

4

 – Manufacturer’s logo  

9

 – Lifting instructions 

– Water circuit filling warning

Summary of Contents for EWAD-CZ

Page 1: ... R 134a English 9 Deutsch 16 Français 25 Nederlands 34 Español 41 Italiano 48 ǼȜȜȘȞȚțȐ 55 Português 64 Ɋɭɫɫɤɢɣ 71 Swedish 78 Norsk 85 Finnish Suomi 92 Połysk 99 ýech 106 Hrvat 113 Magyar 120 Român 127 Slovenski 134 Ȼɴɥɝɚɪɫɤɢ 141 Slovenský 148 English language Original instructions All other language Translation of the Original instructions Installation Operation and Maintenance Manual D EIMAC00607...

Page 2: ...ɟɪɚ Ⱦɥɹ ɨɩɪɟɞɟɥɟɧɢɹ ɩɚɪɚɦɟɬɪɨɜ ɩɨɞɤɥɸɱɟɧɢɹ ɜɨɞɨɩɪɨɜɨɞɚ ɫɥɟɞɭɟɬ ɭɱɢɬɵɜɚɬɶ ɞɚɧɵɟ ɝɚɛɚɪɢɬɧɵɯ ɱɟɪɬɟɠɟɣ ɨɛɨɪɭɞɨɜɚɧɢɹ A Typisk kylkrets Vattenledningens inlopp och utlopp är ungefärliga Se maskinens dimensionsdiagram för exakta vattenanslutningar A Typisk kjølemediekrets vanninntak og uttak er kun antydninger Se maskinens måltegninger for nøyaktige vanntilkoblinger A Tyypillinen jäähdytyspiiri Vedentulo...

Page 3: ...D EIMAC00607 11EU 3 156 A ...

Page 4: ...ɩɚɪɚɦɟɬɪɨɜ ɩɨɞɤɥɸɱɟɧɢɹ ɜɨɞɨɩɪɨɜɨɞɚ ɫɥɟɞɭɟɬ ɭɱɢɬɵɜɚɬɶ ɞɚɧɵɟ ɝɚɛɚɪɢɬɧɵɯ ɱɟɪɬɟɠɟɣ ɨɛɨɪɭɞɨɜɚɧɢɹ B Typisk kylkrets med värmeåtervinning Vattenledningens inlopp och utlopp är ungefärliga Se maskinens dimensionsdiagram för exakta vattenanslutningar B Typisk kjølemediekrets med varmegjenvinning vanninntak og uttak er kun antydninger Se maskinens måltegninger for nøyaktige vanntilkoblinger B Tyypillinen jä...

Page 5: ...D EIMAC00607 11EU 5 156 B ...

Page 6: ...ón Sonda temperatura aspirazione 19 EP Low pressure transducer Niederdrucksensor Transducteur basse pression Omzetter lage druk Transductor de baja presión Trasduttore bassa pressione 20 Suction shut off valve Absperrventil Saugleitung Robinet d aspiration Aanzuiging afsluitklep Grifo de aspiración Rubinetto di aspirazione 21 Liquid injection shut off valve Asperrventil der Flüssigkeitseinspritzun...

Page 7: ...un lämpötila anturi Sonda temperatury zasysania Tepelná sonda nasávání 19 EP ȂİIJĮIJȡȠʌȑĮȢ ȤĮȝȘȜȒȢ ʌȓİıȘȢ Subarrefecedor ou economizador adicional Ⱦɚɬɱɢɤ ɧɢɡɤɨɝɨ ɞɚɜɥɟɧɢɹ Lågtrycksomvandlare Lavtrykksomformer Matalapaineanturi Przetwornik niskiego ciĞnienia Transduktor nízkého tlaku 20 ȈIJȡĮȖȖĮȜȚıIJȚțȒ ȕĮȜȕȓįĮ ĮȞĮȡȡȩijȘıȘȢ Válvula solenóide subarrefecedor ou economizador adicional Ɉɬɫɟɱɧɨɣ ɤɥɚɩɚɧ ɧɚ ɜɫ...

Page 8: ...da usisa Elszívási hĘmérsékletmérĘ szonda Sondă de temperatură aspiraĠie Sonda temperature v sesalnem tokokrogu Ɍɟɦɩɟɪɚɬɭɪɧɚ ɫɨɧɞɚ ɡɚ ɡɚɫɦɭɤɜɚɧɟ Tepelná sonda nasávania 19 EP Transduktor nizak pritisak Kis nyomás transzduktor Traductor presiune joasă Nizkotlaþni pretvornik Ʉɨɧɜɟɪɬɨɪ ɧɢɫɤɨ ɧɚɥɹɝɚɧɟ Transduktor nízkeho tlaku 20 Ventil za zatvaranje usisa Elszívó zárócsap Robinet de aspiraĠie Ventil ...

Page 9: ...documents please refer to on board documents In case of any doubt contact the manufacturer representative The purpose of this manual is to allow the installer and the qualified operator to ensure proper installation commissioning and maintenance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reach...

Page 10: ... from the unit and in rest position contact immediately emergency rescue personnel of the building or the Health Emergency Service wait without leaving the injured person alone until the rescue operators come give all necessary information to the the rescue operators Avoid installing the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or ra...

Page 11: ...t air supply to the air cooled condenser Both these conditions can cause an increase of condensing pressure which leads to a reduction in energy efficiency and refrigerating capacity Any side of the unit must be accessible for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstac...

Page 12: ... against water freezing at ambient temperatures as low as 25 C All the other water piping devices outside the unit must therefore be protected against freezing 10 The heat recovery device must be emptied of water during the winter season unless an ethylene glycol mixture in appropriate percentage is added to the water circuit 11 If case of unit substitution the entire water system must be emptied ...

Page 13: ...eat exchanging capacity Pressure drop can increase as well thus reducing water flow Proper water treatment therefore reduces the risk of corrosion erosion scaling etc The most appropriate water treatment must be determined locally according to the type of system and water characteristics The manufacturer is not responsible for damage to or malfunctioning of equipment caused by failure to treat wat...

Page 14: ... Before servicing the unit in any way open the general disconnecting switch on the unit s main power supply When the unit is off but the disconnecting switch is in the closed position unused circuits are live as well Never open the terminal board box of the compressors before having opened the unit s general disconnecting switch Contemporaneity of single phase and three phase loads and unbalance b...

Page 15: ...orne particles it might be necessary to clean the condenser bank more often 5 Replace the oil filter when the pressure drop across it reaches 2 0 bar 6 Check for any dissolved metals 7 TAN Total Acid Number 0 10 No action Between 0 10 and 0 19 Replace anti acid filters and re check after 1000 running hours Continue to replace filters until the TAN is lower than 0 10 0 19 Replace oil oil filter and...

Page 16: ...TUNG Für den Fall eines etwaigen Widerspruchs zwischen diesem Handbuch und der Geräteunterlagen beziehen Sie sich bitte auf diese Wenden Sie sich bitte in Zweifelsfällen an den Vertreter des Herstellers Mithilfe dieses Handbuchs können Installationstechniker und qualifizierte Benutzer alle notwendigen Schritte zur richtigen Installation Inbetriebnahme und Wartung der Einheit vornehmen ohne dass da...

Page 17: ...D EIMAC00607 11EU 155 156 ...

Page 18: ... cover picture is not binding Air cooled screw chillers EWAD CZ Inverter X High Efficiency 640 C18 Cooling capacity from 635 to 1800 kW 1 8523 1 9 1 8523 1 9 1 8523 1 9 1 8523 1 9 Zandvoordestraat 300 B 8400 Ostend Belgium www daikineurope com Daikin units comply with the European regulations that guarantee the safety of the ...

Reviews: