D - EIMAC00607-11EU - 15/156 

Periodic obligatory checks and starting up of 
appliances under pressure  

The  units  are  included  in  category  IV  of  the  classification 
established by the European Directive PED 97/23/EC.  

For chillers belonging to this category, some local regulations 
require a periodic inspection by an authorized agency. Please 
check with your local requirements. 

Table 2 - Routine maintenance programme 

List of Activities 

Weekly 

Monthly 

(Note 1) 

Yearly/Seas

onal 

(Note 2) 

General:

Reading of operating data (Note 3) 

X

Visual inspection of unit for any damage and/or loosening 

X

Verification of thermal insulation integrity 

X

Clean and paint where necessary 

X

Analysis of water (6) 

X

Check of flow switch operation 

X

Electrical:

Verification of control sequence 

X

Verify contactor wear – Replace if necessary 

X

Verify that all electrical terminals are tight – Tighten if necessary 

X

Clean inside the electrical control board 

X

Visual inspection of components for any signs of overheating 

X

Verify operation of compressor and electrical resistance 

X

Measure compressor motor insulation using the Megger  

X

Refrigeration circuit:

Check for any refrigerant leakage 

X

Verify refrigerant flow using the liquid sight glass – Sight glass full 

X

Verify filter dryer pressure drop  

X

Verify oil filter pressure drop (Note 5) 

X

Analyse compressor vibrations 

X

Analyse compressor oil acidity (7) 

X

Condenser section:

Clean condenser banks (Note 4) 

X

Verify that fans are well tightened 

X

Verify condenser bank fins – Comb if necessary 

X

Notes: 
1. 

Monthly activities include all the weekly ones. 

2. 

The annual (or early season) activities include all weekly and monthly activities. 

3. 

Unit operating values should be read on a daily basis thus keeping high observation standards. 

4. 

In environments with a high concentration of air-borne particles, it might be necessary to clean the condenser bank more often. 

5. 

Replace the oil filter when the pressure drop across it reaches 2.0 bar. 

6. 

Check for any dissolved metals. 

7. 

TAN (Total Acid Number) :  

0,10 : No action 

Between  0.10  and  0.19  :  Replace  anti-acid  filters  and  re-check  after  1000  running  hours.  Continue  to  replace  filters 
until the TAN is lower than 0.10. 

>

0,19 : Replace oil, oil filter and filter dryer. Verify at regular intervals. 

Important information regarding the refrigerant 
used  

This  product  contains  fluorinated  greenhouse  gases  covered 
by the Kyoto Protocol. Do not vent gases into the atmosphere. 
Refrigerant type: 

 

R134a 

GWP(1) value: 

 

1300 

(1)GWP = 

 

global warming potential 

The  refrigerant  quantity  necessary  for  standard  operation  is 
indicated on the unit name plate. 
Real refrigerant quantity charged in the unit is listed on a silver 
sticker inside the electrical panel. 
Periodical  inspections  for  refrigerant  leaks  may  be  required 
depending on European or local legislation. 
Please contact your local dealer for more information. 

Disposal 

The  unit  is  made  of  metal,  plastic  and  electronic  parts.    All 
these parts must be disposed of in accordance with the local 
regulations in terms of disposal. 
Lead  batteries  must  be  collected  and  sent  to  specific  refuse 
collection centres.  
Oil  must  be  collected  and  sent  to  specific  refuse  collection 
centres.  

This manual is a technical aid and does not represent a binding offer. The content cannot be held as explicitly or implicitly guaranteed as complete, precise or reliable. All data and 
specifications contained herein may be modified without notice. The data communicated at the moment of the order shall hold firm. 
The manufacturer shall assume no liability whatsoever for any direct or indirect damage, in the widest sense of the term, ensuing from or connected with the use and/or interpretation 
of this manual. 

We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. 

Summary of Contents for EWAD-CZ

Page 1: ... R 134a English 9 Deutsch 16 Français 25 Nederlands 34 Español 41 Italiano 48 ǼȜȜȘȞȚțȐ 55 Português 64 Ɋɭɫɫɤɢɣ 71 Swedish 78 Norsk 85 Finnish Suomi 92 Połysk 99 ýech 106 Hrvat 113 Magyar 120 Român 127 Slovenski 134 Ȼɴɥɝɚɪɫɤɢ 141 Slovenský 148 English language Original instructions All other language Translation of the Original instructions Installation Operation and Maintenance Manual D EIMAC00607...

Page 2: ...ɟɪɚ Ⱦɥɹ ɨɩɪɟɞɟɥɟɧɢɹ ɩɚɪɚɦɟɬɪɨɜ ɩɨɞɤɥɸɱɟɧɢɹ ɜɨɞɨɩɪɨɜɨɞɚ ɫɥɟɞɭɟɬ ɭɱɢɬɵɜɚɬɶ ɞɚɧɵɟ ɝɚɛɚɪɢɬɧɵɯ ɱɟɪɬɟɠɟɣ ɨɛɨɪɭɞɨɜɚɧɢɹ A Typisk kylkrets Vattenledningens inlopp och utlopp är ungefärliga Se maskinens dimensionsdiagram för exakta vattenanslutningar A Typisk kjølemediekrets vanninntak og uttak er kun antydninger Se maskinens måltegninger for nøyaktige vanntilkoblinger A Tyypillinen jäähdytyspiiri Vedentulo...

Page 3: ...D EIMAC00607 11EU 3 156 A ...

Page 4: ...ɩɚɪɚɦɟɬɪɨɜ ɩɨɞɤɥɸɱɟɧɢɹ ɜɨɞɨɩɪɨɜɨɞɚ ɫɥɟɞɭɟɬ ɭɱɢɬɵɜɚɬɶ ɞɚɧɵɟ ɝɚɛɚɪɢɬɧɵɯ ɱɟɪɬɟɠɟɣ ɨɛɨɪɭɞɨɜɚɧɢɹ B Typisk kylkrets med värmeåtervinning Vattenledningens inlopp och utlopp är ungefärliga Se maskinens dimensionsdiagram för exakta vattenanslutningar B Typisk kjølemediekrets med varmegjenvinning vanninntak og uttak er kun antydninger Se maskinens måltegninger for nøyaktige vanntilkoblinger B Tyypillinen jä...

Page 5: ...D EIMAC00607 11EU 5 156 B ...

Page 6: ...ón Sonda temperatura aspirazione 19 EP Low pressure transducer Niederdrucksensor Transducteur basse pression Omzetter lage druk Transductor de baja presión Trasduttore bassa pressione 20 Suction shut off valve Absperrventil Saugleitung Robinet d aspiration Aanzuiging afsluitklep Grifo de aspiración Rubinetto di aspirazione 21 Liquid injection shut off valve Asperrventil der Flüssigkeitseinspritzun...

Page 7: ...un lämpötila anturi Sonda temperatury zasysania Tepelná sonda nasávání 19 EP ȂİIJĮIJȡȠʌȑĮȢ ȤĮȝȘȜȒȢ ʌȓİıȘȢ Subarrefecedor ou economizador adicional Ⱦɚɬɱɢɤ ɧɢɡɤɨɝɨ ɞɚɜɥɟɧɢɹ Lågtrycksomvandlare Lavtrykksomformer Matalapaineanturi Przetwornik niskiego ciĞnienia Transduktor nízkého tlaku 20 ȈIJȡĮȖȖĮȜȚıIJȚțȒ ȕĮȜȕȓįĮ ĮȞĮȡȡȩijȘıȘȢ Válvula solenóide subarrefecedor ou economizador adicional Ɉɬɫɟɱɧɨɣ ɤɥɚɩɚɧ ɧɚ ɜɫ...

Page 8: ...da usisa Elszívási hĘmérsékletmérĘ szonda Sondă de temperatură aspiraĠie Sonda temperature v sesalnem tokokrogu Ɍɟɦɩɟɪɚɬɭɪɧɚ ɫɨɧɞɚ ɡɚ ɡɚɫɦɭɤɜɚɧɟ Tepelná sonda nasávania 19 EP Transduktor nizak pritisak Kis nyomás transzduktor Traductor presiune joasă Nizkotlaþni pretvornik Ʉɨɧɜɟɪɬɨɪ ɧɢɫɤɨ ɧɚɥɹɝɚɧɟ Transduktor nízkeho tlaku 20 Ventil za zatvaranje usisa Elszívó zárócsap Robinet de aspiraĠie Ventil ...

Page 9: ...documents please refer to on board documents In case of any doubt contact the manufacturer representative The purpose of this manual is to allow the installer and the qualified operator to ensure proper installation commissioning and maintenance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reach...

Page 10: ... from the unit and in rest position contact immediately emergency rescue personnel of the building or the Health Emergency Service wait without leaving the injured person alone until the rescue operators come give all necessary information to the the rescue operators Avoid installing the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or ra...

Page 11: ...t air supply to the air cooled condenser Both these conditions can cause an increase of condensing pressure which leads to a reduction in energy efficiency and refrigerating capacity Any side of the unit must be accessible for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstac...

Page 12: ... against water freezing at ambient temperatures as low as 25 C All the other water piping devices outside the unit must therefore be protected against freezing 10 The heat recovery device must be emptied of water during the winter season unless an ethylene glycol mixture in appropriate percentage is added to the water circuit 11 If case of unit substitution the entire water system must be emptied ...

Page 13: ...eat exchanging capacity Pressure drop can increase as well thus reducing water flow Proper water treatment therefore reduces the risk of corrosion erosion scaling etc The most appropriate water treatment must be determined locally according to the type of system and water characteristics The manufacturer is not responsible for damage to or malfunctioning of equipment caused by failure to treat wat...

Page 14: ... Before servicing the unit in any way open the general disconnecting switch on the unit s main power supply When the unit is off but the disconnecting switch is in the closed position unused circuits are live as well Never open the terminal board box of the compressors before having opened the unit s general disconnecting switch Contemporaneity of single phase and three phase loads and unbalance b...

Page 15: ...orne particles it might be necessary to clean the condenser bank more often 5 Replace the oil filter when the pressure drop across it reaches 2 0 bar 6 Check for any dissolved metals 7 TAN Total Acid Number 0 10 No action Between 0 10 and 0 19 Replace anti acid filters and re check after 1000 running hours Continue to replace filters until the TAN is lower than 0 10 0 19 Replace oil oil filter and...

Page 16: ...TUNG Für den Fall eines etwaigen Widerspruchs zwischen diesem Handbuch und der Geräteunterlagen beziehen Sie sich bitte auf diese Wenden Sie sich bitte in Zweifelsfällen an den Vertreter des Herstellers Mithilfe dieses Handbuchs können Installationstechniker und qualifizierte Benutzer alle notwendigen Schritte zur richtigen Installation Inbetriebnahme und Wartung der Einheit vornehmen ohne dass da...

Page 17: ...D EIMAC00607 11EU 155 156 ...

Page 18: ... cover picture is not binding Air cooled screw chillers EWAD CZ Inverter X High Efficiency 640 C18 Cooling capacity from 635 to 1800 kW 1 8523 1 9 1 8523 1 9 1 8523 1 9 1 8523 1 9 Zandvoordestraat 300 B 8400 Ostend Belgium www daikineurope com Daikin units comply with the European regulations that guarantee the safety of the ...

Reviews: