6 Electrical installation
Installation manual
13
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620240-1 – 2020.06
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
be
reached
via
professional.standbyme.daikin.eu
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
Rotating fan.
Before powering ON the outdoor unit, make
sure that the discharge grille covers the fan as protection
against a rotating fan. See
"4.2.4 To install the discharge
9].
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Only for EWAA011~016DAV3P, EWAA011~016DAV3P-H-,
EWYA009~016DAV3P and EWYA009~016DAV3P-H-
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X3M
0.88 ±10%
X4M
2.45 ±10%
X5M
0.88 ±10%
X9M
2.45 ±10%
X10M
0.88 ±10%
6.3
Connections to the outdoor unit
Item
Description
Power supply (main)
See
"6.3.2 To connect the main power
14].
User interface
See
16].
Shut-off valve
See
"6.3.4 To connect the shut-off
17].
Item
Description
Electricity meters
"6.3.5 To connect the electricity
Alarm output
18].
Space cooling/heating
operation control
"6.3.7 To connect the space cooling/
Changeover to
external heat source
control
"6.3.8 To connect the changeover to
Power consumption
digital inputs
19].
Safety thermostat
thermostat (normally closed
contact)"
Smart Grid
Backup heater kit +
Bypass valve kit
"6.3.12 External backup heater
21].
Room thermostat
(wired or wireless)
In case of wireless room
thermostat
, see:
▪ Installation manual of the wireless
room thermostat
▪ Addendum
book
for
optional
equipment
In case of wired room thermostat
,
see:
▪ Installation manual of the wired
room thermostat
▪ Addendum
book
for
optional
equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Remote outdoor
sensor
See:
▪ Installation manual of the remote
outdoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (
External sensor
=
Outdoor
)
[9.B.2]
Ext. amb. sensor offset
[9.B.3]
Averaging time
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset