6 Electrical installation
Installation manual
14
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620240-1 – 2020.06
Item
Description
Human Comfort
Interface
See:
▪ Installation and operation manual of
the Human Comfort Interface
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
WLAN cartridge
See:
▪ Installation manual of the WLAN
cartridge
▪ Installer reference guide
—
[D]
Wireless gateway
Flow switch
See installation manual of the flow
switch
Wires: 2×0.5 mm²
—
Location extra components
The following illustration shows the location of the extra components
that you need to install on the outdoor unit when using certain option
kits.
c
b
a
d
a
Flow switch (EKFLSW1)
b
Demand PCB (A8P: EKRP1AHTA)
c
Digital I/O PCB (A4P: EKRP1HBAA)
d
Smart grid relay kit (EKRELSG)
6.3.1
To connect the electrical wiring to the
outdoor unit
1
Open the service cover. See
2
Insert the cables at the back of the unit, and route them through
the unit to the appropriate terminal blocks.
b
c
a
d
a
High voltage options
b
Low voltage options
c
Power supply for backup heater (in case of unit with
integrated backup heater)
Wiring for backup heater kit (in case of external backup
heater kit)
d
Unit power supply
3
Connect the wires to the appropriate terminals, and fix the
cables with cable ties.
6.3.2
To connect the main power supply
This topic describes 2 possible ways to connect the main power
supply:
▪ In case of normal kWh rate power supply
▪ In case of preferential kWh rate power supply
In case of normal kWh rate power supply
Normal kWh rate
power supply
Wires: 1N+GND, OR 3N+GND
Maximum running current: Refer to name
plate on unit.
—
1
Open the service cover. See
9].
2
Connect as follows (1N~or 3N~ depending on model, see name
plate):
N
L N PE
Q1DI
X1M.L
X1M.L1
X1M.L2
X1M.L3
X1M.N
X1M.N
X1M.
X1M.
L3
L2
L1
N PE
Q1DI
1N~
3N~
OR
1N~, 50 Hz,
220-240 V AC
3N~, 50 Hz,
380-415 V AC
X1M
OR
1N~
3N~
L1 L2 L3 N
L N
3
Fix the cables with cable ties to the cable tie mountings.