Checking the Inputs and Outputs
ESIE11-02
3–20
3
1
3
4
5
3.7
Electrical Error Overview: EUWA*5-24KBZW1 and EUWY*5-24KBZW1
Introduction
This map gives an overview of the most common electrical errors that can occur on the
EUWA*5-24KBZW1 and the EUWY*5-24KBZW1.
See also "Wiring Diagram: EUWA*5-24KBZW1 and EUWY*5-24KBZW1" on page 1–75.
General items
Before proceeding, confirm the status of the following items:
■
Microchiller compact: is the controller initialized? Are all parameters set?
■
I/O PCB: Is the PCB working?
If the HAP (green led) blinks, the PCB is working.
General remark
about H1P and H2P
on I/O PCB
If an electrical error is solved, H1P (red) and H2P (red) on the I/O PCB keep their latest status. H1P
and H2P can only be reset by switching the I/O PCB OFF/ON.
Error list
microchiller
compact controller
The table below contains an error list for the microchiller compact controller.
Microchiller
compact
controller
I/O PCB
General
error
description
Possible cause
Part
Con-
nector
Action
H1P
H2P
e1
OFF
OFF
Sensor input
1 broken
Evaporator inlet water
sensor broken
R3T
X60A
Check sensor.
e2
OFF
OFF
Sensor input
2 broken
Evaporator outlet water
sensor broken
R4T
X61A
Check sensor.
e3
Or
fl
and
hp1
OFF
ON
Fuse blown
F4
X1A
Check fuse.
Reverse phase error
X1A
Check L1/L2/L3
connection.
I/O PCB broken
A2P
■
Check I/O PCB (HAP
must be blinking).
■
Check trafo power
supply.
fl
OFF
OFF
Flow error
Flow switch open
S10L
X65A
Green LED’s = flow
Overcurrent protection
pump
K6A
X28A
Reset overcurrent.
Shortcut
X28A
Check shortcut
Wireharness between I/O
PCB and microchiller
compact
X71A
X1
■
Check connections on
X71A (I/O PCB)
■
Check connections on
X1 (microchiller
compact)
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...