EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
Setting
Value
In case of heat pump convectors:
External room thermostat for the
additional
zone:
▪
#: [3.A]
▪
Code: [C-06]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Shut-off valve output
Set to follow the thermo demand of the
main zone.
Benefits
▪
Comfort.
-
The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature
(modulation).
-
The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heat pump convectors.
▪
Efficiency.
-
Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.
6.3 Setting up an auxiliary heat source for space heating
INFORMATION
Bivalent is only possible in case of 1 leaving water temperature zone with:
▪
room thermostat control, OR
▪
external room thermostat control.
▪
Space heating can be done by:
-
The indoor unit
-
An auxiliary boiler (field supply) connected to the system
▪
When there is a heating request, the indoor unit or the auxiliary boiler starts
operating. Which of these units operates, depends on the outdoor temperature
(status of the changeover to external heat source). When the permission is given
to the auxiliary boiler, the space heating by the indoor unit is turned OFF.
▪
Domestic hot water is always produced by the DHW tank connected to the
indoor unit.
▪
Bivalent operation is only possible if space heating is turned ON.
INFORMATION
▪
During heating operation of the heat pump, the heat pump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
▪
During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.