7 Configuration

Installation manual

28

ETSH/X(B)12P30+50EF

Daikin Altherma 3 H MT ECH

O

4P663479-1A – 2022.07

1234

Advanced user

User pin code

The 

User

 pin code is 

0000

.

0000

User

To access the installer settings

1

Set the user permission level to 

Installer

.

2

Go to [9]: 

Installer settings

.

To modify an overview setting

Example: 

Modify [1‑01] from 15 to 20.

Most  settings  can  be  configured  via  the  menu  structure.  If  for  any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:

1

Set the user permission level to 

Installer

. See 

"To

change the user permission level"

 [

4

 27].

2

Go to [9.I]: 

Installer settings

 > 

Overview

field settings

.

3

Turn the left dial to select the first part of the setting
and confirm by pressing the dial.

00
01
02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

0

1

2
3

4

Turn the left dial to select the second part of the
setting

00
01

15

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

5

Turn the right dial to modify the value from 15 to 20.

00
01

20

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

6

Press the left dial to confirm the new setting.

7

Press the center button to go back to the home
screen.

INFORMATION

When  you  change  the  overview  settings  and  you  go  back
to  the  home  screen,  the  user  interface  will  show  a  popup
screen and request to restart the system.

When  confirmed,  the  system  will  restart  and  recent
changes will be applied.

7.2

Configuration wizard

After  first  power  ON  of  the  system,  the  user  interface  starts  a
configuration wizard. Use this wizard to set the most important initial
settings  for  the  unit  to  run  properly.  If  required,  you  can  afterwards
configure  more  settings.  You  can  change  all  these  settings  via  the
menu structure.

7.2.1

Configuration wizard: Language

#

Code

Description

[7.1]

N/A

Language

7.2.2

Configuration wizard: Time and date

#

Code

Description

[7.2]

N/A

Set the local time and date

INFORMATION

By  default,  daylight  savings  time  is  enabled  and  clock
format  is  set  to  24  hours.  If  you  want  to  change  these
settings,  you  can  do  this  in  the  menu  structure  (

User

settings

 > 

Time/date

) once the unit is initialised.

7.2.3

Configuration wizard: System

Indoor unit type

The indoor unit type is displayed, but cannot be adjusted.

Backup heater type

#

Code

Description

[9.3.1]

[E‑03]

▪ 0: 

None

▪ 2: 

3V

▪ 3: 

6V

▪ 4: 

9W

Domestic hot water

The  system  includes  an  energy  storage  tank  and  can  prepare
domestic hot water. This setting is read only.

#

Code

Description

[9.2.1]

[E‑05]

[E‑06]

[E‑07]

Integrated

The  backup  heater  will  also  be  used
for domestic hot water heating.

Emergency

When the heat pump fails to operate, the backup heater or boiler can
serve  as  an  emergency  heater.  It  then  takes  over  the  heat  load
either automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs,  the  backup  heater  or  boiler  automatically  takes  over  the
domestic hot water production and space heating.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

Summary of Contents for ETSH12P30EF

Page 1: ...aldatahub eu Installation manual Daikin Altherma 3 H MT ECH O English Installation manual Daikin Altherma 3 H MT ECH O ETSH12P30EF ETSH12P50EF ETSHB12P30EF ETSHB12P50EF ETSX12P30EF ETSX12P50EF ETSXB12...

Page 2: ...v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu...

Page 3: ...vered as accessory 26 6 3 15 To connect the solar input 26 6 3 16 To connect the DHW output 26 7 Configuration 27 7 1 Overview Configuration 27 7 1 1 To access the most used commands 27 7 2 Configurat...

Page 4: ...nd regulations Installation site see 4 1 Preparing the installation site 46 WARNING Follow the service space dimensions in this manual for correct installation of the unit See 4 1 1 Installation site...

Page 5: ...eating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WA...

Page 6: ...e requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space cooling operation 5 35 C Dome...

Page 7: ...nd slide the interface panel downwards 1 2 2 Remove the switch box cover NOTICE Do NOT damage or remove the foam sealing of the switch box 3 Disconnect the ground connection from the top cover of the...

Page 8: ...nstall the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 46 2 Connect the drain hose to the drain See 4 3 2 To connect the drain...

Page 9: ...er inside the storage tank is not pressurized Therefore a visual check of the water level in the storage tank has to be carried out annually Water temperature All installed piping and piping accessori...

Page 10: ...rtorque with a suitable tool 7 mm 1 2 3 2 Remove the thermal insulation of the hydraulic block Open the vent valve on the pump by one turn Afterwards put the thermal insulation back on the hydraulic b...

Page 11: ...o install a non return valve on the water inlet of the storage tank in accordance with the applicable legislation It is recommended to install a pressure reducing valve on the cold water inlet in acco...

Page 12: ...ts from freezing the software is equipped with special frost protection functions such as water pipe freeze prevention and drain prevention see the installer reference guide that include the activatio...

Page 13: ...e system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves located indoors near the piping entry exit points can preven...

Page 14: ...kup heater of the indoor unit See 6 3 3 To connect the backup heater power supply 417 6 2 Guidelines when connecting the electrical wiring Tightening torques Indoor unit Item Tightening torque N m M4...

Page 15: ...rface See Installation and operation manual of the Human Comfort Interface Addendum book for optional equipment Wires 2 0 75 1 25 mm Maximum length 500 m 2 9 Control 1 6 Room sensor offset WLAN module...

Page 16: ...minals is NOT in service position while cables are connected to one of the terminals Otherwise the cables could be too short X12M 6 3 2 To connect the main power supply 1 Open the following see 4 2 1...

Page 17: ...nefit kWh power supply A B X1M 1 2 3 3 4 4 5 6 c X 5M 1 3x b a S1S c 3 4 a 1 2 3 230 6 3 A V AC 1N 50 Hz b L N F2B 1 3 2 4 I I Q DI 2 6 5 3x A B a Interconnection cable b Power supply indoor unit c Pr...

Page 18: ...tage systems with input current 16 A and 75 A per phase b This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctu...

Page 19: ...cover 2 Connect both connection cables from the backup heater EKECBU to the appropriate connectors as shown in the illustration below 3 Fix the cable with cable ties to the cable tie mountings General...

Page 20: ...and X5M 3 1 Open the following see 4 2 1 To open the indoor unit 47 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the electricity meters cable to the appropriate...

Page 21: ...the alarm output cable to the appropriate terminals as shown in the illustration below A B B 1 2 X 2M 1 N L Alarm output Max load 0 3 A 230 V AC 1 A 5 V DC 1 2 A 3 Fix the cable with cable ties to the...

Page 22: ...n the following see 4 2 1 To open the indoor unit 47 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the changeover to external heat source cable to the appropriat...

Page 23: ...the indoor unit 47 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the safety thermostat normally closed cable to the appropriate terminals as shown in the illust...

Page 24: ...the Smart Grid in case of low voltage contacts is as follows 8 7 S11S 6 5 S S 10 4 3 X 5M 1 S S 4 10 9 a 2 1 a Jumper factory mounted If you also connect a safety thermostat Q4L replace the jumper wi...

Page 25: ...rt Grid relay kit EKRELSG and remove the terminal X M 10 K1A X10M K2A 3 Install the components of the Smart Grid relay kit as follows 2 2 K1A K2A X15M X12M X 5M M X 1 12 3 4 5 6 X15M 3 X12M 23 X12M 24...

Page 26: ...input Wires 0 5 mm Solar input contact 5 V DC voltage supplied by PCB 1 Open the following see 4 2 1 To open the indoor unit 47 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cov...

Page 27: ...e most used commands 427 Afterwards If necessary you can make changes to the configuration in the menu structure or the overview settings INFORMATION When the configuration wizard is finished the user...

Page 28: ...starts a configuration wizard Use this wizard to set the most important initial settings for the unit to run properly If required you can afterwards configure more settings You can change all these s...

Page 29: ...er temperature zones During configuration the number of water zones must be set INFORMATION Mixing station If your system layout contains 2 LWT zones you need to install a mixing station in front of t...

Page 30: ...to heat up the storage tank INFORMATION The capacities displayed in the selection menu for 4 0A are only correctly displayed for correct selection of the capacity steps 6 03 and 6 04 INFORMATION Ener...

Page 31: ...ctive low outdoor temperatures will result in warmer water and vice versa During weather dependent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates...

Page 32: ...curve There are 2 types of weather dependent curves 2 points curve Slope offset curve Which type of curve you use to make adjustments depends on your personal preference See 7 3 4 Using weather depend...

Page 33: ...ne Setpoint mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Additional zone Setpoint mode WD heating fixe...

Page 34: ...Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection...

Page 35: ...peration mode Allow electrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4...

Page 36: ...ing has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply pan...

Page 37: ...water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the opera...

Page 38: ...all an electric backup heater to ensure safe operation for all conditions Drain back models For drain back models a backup heater EKECBUA must always be installed For drain back models the factory set...

Page 39: ...onnection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 1 b2 DHW Hot water OUT screw connection 1 c1 Water IN from outdoor unit screw connection 1 c2 Wa...

Page 40: ...OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Eng...

Page 41: ...Normally closed Normally open Normally open Note outputs can be taken from terminal positions X12M 17 L 18 N and X12M 17 L 11 N Max 2 outputs at once are possible this way Note outputs can be taken fr...

Page 42: ...M 3 4 2 core 2x0 75 2 core 2x0 75 X15M 7 8 X15M 8 X15M 7 2 Safety thermostat Q4L 2 1 Smartgrid contact K1A Smartgrid relais K1A Smartgrid relais K2A X12M 23 25 2 core 2x0 75 X12M 24 25 2 core 2x0 75 O...

Page 43: ......

Page 44: ...4P663479 1A 2022 07 Copyright 2021 Daikin 4P663479 1 A 00000005 Verantwortung f r Energie und Umwelt...

Reviews: