• Air Handling Unit Connection • Heat pump
7
• Air Handling Unit Connection • ERQ-AV1
5
Capacity tables
5 - 1 Combination table
ERQ-AV1
Combination table
Control box
Expansion valve kit
Outdoor unit
EKEQDCBV3
EKEQFCBV3
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
EKEXV200
EKEXV250
1 ph
ERQ100
P
P
P
P
P
P
-
-
-
ERQ125
P
P
P
P
P
P
P
-
-
ERQ140
P
P
-
P
P
P
P
-
-
3 ph
ERQ125
P
P
P
P
P
P
P
-
-
ERQ200
P
P
-
-
P
P
P
P
P
ERQ250
P
P
-
-
-
P
P
P
P
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity
Allowed heat exchanger volume (dm ) Allowed heat exchanger capacity (kW)
EKEXV
Class
Minimum
Maximum
Minimum
Maximum
63
1.66
2.08
6.3
7.8
80
2.09
2.64
7.9
9.9
100
2.65
3.3
10
12.3
125
3.31
4.12
12.4
15.4
140
4.13
4.62
15.5
17.6
200
4.63
6.6
17.7
24.6
250
6.61
8.25
24.7
30.8
Saturated suction temperature (SST) = 6°C, Superheat (SH = 5K
Air temperature =27°CDB/19°CWB
If conflicting result occurs, capacity selection has priority over volume.
3TW32009-1
)
3