background image

Installation manual

10

ERLQ036~054BAVJU

Outdoor unit for air to water heat pump

4PW55905-1

C

HARGING

 

REFRIGERANT

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some systems require
additional charging of refrigerant. See "Calculating the additional
refrigerant charge" on page 10.

In case re-charge is required, refer to "Complete recharging" on
page 10.

Precautions and general guidelines

This unit requires additional charging of refrigerant according to
the length of refrigerant piping connected at the site.

Make sure to charge the refrigerant in liquid state to the liquid
pipe. Since R410A is a mixed refrigerant, its composition
changes if charged in its gaseous state and normal system
operation would then no longer be assured.

Before charging, check whether the refrigerant cylinder has a
syphon attached or not and position the cylinder accordingly.

Calculating the additional refrigerant charge

It is not necessary to charge additionally if the piping length is under
98.43 ft (30 m).
However, if the piping length is under 16.40 ft (5 m), a complete
recharging of the unit is required. Refer to "Complete recharging" on
page 10.

If the piping length is over 98.43 ft (30 m) please determine the
additional amount of refrigerant to be charged using table 1 or table 2
in function of unit of measurements.

Table 1:  Additional charging of refrigerant <unit: lbs>

Table 2:  Additional charging of refrigerant <unit: kg>

Complete recharging

In case complete recharging is required (after a leak, etc.), refer to
table 3 or table 4 in function of unit of measurement to determine the
necessary amount of refrigerant.

Table 3:  Total charging amount <unit: lbs>

Table 4:  Total charging amount <unit: kg>

P

UMP

 

DOWN

 

OPERATION

This unit is equipped with an automatic pump down operation which
will collect all refrigerant from the field piping and indoor unit in the
outdoor unit. To protect the environment, make sure to perform the
following pump down operation when relocating or disposing of the
unit.

1.

Turn on the main power supply switch.

2.

Make sure the liquid stop valve and the gas stop valve are open
(see "Stop valve operation" on page 7).

3.

Press the pump down button (BS4) on the PCB of the outdoor
unit for at least 8 seconds.

4.

The compressor and outdoor unit fan will start operating
automatically. 

When servicing the unit requires the refrigerant
system to be opened, treatment and evacuation of
refrigerant must be done in accordance with relevant
local laws and national regulations.

Refrigerant can not be charged until field wiring has
been completed.

Refrigerant may only be charged after performing the
leak test and vacuum drying (see "Leak test and
vacuum drying" on page 9).

When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.

Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.

Refrigerant cylinders shall be opened slowly.

Always use protective gloves and protect your eyes
when charging refrigerant.

DANGER

When the power is on, please close the front panel when
leaving the unit unattended.

Filling using a cylinder 
with a siphon attached
Charge the liquid refrigerant 
with the cylinder in upright 
position.

Filling using a cylinder 
without a siphon attached
Charge the liquid refrigerant 
with the cylinder in up-side-
down position.

Piping length is the one way length of gas or liquid piping
whichever is the longest.

Refrigerant piping length

9.84~16.40 ft

16.40~98.43 ft

98.43~131.23 ft

(a)

(a) Recharge required, refer to "Complete recharging" on page 10

(b)

(b) Additional charge not required

1.10

131.23~164.04 ft

164.04~196.85 ft

196.85~246.06 ft

2.20

3.31

4.41

Refrigerant piping length

3~5 m

5~30 m

30~40 m

40~50 m

50~60 m

60~75 m

(a)

(a) Recharge required, refer to "Complete recharging" on page 10

(b)

(b) Additional charge not required

0.5

1.0

1.5

2.0

Before recharging, make sure to execute vacuum drying of
the internal piping of the unit as well. To do so, use the
internal service port of the unit. Do NOT use the service
ports located on the stop valve (see "Stop valve operation"
on page 7), since vacuum drying can not be performed
properly from these ports.
Outdoor units have 1 port on the piping. It is between the
heat exchanger and the 4-way valve.

Refrigerant piping length (ft)

9.84~32.81 ft

32.81~65.62 ft

65.62~98.43 ft

98.43~131.23 ft

5.95

7.05

8.16

9.26

131.23~164.04 ft

164.04~196.85 ft

196.85~246.06 ft

10.36

11.46

12.57

Refrigerant piping length

3~10 m

10~20 m

20~30 m

30~40 m

40~50 m

50~60 m

60~75 m

2.7

3.2

3.7

4.2

4.7

5.2

5.7

NOTE

For more details, refer to the applicable service
manual.

WARNING

The outdoor unit is equipped with a low pressure switch or
a low pressure sensor to protect the compressor by
switching it off. Never short-circuit the low pressure switch
during pump down operation!

1D_IM_4PW55905-1.book  Page 10  Wednesday, September 9, 2009  10:09 AM

Summary of Contents for ERLQ036BAVJU

Page 1: ...to water heat pump English Manuel d installation Unit ext rieure pour pompe chaleur air eau Fran ais Manual de instalaci n Unidad exterior para bomba de calor de aire agua Espa ol ERLQ036BAVJU ERLQ04...

Page 2: ...0 40 40 40 40 40 40 40 50 60 12 10 12 10 12 12 20 20 60 10 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L...

Page 3: ...ked refrigerant does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen depletion Be sure to use only the specified accessories and parts...

Page 4: ...Electric potential may rise abnormally if struck by a lightning bolt Install drain piping according to this installation manual to ensure good drainage and insulate the pipe to prevent condensation I...

Page 5: ...ed drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust i...

Page 6: ...llation site where the snow will not affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is not affected by the snow if necessary construct a lateral canopy PRECAUTI...

Page 7: ...ANT PIPE SIZE AND ALLOWABLE PIPE LENGTH A Location of the 2 fixation holes on the front side of the unit B Location of the 2 fixation holes on the rear side of the unit C Wires field supply Suction si...

Page 8: ...tress Flaring guidelines Flares should not be re used New ones should be made in order to prevent leaks Use a pipe cutter and flare tool suitable for the refrigerant used Only use the flare nuts inclu...

Page 9: ...the outside air temperature is low sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing Opening closing the stop valve Opening the stop valve 1 Re...

Page 10: ...not to let the indoor and outdoor piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown in the fi...

Page 11: ...psi 0 2 MPa 2 bar Never set the gauge pressure higher than the maximum operation pressure of the unit i e 580 psi 4 0 MPa 40 bar 2 2 Test for leaks by applying a bubble test solution to all piping co...

Page 12: ...g automatically When servicing the unit requires the refrigerant system to be opened treatment and evacuation of refrigerant must be done in accordance with relevant local laws and national regulation...

Page 13: ...tachment plate so that it does not slide 2 Secure the ground wire to the stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so...

Page 14: ...on manual to ensure that all functions and parts are working properly Tightening torque M4 X1M 0 89 1 33 lbs ft 1 2 1 8 N m M5 X1M 1 48 2 21 lbs ft 2 0 3 0 N m M5 ground 2 21 2 95 lbs ft 3 0 4 0 N m 1...

Page 15: ...ake sure you do not touch a conductive section The outdoor fan may rotate due to strong backblow wind causing the capacitor to charge This may result in an electric shock After maintenance make sure t...

Page 16: ...e switch high TC Signal transmission circuit V1R Power module V2R V3R Diode module V1T Insulated gate bipolar transistor X1M Terminal strip X1Y Connector X6A Connector option Y1E Expansion valve Y1S S...

Page 17: ...aire en cas de fuite de r frig rant Quand l unit doit tre install e dans une petite pi ce il est n cessaire de prendre des mesures ad quates pour que l ampleur de la fuite de r frig rant ne d passe pa...

Page 18: ...provoquer des chocs lectriques et un incendie Attention Relier l unit la terre La r sistance de mise la terre doit tre conforme la l gislation et r glementation locales Ne pas connecter le c ble de m...

Page 19: ...est pas destin une utilisation dans une atmosph re potentiellement explosive Endroits octroyant un espace suffisant pour l entretien Endroits d o les tuyauteries et les c blages des unit s int rieure...

Page 20: ...unit ext rieure Dans les r gions expos es de fortes chutes de neige il est important de choisir un lieu d installation o la neige n affectera pas l unit Si des chutes de neige transversales sont possi...

Page 21: ...ose du tuyau d vacuation de l unit ext rieure sup rieure Etanch iser la partie A afin d emp cher l air de sortie de d river C Dans le cas d une installation sur plusieurs rang es pour utilisation sur...

Page 22: ...st requise lors du placement de tubes en cuivre dans les murs La tuyauterie doit tre mont e de sorte que l vasement ne soit pas soumis une contrainte m canique Directives d vasement Les vasements ne d...

Page 23: ...d arr t Mesures prendre pour manipuler la vanne d arr t Veiller maintenir les vannes d arr t ouvertes pendant le fonctionnement La figure ci dessous illustre le nom de chaque pi ce requise pour manip...

Page 24: ...tuyauteries non fournies peuvent tre install es dans quatre directions Figure Tuyauteries non fournies dans quatre directions La d coupe des deux fentes permet l installation montr e dans figure Tuyau...

Page 25: ...eure Espace pour installation du pi ge Voir figure 4 Un pi ge n est pas n cessaire quand l unit ext rieure est install e plus haut que l unit int rieure TEST D TANCH IT ET S CHAGE VIDE Lorsque toute l...

Page 26: ...r frig rant conform ment la longueur du tuyau de r frig rant raccord sur place Veiller charger le r frig rant l tat liquide dans le tuyau de liquide Le R410A tant un r frig rant mixte l tat gazeux sa...

Page 27: ...ur de tuyau correspond la longueur dans un sens du tuyau de gaz ou de liquide selon le plus long des deux Longueur de tuyauterie de r frig rant 9 84 16 40 pi 16 40 98 43 pi 98 43 131 23 pi a a Recharg...

Page 28: ...ompensation de phase Fixer le c blage dans l ordre montr ci dessous 1 Fixer le fil de terre la plaque o se fixe la vanne d arr t pour qu il ne glisse pas 2 Fixer le fil de terre la plaque laquelle s a...

Page 29: ...correctement Couple de serrage M4 X1M 0 89 1 33 lb pi 1 2 1 8 N m M5 X1M 1 48 2 21 lb pi 2 0 3 0 N m M5 terre 2 21 2 95 lb pi 3 0 4 0 N m 1 Disjoncteur de fuite la terre 2 Fusible ou disjoncteur 3 Di...

Page 30: ...r de partie conductrice Le ventilateur ext rieur peut tourner l envers en raison d un vent puissant ce qui peut provoquer la charge de la capacitance Cela peut entra ner un choc lectrique Apr s l entr...

Page 31: ...de transmission du signal V1R Module d alimentation V2R V3R Module de diode V1T Transistor bipolaire de grille isol e X1M Barrette de raccordement X1Y Connecteur X6A Connecteur option Y1E Soupape de d...

Page 32: ...e agua descargas el ctrica o fuego Consulte a su distribuidor local si se producen fugas de refrigerante Si se pretende instalar la unidad en una habitaci n peque a es necesario tomar las medidas nece...

Page 33: ...conexi n a tierra es incompleta pueden producirse descargas el ctricas Tubo del gas Puede producirse una ignici n o explosi n si se producen fugas de gas Tubo de agua Los tubos de vinilo no son eficac...

Page 34: ...de la tuber a y el cableado de las unidades interior y exterior est n dentro de las medidas permitidas Lugares en los que la p rdida de agua de la unidad no puede causar da os en la instalaci n por ej...

Page 35: ...to de la unidad Si cabe la posibilidad de que se produzcan nevadas laterales aseg rese de que el serpent n del intercambiador de calor no se v afectado por la nieve si fuera necesario construya un rec...

Page 36: ...de la unidad exterior Selle la parte A de tal forma que el aire de la salida no derive C En el caso de instalar en varias hileras cuando se utiliza en el techo etc 1 En el caso de instalar una unidad...

Page 37: ...forma que la parte abocardada no quede expuesta a estr s mec nico Recomendaciones de abocardado No deben reutilizarse los abocardados Deber n efectuarse unos nuevos para evitar fugas Utilice un corta...

Page 38: ...de la v lvula de cierre Aseg rese de mantener abiertas ambas v lvulas de cierre durante el funcionamiento La figura de abajo muestra la denominaci n de cada pieza necesaria para el manejo de la v lvul...

Page 39: ...anuras hace posible la instalaci n tal y como aparece en la figura Los tubos de obra en cuatro direcciones Utilice una sierra para metal para cortar las ranuras Para instalar el tubo de conexi n a la...

Page 40: ...o de instalaci n del separador Ver figura 4 No es necesario el separador cuando la unidad exterior est instalada en una posici n m s elevada que la unidad interior PRUEBA DE FUGAS Y DESHUMIDIFICACI N...

Page 41: ...frigerante instalada Aseg rese de cargar el refrigerante en estado l quido a la tuber a de l quido Puesto que el R410A es una mezcla de refrigerantes su composici n var a si se carga en estado gaseoso...

Page 42: ...ncionando durante unos 30 segundos Esto no se considera un fallo de funcionamiento La unidad no se pondr en marcha ni siquiera cuando se pulsa el bot n de encendido ON del controlador remoto Para pone...

Page 43: ...al Cuando los cables se dirigen desde la unidad se puede insertar un manguito de protecci n para los conductos inserciones de generaci n de patrones en el orificio de instalaci n Ver figura 3 Cuando u...

Page 44: ...stalaci n de la unidad interior para garantizar el correcto funciona miento de todas las funciones y componentes Par de fijaci n M4 X1M 0 89 1 33 lbs pies 1 2 1 8 N m M5 X1M 1 48 2 21 lbs pies 2 0 3 0...

Page 45: ...or la acci n de un fuerte viento de retorno y de este modo puede hacer que se cargue el condensador Puede provocar descargas el ctricas Despu s del mantenimiento aseg rese de que el conector del venti...

Page 46: ...V2R V3R M dulo del diodo V1T Transistor bipolar de puerta aislada IGBT X1M Regleta de conexiones X1Y Conector X6A Conector opcional Y1E V lvula de expansi n Y1S V lvula de solenoide v lvula de 4 v as...

Page 47: ...2 5 6 3 4 R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H L NOTES 1 2 3 16 16a VJU type 2 60 Hz 230 V L1 L2 L1 L2 2 3 4 5 6...

Page 48: ...4PW55905 1 DAIKIN AIR CONDITIONING AMERICAS 1645 Wallace Drive Suite 110 Carrollton TX 75006 Copyright Daikin...

Reviews: