Configuration
Installer reference guide
219
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
#
Code
Description
[9.9.4]
[5-05]
Limit 1
: 0 A~50 A
[9.9.5]
[5-06]
Limit 2
: 0 A~50 A
[9.9.6]
[5-07]
Limit 3
: 0 A~50 A
[9.9.7]
[5-08]
Limit 4
: 0 A~50 A
Limit when [9.9.1]=
Continuous
and [9.9.2]=
kW
:
#
Code
Description
[9.9.8]
[5-09]
Limit
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Limits when [9.9.1]=
Inputs
and [9.9.2]=
kW
:
#
Code
Description
[9.9.9]
[5-09]
Limit 1
: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 2
: 0 kW~20 kW
[9.9.B]
[5-0B]
Limit 3
: 0 kW~20 kW
[9.9.C]
[5-0C]
Limit 4
: 0 kW~20 kW
Priority heater
#
Code
Description
[9.9.D]
[4-01]
Power consumption control DISABLED
[4‑08]=0
▪
0
None
: Backup heater and booster heater
can operate simultaneously.
▪
1
Booster heater
: The booster heater is
prioritised.
▪
2
Backup heater
: The backup heater is
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
▪
0
None
: Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
▪
1
Booster heater
: Depending on the
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
▪
2
Backup heater
: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
Note:
In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.