t
roubleshooting
MicroTech III Unit Controller LED Faults
Table 14: Low Voltage Brownout or Emergency Shutdown
Description*
Type
Yellow
Green
Red
Low Voltage Brownout
Fault
OFF
Flash
OFF
Emergency Shutdown
Mode
OFF
Flash
OFF
* Same LED display for both conditions.
• Verify the E terminal is not connected to common. Remove wire, if connected, and LED should change to solid green only.
• Confirm the low voltage supply is between 19-32VAC at the H1 terminal of the main board. If the low voltage supply is out of range, verify the unit
supply voltage matches the nameplate voltage and the correct transformer primary wire has been selected.
Table 15: Compressor High Pressure
Description*
Type
Yellow
Green
Red
Compressor High Pressure
Fault
OFF
OFF
Flash
• Verify high pressure switch is connected to terminal H3 on the main board.
• Check for continuity of the high pressure switch.
If the high pressure fault resets when power is cycled:
• Check water flow (cooling operation)
• Check airflow (heating operation)
• Entering water and air temperatures should be within the operating limits.
Table 16: Compressor Low Pressure
Description*
Type
Yellow
Green
Red
Compressor Low Pressure
Fault
OFF
OFF
ON
• Loose wire connection on low pressure circuit
• Failed low pressure switch
• Unit is low on charge
Table 17: Compressor Low Suction Temp
Description*
Type
Yellow
Green
Red
Compressor Low Suction Temp
Fault
Flash
Flash
ON
• Check water flow (heating operation)
• Check airflow (cooling operation)
• Entering water and air temperatures should be within the operating limits.
Table 18: Condensate Overflow
Description*
Type
Yellow
Green
Red
Condensate Overflow
Fault
ON
OFF
OFF
• Poor condensate drain
• Check the resistance to ground on condensate wire. This should be open if there is no water in the pan.
Table 19: Serial EEPROM Corrupted
Description*
Type
Yellow
Green
Red
Serial EEPROM Corrupted
Fault
ON
ON
ON
• Cycle power to see if problem is corrected.
• Replace main board, only if problem persists after power cycle.
Table 20: Service Test Mode Enabled
Description*
Type
Yellow
Green
Red
Service Test Mode Enabled
Mode
Flash
Flash
Flash
• Jumper JP1 is shorted for service test mode operation. Note: Used only for testing purposes, control timing may damage actual hardware.
Table 21: Unoccupied Mode
Description*
Type
Yellow
Green
Red
Unoccupied Mode
Mode
ON
ON
OFF
• Terminal U on main control board is connected to common from external source, or the network is overriding occupancy mode.
IM 930-6
•
Enfinity Vertical Water Source Heat Pumps
34