Enfinity Vertical Water Source Heat Pumps
14
www .DaikinApplied .com
Table 10: MicroTech III Controller Status LED's
Description
Type*
Yellow
Green
Red
Emergency Shutdown
Mode
OFF
Flash
OFF
Low Voltage Brownout
Fault
OFF
Flash
OFF
High Pressure (HP1)
Fault
OFF
OFF
Flash
Low Pressure (LP1)
Fault
OFF
OFF
ON
Low Suction Temp (LT1) Sensor Fail
Fault
Flash
Flash
ON
Low Suction Temp (LT1)
Fault
Flash
OFF
OFF
Room Temp Sensor Fail (with Room Sensor Control Only)
Fault
Flash
Flash
ON
Condensate Overflow (Cooling & Dehumidification Modes Only)
Fault
ON
OFF
OFF
Low Entering Water Temp (Heating Compressor Inhibit; No Display with Boilerless EH)
Fault
Flash
OFF
Flash
Serial EEPROM Corrupted
Fault
ON
ON
ON
Service Test Mode Enabled
Mode
Flash
Flash
Flash
Unoccupied Mode
Mode
ON
ON
OFF
Occupied, Bypass, Standby, or Tenant Override Modes
Mode
OFF
ON
OFF
Note:* Mode / Faults are listed in order of priority.