t
roubleshooting
MicroTech III Unit Controller LED Faults (Continued)
Table 18: Serial EEPROM Corrupted
Description
Type
Yellow
Green
Red
Serial EEPROM Corrupted
Fault
ON
ON
ON
• Cycle power to see if problem is corrected
• Replace main board, only if problem persists after power cycle
Table 19: Service Test Mode Enabled
Description
Type
Yellow
Green
Red
Service Test Mode Enabled
Mode
Flash
Flash
Flash
• Jumper JP1 is shorted for service test mode operation. Note: Used only for testing purposes, control timing may damage actual hardware
Table 20: Unoccupied Mode
Description
Type
Yellow
Green
Red
Unoccupied Mode
Mode
ON
ON
OFF
• Terminal U on main control board is connected to common from external source, or the network is overriding occupancy mode
Table 21: Occupied, Bypass Mode, Standby or Tenant Override Modes
Description
Type
Yellow
Green
Red
Occupied, Bypass Mode, Standby or
Tenant Override Modes
Mode
OFF
ON
OFF
• Unit is operating normal. It may currently have a control signal or ready to operate when a control signal is active
I/O Expansion Module LED Faults (For units with optional boilerless
electric heat)
Table 22: Invalid Jumper Configuration
Description
Type
Yellow
Green
Red
Invalid Jumper Configuration
Fault
Flash
Flash
OFF
• Verify jumper settings
Table 23: Baseboard Communication Fail
Description
Type
Yellow
Green
Red
Baseboard Communication Fail
Fault
OFF
Flash
Flash
• Verify connection of cable between H5 on main board and H1 on I/O expansion board
Table 24: Entering Water Temp Sensor Fail (Boilerless Electric Heat or Waterside Economizer Only)
Description
Type
Yellow
Green
Red
Entering Water Temp Sensor Fail
(Boilerless Electric Heat or Waterside
Economizer Only)
Fault
Flash
Flash
ON
• Verify connections at terminals H4 on the I/O expansion board
• Verify resistance of EWT thermistor is 10K @ 77
°
F
Table 25: Low Entering Water Temperature (No Display On Boilerless Electric Heat)
Description
Type
Yellow
Green
Red
Low Entering Water Temperature (No
Display On Boilerless Electric Heat)
Fault
OFF
ON
Flash
• Verify entering water temperature is greater than set point
IM 1049-9
38 www.DaikinApplied.com