Heating • Daikin Altherma flex type

17

Outdoor Unit • Daikin Altherma flex type• EMRQ-A

9

Wiring diagrams

9 - 1 Wiring Diagrams - Single Phase

1TW59926-2

EMRQ8-12A

A1P

A8P

Printed circuit board

A1P: Main

A5P: Inverter

A2P: Sub 1

A6P, A7P: Fan

A3P: Sub 2

A8P: Current sensor

A4P: Noise filter

BS1

BS5

Push button switch (Mode, set, return, test, reset)

C1, C63, C66

Capacitor

E1HC, E2HC

Crankcase heater (A1P, A3P)

F1U, F2U

Fuse (T, 3.15A, 250V) (A1P, A3P)

F1U

Fuse (T, 3.15A, 250V) (A2P)

F1U

Fuse (8A, DC650V) (A6P, A7P)

F5U

Field fuse

F400U

Fuse (T, 6.3,250V)

H1P

H8P

Pilot lamp (service monitor-orange)

[H2P] Prepare test----Flickering

Malfunction detection----Light up

HAP

Pilot lamp (Service monitor green) (A1P A2P A3P)

K1

K4

K1: Magnetic relay

K3: Magnetic relay

K2: Magnetic contactor (M1C)

K4: Magnetic contactor (M1C)

K1R

K8R, K11R

Magnetic relay

K1R: Y4S (A2P)

K5R: For option (A2P)

K1R: K2M (A3P)

K5R Y9S (A3P)

K2R: Y5S

K6R: Y7S

K3R: Y1S (A1P)

K7R: E1HC (A1P)

K3R: Y6S (A2P)

K8R: E2HC (A3P)

K4R: Y8S

K11R: Y3S (A1P)

K5R: Y2S (A1P)

K11R: Y10S (A3P)

L1R

Reactor

M1C, M2C

Motor (Compressor)

M1F, M2F

Motor (Fan)

PS

Switching power supply (A1P, A3P, A5P)

Q1DI

Earth leakage breaker

Q1RP

Reverse phase detection circuit (A1P, A3P)

R10

Resistor (current sensor) (A6P, A7P)

R50, R59

Resistor

R90

Resistor (current sensor)

R95

Resistor (current sensor) (A6P, A7P)

R95

Resistor (current limiting)

R1T

R15T

R31T, R32T

Thermistor

R1T: Air (A1P)

R8T: Suction 1

R1T: Fin (A5P)

R9T: Liquid

R2T: H/E gas 1

R10T: Suction 2

R31T: M1C Discharge

R11T: H/E gas 2

R32T: M2C Discharge

R12T: H/E deicer 2

R4T: H/E deicer 1

R13T: Subcool H/E gas 2

R5T: Subcool H/E gas 1

R14T: Liquid 2

R6T: Subcool H/E Liq

R15T: H/E Liquid 2

R7T: H/E Liquid 1

S1NPH

Pressure sensor (high)

S2NPL

Pressure sensor (Pressure sensor (low))

S1PH, S2PH

Pressure switch (high)

T1A

Current sensor

SD1

Safety devices input (A1P, 3AP)

V1R

Diode bridge (A5P)

Power module (A6P,A7P)

V2R

Power module

X1A

X9A

Connector

Male connector RED
Female connector WHT

Female connector WHT

Male connector RED

(Note 5) Indoor

To

in/d

unit

To

out/d

unit

To

multi

unit

(Note 4)

Male connector BLU

Female connector WHT

Female connector WHT

Male connector BLK

(Note 4)

POWER
SUPPLY

3/N

380-415V 50Hz

El. Compo. Box 2

El. Compo. Box 1

Front layer

Rear layer

Position of M1,2C, M1,2F

El. Compo. Box 2 El. Compo. Box 1

Outer shell

Wiring diagram

sticker

Detail of M1C, M2C

Notes:

1 This wiring diagram only applies to the outdoor unit
2

g

: Field wiring

3

D

: Terminal strip

F

: Fixed connector

R

: Protective earth (screw)

G

: Terminal

4 When using the option adaptor, refer to the installation manual
5 Refer to the installation manual for connection wiring to indoor - outdoor unit transmission F1-F2 and

how to use BS1-BS5

6 Do not operate the unit by short-circuiting any protection device S1Ph, S2PH.
7 BLK = Black

RED = Red

YLW = Yellow

WHT = White

PNK = Pink

BRN = Brown

GRY = Grey

GRN = Green

ORG = Orange

BLU = Blue

8,10,12 HP

To multi

unit

X1M

Terminal strip (Power supply)

X1M

Terminal (Control) (A1P,A3P)

X2M

Terminal strip (Relay)

Y1E

Electronic expansion valve (Main 1)

Y2E

Electronic expansion valve (Subcool 1)

Y3E

Electronic expansion valve (Main 2)

Y4E

Electronic expansion valve (Charge)

Y5E

Electronic expansion valve (Subcool 2)

Y1S

Y10S

Solenoid valve

Y1S: RMTG

Y6S: RMTT

Y2S: 4 way valve

Y7S: RMTO

Y3S: RMTL

Y8S: 4 way valve (pipe)

Y4S: hot gas

Y9S: 4 way valve (H/E 2)

Y5S: EV Bypass 1

Y10S: EV Bypass 2

Z1

Z8C

Noise filter (Ferrite core)

Z1F

Noise filter (with surge absorber)

Connector for optional parts

X7A

Refer to the installation manual for connection wiring to indoor -

outdoor unit transmission F1-F2 and how to use BS1-BS5 (A2P)

X9A

Power supply (Adapter) (A2P)

X37A

Power supply (Adapter) (A3P)

Summary of Contents for EMRQ10A

Page 1: ...Heating Technical Data Daikin Altherma flex type EEDEN12 726 EMRQ A ...

Page 2: ......

Page 3: ...pacity tables 7 Heating Capacity Tables 7 Integrated Heating Capacity Correction Factor 10 Capacity Correction Factor 11 6 Dimensional drawings 14 Dimensional Drawings 14 7 Centre of gravity 15 Centre of Gravity 15 8 Piping diagrams 16 Piping Diagrams 16 9 Wiring diagrams 17 Wiring Diagrams Single Phase 17 10 Sound data 19 Sound Power Spectrum 19 Sound Pressure Spectrum 21 11 Installation 23 Insta...

Page 4: ...i n A l t h The ultimate heating solution for residential and commercial applications based on air to water heat pump technology Customised to meet your building s needs up to 10 indoor units can be connected to 1 outdoor unit Low energy bills and low CO2 emissions Easy installation and maintenance Integrated heat recovery system ...

Page 5: ...tity 2 Type Hermetically sealed scroll compressor Starting method Soft start Crankcase heater Quantity 2 Operation range Heating Min ºCWB 15 Max ºCWB 20 Domestic hot water Ambien t Min ºCDB 15 Max ºCDB 35 Cooling Max ºCDB 43 Refrigerant Type R 410A Charge kg 10 3 10 6 10 8 11 1 Control Expansion valve electronic type Refrigerant oil Type Daphne FVC68D Piping connections Liquid Quantity 1 Type Braz...

Page 6: ... IEC 61000 3 11 European international technical standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated 75A 7 Maximum installation height difference between indoor units can be increased up to 25m with special field setting 8 380 V 9 400 V 10 415 V 2 2 Electrical Specifications EMRQ8A EMRQ10A EMRQ12A EMRQ14A EM...

Page 7: ...3 1 3 Heating Daikin Altherma flex type 5 Outdoor Unit Daikin Altherma flex type EMRQ A 3 Selection procedure 3 1 Selection Procedure ...

Page 8: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 4 Heating Daikin Altherma flex type 6 4 Combination table 4 1 Combination Table ...

Page 9: ...3 1 5 Heating Daikin Altherma flex type 7 Outdoor Unit Daikin Altherma flex type EMRQ A 5 Capacity tables 5 1 Heating Capacity Tables ...

Page 10: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 5 Heating Daikin Altherma flex type 8 5 Capacity tables 5 1 Heating Capacity Tables ...

Page 11: ...3 1 5 Heating Daikin Altherma flex type 9 Outdoor Unit Daikin Altherma flex type EMRQ A 5 Capacity tables 5 1 Heating Capacity Tables ...

Page 12: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 5 Heating Daikin Altherma flex type 10 5 Capacity tables 5 2 Integrated Heating Capacity Correction Factor ...

Page 13: ...1 heating D The correction factor for capacity when H 0m α 0 85 cooling EXAMPLE Equivalent length Equivalent length Outdoor unit Liquid pipe Size increase Branch Indoor 3TW59912 2 EMRQ10A Capacity correction 1 Rate of change in heating capacity Notes capacity correction 1 These figures illustrate the rate of change in capacity α of a standard indoor unit system at nominal load under standard condi...

Page 14: ... 1 heating D The correction factor for capacity when H 0m α 0 91 cooling EXAMPLE Equivalent length Equivalent length Outdoor unit Liquid pipe Size increase Branch Indoor 3TW59912 2 EMRQ14A Capacity correction 1 Rate of change in heating capacity Notes capacity correction 1 These figures illustrate the rate of change in capacity α of a standard indoor unit system at nominal load under standard cond...

Page 15: ...indoor and outdoor unit outdoor unit is on highest location Hm level difference m between indoor and outdoor outdoor unit is on lowest location Model Liquid standard Liquid increase Correction factor β heating Correction factor β cooling EMRQ16 12 7 J 15 9 J 0 3 1 2 Rate of change in cooling capacity Height difference between outdoor and farest indoor m Hp Hm Hm Hp Height difference between outdoo...

Page 16: ...8AAY1 J19 1 Brazing connection EMRQ10 12AAY1 J22 2 Brazing connection EMRQ14 16AAY1 Suction gas pipe J19 1 Brazing connection EMRQ8AAY1 J22 2 Brazing connection EMRQ10 12AAY1 J28 6 Brazing connection EMRQ14 16AAY1 Liquid pipe J9 5 Brazing connection EMRQ8 10AAY1 J12 7 Brazing connection EMRQ12 14 16AAY1 3 Shows the dimensions after fixing the accessary bag No Parts name Remarks 1 Liquid pipe conne...

Page 17: ... gravity 7 1 Centre of Gravity 3TW59924 1 EMRQ8 16A Center of foundation bolt hole Center of foundation bolt hole Slot Item A B EMR08 10 12AAY1 613 322 EMRQ14 16AAY1 609 313 Center of foundation bolt hole Slot Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole ...

Page 18: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 8 Heating Daikin Altherma flex type 16 8 Piping diagrams 8 1 Piping Diagrams ...

Page 19: ...PH S2PH Pressure switch high T1A Current sensor SD1 Safety devices input A1P 3AP V1R Diode bridge A5P Power module A6P A7P V2R Power module X1A X9A Connector Male connector RED Female connector WHT Female connector WHT Male connector RED Note 5 Indoor To in d unit To out d unit To multi unit Note 4 Male connector BLU Female connector WHT Female connector WHT Male connector BLK Note 4 POWER SUPPLY ...

Page 20: ...w S1PH S2PH Pressure switch high T1A Current sensor SD1 Safety devices input A1P 3AP V1R Diode bridge A5P A8P Power module A6P A9P V2R Power module A5P A8P X1A X9A Connector X1M Terminal strip Power supply X1M Terminal Control A1P A3P X2M Terminal strip Relay Y1E Electronic expansion valve Main 1 Y2E Electronic expansion valve Subcool 1 Y3E Electronic expansion valve Main 2 Y4E Electronic expansio...

Page 21: ...3 1 10 Heating Daikin Altherma flex type 19 Outdoor Unit Daikin Altherma flex type EMRQ A 10 Sound data 10 1 Sound Power Spectrum ...

Page 22: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 10 Heating Daikin Altherma flex type 20 10 Sound data 10 1 Sound Power Spectrum ...

Page 23: ...3 1 10 Heating Daikin Altherma flex type 21 Outdoor Unit Daikin Altherma flex type EMRQ A 10 Sound data 10 2 Sound Pressure Spectrum ...

Page 24: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 10 Heating Daikin Altherma flex type 22 10 Sound data 10 2 Sound Pressure Spectrum ...

Page 25: ...partment building to be installed at identical piping distance from indoor unit I U Tank heat meter at identical distance A Space heat cooling meters at identical distance B The flow measuring unit of the meter must be mounted in the return pipe When mounting the meter the direction of flow must be observed It is advised to mount the flow measuring unit of the meter between two shut off valves Bef...

Page 26: ... month Minimum storage capacity 13 months 13 months 13 months 13 months Register kWh heat cooling values heat cooling values heat values heat values Check local regulations and heat meter documentation for the possiblity of mountaing the tank heat meter in the drinking water circuit In case of heating only units heat meter is sufficient no heat cooling meter Other Refer to specifications of tank a...

Page 27: ...eat meter 12 Temperature sensors heat meter 13 Flow measuring unit of space heat and cooling meter 14 Temperature sensor space heat and cooling meter 15 Space heating and cooling applications 16 Refrigerant cooling exchanger 17 Motorised 3 way valve 1 Outdoor unit 2 Indoor unit 3 Electronic expansion valve 4 Refrigerant heat exchanger 5 Water heat exchanger 6 Pump 7 Motorised 3 way valve Optional ...

Page 28: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 11 Heating Daikin Altherma flex type 26 11 Installation 11 2 Refrigerant Pipe Selection ...

Page 29: ...3 1 11 Heating Daikin Altherma flex type 27 Outdoor Unit Daikin Altherma flex type EMRQ A 11 Installation 11 2 Refrigerant Pipe Selection ...

Page 30: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 11 Heating Daikin Altherma flex type 28 11 Installation 11 2 Refrigerant Pipe Selection ...

Page 31: ...3 1 11 Heating Daikin Altherma flex type 29 Outdoor Unit Daikin Altherma flex type EMRQ A 11 Installation 11 2 Refrigerant Pipe Selection ...

Page 32: ... Outdoor Unit Daikin Altherma flex type EMRQ A 1 12 Heating Daikin Altherma flex type 30 12 Operation range 12 1 Operation Range ...

Page 33: ...3 1 12 Heating Daikin Altherma flex type 31 Outdoor Unit Daikin Altherma flex type EMRQ A 12 Operation range 12 1 Operation Range ...

Page 34: ...lash com EEDEN12 726 06 12 Copyright Daikin The present publication supersedes EEDEN11 726 The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of its knowledge No express or implied warranty is given for the completeness accuracy re liability or fitness for ...