8 Technical specifications

Installation manual

7

EKRTETS
Room thermostat
4P677092-1 – 2021.10

Push button
LED

Contact LED

RF LED

Meaning

Green, 50%

Forced cooling
(manual mode)

Green, 10%

Forced OFF
(manual mode)

Orange,
blinking slowly

Radio
configuration
mode

Orange,
blinking quickly

RF signal lost

Orange, quick
short blink

RF reception
indicator

Red/Green,
blinking

Thermostat
sensor error

Orange

Blue/Red

Orange

Receiver reset

(a)

(a)

To reset the receiver, press and hold the push button for 30
seconds.

INFORMATION

Pressing the push button will turn OFF the receiver. When
the  receiver  is  turned  off,  the  integrated  frost  protection
(4°C) remains active.

7.4

Temperature sensor calibration

Both the internal temperature sensor of the room thermostat and the
(optional)  external  temperature  sensor  can  be  calibrated.  It  is
recommended  to  calibrate  the  sensor(s)  after  installation.  The
procedure is the same for both the internal temperature sensor and
the optional external temperature sensor.

7.4.1

To calibrate the temperature sensor

1

Using a thermometer, measure the temperature in the room at
1.5 m distance from the floor for at least 1 hour.

2

Press  and  hold 

  on  the  room  thermostat  for  5  seconds  to

enter the user menu.

3

Use  to  navigation  keys  to  select  AirC  or  AMbC  parameter,
depending  on  whether  you  want  to  calibrate  the  internal  or
(optional) external temperature sensor.

4

Press OK to modify the selected parameter. By default it is set
to "no".

5

Use 

 and 

 to enter the measured value.

6

Press OK to confirm.

Result: 

The  message  "yes"  is  displayed  and  the  value  is  stored  in

the internal memory of the room thermostat.

If needed, the stored calibration value can be erased by pressing 

.

The message "no" will be displayed, confirming the value has been
erased.

7.5

Dew prevention

For  reversible  systems,  the  room  thermostat  offers  2  ways  of
managing humidity in order to prevent condensation while cooling.

Humidity percentage threshold

You  can  set  a  threshold  value  for  the  humidity  percentage.
Whenever the room thermostat detects that the humidity percentage
exceeds  the  set  threshold,  cooling  demand  is  ceased  to  prevent
condensation.  Whenever  this  is  the  case, 

blinks  on  the  room

thermostat display. To change the threshold value (default 55%), set
the value for parameter 34 ("

rH

") to the desired value in the installer

menu.

Dew prevention function with floor temperature sensor

If the optional external temperature sensor EKRTETS is installed as
floor  temperature  sensor,  parameter  35  ("

dEv

")  can  be  set  to  "yes"

in the installer menu to enable the dew prevention function.

When  enabled,  this  function  will  continuously  compare  the
temperature  measured  by  the  floor  temperature  sensor  against  the
dew  point.  The  dew  point  is  calculated  based  on  the  room
temperature and humidity. When the floor temperature drops below
or  comes  too  close  to  the  dew  point,  cooling  demand  is  stopped
temporarily to prevent any condensation on the floor. While the dew
prevention function is active,

blinks on the room thermostat display.

8

Technical specifications

Room thermostat (EKRTRB)

Temperature read out precision

Steps of 0.1°C

Operating temperature

0°C~40°C

Setpoint temperature range

5°C~37°C, in steps of 0.5°C

Holiday mode temperature range 0.5°C~10°C

Electrical protection

Class II – IP30 (indoor use,
pollution degree 2)

Power supply

2 alkaline AAA LR03 1.5V
batteries

Battery autonomy

~2 years, depending on usage
conditions

Sensing element of internal
temperature sensor

NTC 10kΩ at 25°C

Receiver (EKRTRB)

Operating temperature

0°C~40°C

Electrical protection

Class II – IPx3 (indoor use,
pollution degree 2)

Power supply

1N~50 Hz 230 V

Radio frequency and receiving
zone

868 MHz, <10 mW, range of
approximately 100 m in open
space, 30 m in residential
environment

Output relays

Maximum load 5 A, 230 V

Maximum fuse amp

3 A

Power consumption

15 W (maximum)

Immunity against voltage surges Category III (2.5 kV)

Type of automatic action of the
thermostat

1C

External temperature sensor (EKRTETS)

Sensing element

NTC 10kΩ at 25°C

Summary of Contents for EKRTRB

Page 1: ...Installation manual Room thermostat English Installation manual Room thermostat EKRTRB EKRTETS...

Page 2: ...2M and select a power cable that is in accordance with applicable legislation WARNING A main switch or other means for disconnection having a contact separation in all poles MUST be incorporated in th...

Page 3: ...pically close the indoor unit The receiver is designed to be installed in a vertical orientation only Do NOT install the receiver in metal boxes or near vertical metal pipes and electronic circuits Mo...

Page 4: ...e the internal electronic parts Prerequisite You have considered the installation site requirements for the receiver when selecting the installation location See 5 1 Installation site requirements 43...

Page 5: ...the temperature sensor wiring to the room thermostat as described in 6 1 To install the room thermostat 43 4 On the room thermostat set the value for parameter 20 rEGU to FLR in the installer menu For...