6 Configuration
Installation manual
21
EKMBPP1
Modbus adapter
4P720139-1B – 2023.09
6.3.2
Modbus registers
The EKMBPP1 supports 2 types of registers: holding registers and input
registers.
Register type
Access
Function(s)
Holding register
Read/Write
Control and command, readback and
monitoring
Input register
Read-only
Readback and monitoring
The input registers are used to access all analogue and digital values.
The register values are 2 byte (16 bit) values. Depending on the values
accessed, a number of specific conventions apply to the data types the
registers return:
Data type
Value range
Convention
Digital
0~1
▪ 0: False
▪ 1: True
Integer
0~65535
No value scaling required.
Temperature
0~65535
▪ To allow for greater precision,
temperatures values are
returned multiplied by 100.
▪ Negative temperature values are
returned as signed integers. Any
value > 32767 is to be converted
into a negative value by
subtracting 65536 from it.
(a)
(a)
For example, a readback value of 2050 is a positive temperature
(< 32767): 2050/100 = 20.50°C. However, a readback value of 65036
is a negative temperature (> 32767): 65036−65536 = −500. Dividing
−500 by 100 results in a temperature of −5.00°C.
Accessing the registers is done using any of the following standard
Modbus functions:
Function code (hex code)
Function name
Register count
03 (03h)
Read holding register
1~10
04 (04h)
Read input register
1~10
06 (06h)
Preset single holding register
1
16 (10h)
Preset multiple holding registers
1~10