5 Installation
Installation manual
15
EKMBPP1
Modbus adapter
4P720139-1B – 2023.09
RS485 cables must use 24 AWG stranded, twisted pair,
shielded or unshielded to CAT3, CAT4 or CAT5
specification. Use a twisted pair for connections DA, DB
and an extra core for connection GND.
Maximum length: 500 m
5.4.2
To connect the power supply
Power supplied by the indoor unit
Power for EKMBPP1 can be supplied from the indoor unit PCB.
For Sky Air units, connect to X35A on the indoor unit PCB.
For VRV units, connect to either X18A or X35A on the indoor unit PCB.
See the indoor unit installer reference guide to determine the correct
terminal.
For VAM units, connect to either X11A, X18A or X35A on the VAM
PCB.
1
Connect the wiring harness (EKMBPP1 accessory) to screw terminal
X1A on the EKMBPP1.
2
Connect the other end of the wiring harness to the indoor unit PCB.
X18A /
X35A /
X11A
0V
+V
0V
NC
X1A
+V
External power supply
The EKMBPP1 can be powered by an external power supply (field
supplied). For more information, see
8].