E080B3VJU

 

Domestic hot water tank for air to water heat pump system

 

4PW56114-1

 

Installation manual

 

3

 

I

 

NSTALLATION

 

 

 

OF

 

 

 

THE

 

 EKHWS 

 

DOMESTIC

 

 

 

HOT

 

 

 

WATER

 

 

 

TANK

 

In case of very long field water piping between the domestic hot
water tank and the hot water end point (shower, bath, etc.) it can take
more time before the hot water from the domestic hot water tank
reaches the hot water end point.

If required connect a recirculation pump in between the hot water end
point and the recirculation hole in the domestic hot water tank.

 

CAUTION

 

 

The total system (indoor and outdoor unit) is designed
for combination with a domestic hot water tank. In
case another tank is being used in combination with
the unit, Daikin cannot guarantee neither good
operation nor reliability of the system. For those
reasons Daikin cannot give warranty of the system in
such case.

 

 

The equipment is not intended for use in a potentially
explosive atmosphere.

 

 

Only this tank can be used in combination with the
solar kit option (EKSOLHW*).

 

 

Domestic hot water quality must be according to "Safe
Drinking water Act (42 U.S.C. 300f)".

 

 

Do not connect to any heating system or component
previously used with a non potable water heating
appliance.

 

 

Do not introduce toxic chemicals, such as used for
boiler treatment, into the system.

 

 

Fill system only with water (EKHBH, EKHBX, EDLQ,
EBLQ) or water with propylene glycol and inhibitor
(only for EDLQ, EBLQ), having a toxicity rating or
Class of 1, as listed in Clinical Toxicology of
Commercial products, 5th edition.

 

 

If glycol is used, limit the pressure in the system to
30 psi (2.07 bar) by means of an approved pressure
relief valve. Refer to the figure in "Safety devices" on
page 4.

 

 

It is not allowed to add ethylene glycol to the water
circuit. Adding ethylene glycol might lead to
contamination of the domestic water if a leakage
would occur in the heat exchanger coil.

 

 

A drain device should be installed on the cold water
connection on the domestic hot water tank.

 

 

It is important that the storage capacity of the
domestic hot water tank meets normal daily
fluctuations in consumption of domestic hot water
without any fall of the water outlet temperature during
use.

 

NOTE

 

Immediately after installation, the domestic hot water
tank must be flushed with fresh water. This procedure
must be repeated at least once a day the first 5
consecutive days after installation.

 

CAUTION

 

In case of limited consumption of domestic hot water, e.g.
at holiday residences or at houses that are occasionally
not occupied, the domestic hot water tank installation must
be fitted with a shunt pump.

 

 

The shunt pump can be time-controlled,

 

 

the shunt pump must operate to circulate the
complete volume of the domestic hot water tank 1.5
times per hour,

 

 

and the shunt pump must operate, or be programmed
for operation, during 2 uninterrupted hours per day at
least.

1

Cold water 
connection

2

Hot water connection

3

Shunt pump 
(field supply)

4

Non-return valve 
(field supply)

1

2

3

4

2

1

1

Shower

2

Recirculation pump

 

1D_IM_4PW56114-1.book  Page 3  Friday, September 18, 2009  1:50 PM

Summary of Contents for EKHWS050B3VJU

Page 1: ...sh Manuel d installation Ballon d eau chaude domestique pour syst me de pompe chaleur air eau Fran ais Manual de instalaci n Dep sito de agua caliente sanitaria para instalaciones con bomba de calor a...

Page 2: ...5 7 in c h 4 0 0 m m 0 0 1 6 inch 0 40 mm 22 8 inch 580 mm 11 8 inch 300 mm 1 8 6 2 9 9 3 7 4 5 2 1 1x 1x 2x 4x 1x 1 2 3 5 4 3 4 FBSP 3 4 FBSP 1 2 FBSP 3 4 FBSP 3 4 FBSP 62 3 9 inch 100 mm 8 7 inch 2...

Page 3: ...on ACCESSORIES Accessories supplied with the domestic hot water tank See figure 1 EKHWS050B3VJU EKHWS080B3VJU Domestic hot water tank for air to water heat pump system Installation manual READ THESE I...

Page 4: ...d regulations Caution Ground the unit Grounding resistance should be according to local laws and regulations Do not connect the ground wire to gas or water pipes lightning conductor or telephone groun...

Page 5: ...EDLQ EBLQ having a toxicity rating or Class of 1 as listed in Clinical Toxicology of Commercial products 5th edition If glycol is used limit the pressure in the system to 30 psi 2 07 bar by means of...

Page 6: ...er connection H 3 Pressure relief valve connection 4 Pressure relief valve field supply 5 Electrical box 6 Electrical box lid 7 Recirculation hole 8 Thermistor socket 9 Flow inlet connection F from th...

Page 7: ...ssories see Accessories on page 1 are enclosed 2 Place the domestic hot water tank on a level surface 3 Remove the protection tape from the domestic hot water tank See 8 in figure 2 4 Apply thermal pa...

Page 8: ...on the motor sleeve Make sure not to rotate the sleeve during this action so as to maintain the valve position as set during step 4 7 8 Put the scale on the valve as shown below 9 Make sure to firmly...

Page 9: ...ensure strain relief 10 Set DIP switch SS2 2 on the PCB to ON 11 When routing out cables make sure that these do not obstruct mounting of the indoor unit cover CAUTION If a discharge pipe is connected...

Page 10: ...domestic hot water tank remove the booster heater from the domestic hot water tank and immerse in a bucket or similar with lime removing product for 24 hours TR1 TR2 X8M K1M K2M K5M K3M K6M F2B F3B F...

Page 11: ...or on the switch box of the unit always make sure that the circuit breaker of the unit is switched off POSSIBLE CAUSES CORRECTIVE ACTION The main water supply is off Check that all shut off valves of...

Page 12: ...rnis avec le ballon d eau chaude domestique Voir figure 1 EKHWS050B3VJU EKHWS080B3VJU Ballon d eau chaude domestique pour syst me de pompe chaleur air eau Manuel d installation LIRE ATTENTIVEMENT CES...

Page 13: ...e conforme la l gislation et la r glementation locales Ne pas connecter le c ble de mise la terre aux tuyauteries de gaz ou d eau c ble de mise la terre de tiges de paratonnerre ou de t l phone Une mi...

Page 14: ...LQ ayant un taux ou une classe de toxicit de 1 tel qu indiqu dans Toxicologie clinique des produits du commerce 5e dition Si du glycol est utilis limiter la pression dans le syst me 30 psi 2 07 bar au...

Page 15: ...e de pression 4 Soupape de d charge de pression non fournie 5 Coffret lectrique 6 Couvercle du coffret lectrique 7 Trou de recirculation 8 Douille de thermistance 9 Raccord d entr e d eau F de l unit...

Page 16: ...de domestique voir Accessoires la page 1 sont inclus 2 Placer le ballon d eau chaude domestique sur une surface plane 3 Retirer la bande de protection du ballon d eau chaude domestique Voir 8 dans la...

Page 17: ...chon du moteur Veiller ne pas faire tourner le manchon pendant cette action de mani re maintenir la position de la vanne comme r gl l tape 4 7 8 Placer la graduation sur la vanne comme indiqu ci desso...

Page 18: ...d charge est raccord au dispositif de d charge de pression il doit tre install en descente permanente et dans un environnement exempt de gel Il doit tre laiss l atmosph re ATTENTION Un commutateur pri...

Page 19: ...oupape de d charge de pression sur le ballon d eau chaude domestique 2 Surchauffage de ballon d eau chaude domestique Il est conseill d enlever l accumulation de calcaire sur le surchauffage pour tend...

Page 20: ...rique d appareil s assurer que le disjoncteur de l unit est sur arr t CAUSES POSSIBLES MESURE CORRECTIVE L alimentation en eau principale est coup e V rifier que toutes les vannes d arr t du circuit d...

Page 21: ...caci n de modelo ACCESORIOS Accesorios suministrados con el dep sito de agua caliente sanitaria Consulte la figura 1 EKHWS050B3VJU EKHWS080B3VJU Dep sito de agua caliente sanitaria para instalaciones...

Page 22: ...eccionarse en funci n de las leyes y disposiciones locales Precauci n Conecte a tierra la unidad La resistencia de tierra deber a ajustarse a las normativas locales No conecte el cable de tierra a tub...

Page 23: ...EKHBX EDLQ EBLQ o agua con glicol propileno e inhibidor s lo para EDLQ EBLQ con una toxicidad de la clase 1 tal y como aparece en Toxicolog a cl nica de productos comerciales 5 edici n Si se utiliza g...

Page 24: ...vula de alivio de presi n suministro independiente 5 Cuadro el ctrico 6 Tapa del cuadro el ctrico 7 Orificio de recirculaci n 8 Terminal del termistor 9 Conexi n de entrada de flujo F desde la unidad...

Page 25: ...e Accesorios en la p gina 1 2 Coloque el dep sito de agua caliente sanitaria sobre una superficie llana 3 Retire la cinta de protecci n del dep sito de agua caliente sanitaria consulte 8 en la figura...

Page 26: ...aci n seg n figura B y figura C 6 Empuje el motor sobre su manguito Aseg rese de no girar el manguito mientras realiza este paso para mantener la posici n de la v lvula tal y como se ha ajustado duran...

Page 27: ...al u otro medio de desconexi n que tenga una separaci n constante en todos los polos Todo el cableado en obra y los componentes deben ser instalados por un electricista autorizado y deben cumplir con...

Page 28: ...al tornillo de conexi n a tierra 7 Conecte el cable de alimentaci n de la resistencia el ctrica y de protecci n t rmica suministro independiente al terminal X4M de tierra 1 2 y al X2M 13 14 8 Conecte...

Page 29: ...contrar la causa del problema p ngase en contacto con el distribuidor local S ntomas generales S ntoma 1 No fluye el agua desde los grifos de agua caliente S ntoma 2 El agua que sale a trav s de los g...

Page 30: ...0 80 l 200 300 Volumen del intercambiador de calor interno gal 0 8 l 3 Dimensiones totales x Al pulgadas 22 8 x 45 3 22 8 x 63 0 mm 580 x 1150 580 x 1600 Resistencia el ctrica alimentaci n 208 230 V 2...

Page 31: ...NOTES NOTES...

Page 32: ...DAIKIN AIR CONDITIONING AMERICAS 1645 Wallace Drive Suite 110 Carrollton TX 75006 Copyright Daikin 4PW56114 1...

Reviews: