![Daikin EKHWP300B Installation And Operating Instructions Manual Download Page 28](http://html1.mh-extra.com/html/daikin/ekhwp300b/ekhwp300b_installation-and-operating-instructions-manual_3349201028.webp)
Installation and operating instructions
28
Daikin EKHWP/EKHWC/EKHWD
Daikin High-efficiency hot water storage tank
008.1618744 – 03/2017
9
x
Technical data
Pressurised system - P
Unit
EKHWCH300PB
EKHWCH500PB
EKHWCB500PB
Energy Labelling Regulation: (EU) 812/2013 / Ecodesign Regulation: (EU) 814/2013
Energy efficiency class
—
B
Standing loss
W
64
72
Hot water storage tank volume
litres
294
477
basic data
Empty weight
kg
53
80
86
Total filled weight
kg
357
593
599
Dimensions (L x W x H)
cm
59.5 x 61.5 x 164.6
79 x 79 x 165.8
Tilt dimension
cm
163
167
Maximum permissible storage water temperature
°C
85
Heat consumption at stand-by and at 60 °C
kWh/24 h
1.3
1.4
Drinking water heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
19.0
24.5
Maximum operating pressure
bar
6
Domestic water heat exchanger surface
m
2
3.9
5.0
1. Storage tank charging heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
9.4
10.5
Heat exchanger surface area
m
2
1.9
2.1
2. Storage tank charging heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
—
—
11.3
Heat exchanger surface area
m
2
—
—
2.3
Pressurised solar heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
4.2
12.5
Heat exchanger surface area
m
2
0.8
1.7
Solar heating backup (stainless steel 1.4404)
Water capacity heat exchanger
litres
—
3.2
Heat exchanger surface area
m
2
—
0.4
Heat technics power data
Output characteristic N
L
in accordance with
DIN 4708
1)
2.2
2.3
2.5
Continuous output Q
D
according to DIN 4708
kW
27
35
45
Maximum draw-off rate for the duration of 10 min
on recharging at 35 kW
(T
KW
= 10 °C / T
WW
= 40 °C / T
SP
=60 °C)
l/min
21
22
24
Hot water quantity without reheating with up to
15 l/min draw-off rate (T
KW
= 10 °C/T
WW
=
40 °C/T
SP
= 60 °C)
litres
200
230
230 / 405
2)
Hot water volume with post-heating at 15 l/min
draw-off rate (post-charge output 20 kW)
(T
KW
=10 °C / T
WW
=40 °C / T
SP
=60 °C)
litres
400
500
500 / 858
2)
Short-term water quantity in 10 min
litres
210
220
240
Pipe connections
Cold and hot water
inches
1" AG
Heating feed and return flow
inches
1" AG
Solar connections
inches
3/4" IG / 1" AG
Tab. 9-3 Basic data EKHWC - pressurised system
1) With post-charging at 35 kW, 80 °C flow temperature, 65 °C storage tank temperature, 45 °C hot water temperature
;
10 °C cold water temperature.
Summary of Contents for EKHWP300B