background image

Operation manual

15

EKHBRD011~Y1

Indoor unit for air to water heat pump system and options

4PW60971-1

Field settings

The con

fi

guration of the Daikin system is done through 

fi

eld settings.

In this operation manual all 

fi

eld settings related to the operation of

the unit and user demand are explained. A list of all those 

fi

eld

settings and default values is given under "Field settings table" on
page 16.
 In this same list, we provided for 2 columns to register the
date and value of altered 

fi

eld settings at variance with the default

value.

For a total list of 

fi

eld settings, refer to the installation manual.

All 

fi

eld settings are accessible and programmable through the user

interface on the indoor unit.

Each 

fi

eld setting is assigned a 3-digit number or code, for example

[5-03], which is indicated on the user interface display. The 

fi

rst digit

[5] indicates the '

fi

rst code' or 

fi

eld setting group. The second and

third digit [03] together indicate the 'second code'. 

Procedure

To change one or more 

fi

eld settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.
The 

$

 icon (3) will be displayed. The current selected 

fi

eld

setting code is indicated 

;

 (2), with the set value displayed to

the right 

-

 (1).

2

Press the 

ébi

 button to select the appropriate 

fi

eld setting

fi

rst code.

3

Press the 

ébj

 button to select the appropriate 

fi

eld setting

second code.

4

Press the 

pfi

  button and 

pfj

  button to change

the set value of the select 

fi

eld setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other 

fi

eld settings as

required.

7

When 

fi

nished, press the 

z

 button to exit FIELD SET MODE.

NOTE

Changes made to a speci

fi

fi

eld setting are only

stored when the 

pr

 button is pressed. Navigating to a

new 

fi

eld setting code or pressing the 

z

  button will

discard the change made.

NOTE

Before shipping, the set values have been set as
shown under "Field settings table" on page 16.

When exiting FIELD SET MODE, "

88

" may be

displayed on the remote controller LCD while the
unit initializes itself.

2

3

1

When running through the 

fi

eld settings you may notice

that there are some more 

fi

eld settings as there are

mentioned in the "Field settings table" on page 16. 

These

fi

eld settings are not applicable and may not be

changed!

Summary of Contents for EKHBRD014ABV1

Page 1: ...OPERATION MANUAL EKHBRD011ABV1 EKHBRD014ABV1 EKHBRD016ABV1 EKHBRD011ABY1 EKHBRD014ABY1 EKHBRD016ABY1 Indoor unit for air to water heat pump system and options...

Page 2: ...es or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to...

Page 3: ...e rp button See Automatic storage on page 7 The p icon will display Hot water will be produced at next scheduled action When water heat up starts the w icon will be blinking 1 second interval Manual s...

Page 4: ...used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficien...

Page 5: ...seconds the display will show to the actual room temperature 32 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set to permission level 2 or 3 refer to Field setti...

Page 6: ...oor temperatures will result in warmer water and vice versa The unit has a floating set point Activating this operation will result in a lower power consumption than use with a manually fixed leaving...

Page 7: ...k function is turned ON 1 or OFF 0 2 01 Start time time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop Domestic wat...

Page 8: ...storage temperature set point is reached It is a one time hot water making feature Selecting manual storage operation for domestic water heating 1 Push and hold the w button for 5 seconds to activate...

Page 9: ...er Field settings on page 15 for a detailed description how to set one or more field settings 4 00 Status defines whether the disinfection function is turned ON 1 or OFF 0 4 01 Operation interval day...

Page 10: ...multaneous demand of space heating and domestic water heating The unit can not perform domestic water heating and space heating at the same time If both modes are requested at the same time the unit w...

Page 11: ...eating stays enabled When pushing the r p button The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again The schedule timer i...

Page 12: ...tion 3 When both setback function and schedule timer are enabled A Setback function B ON OFF instruction t Time T Temperature set point Room temperature Leaving water temperature t 18 18 C 60 60 C 60...

Page 13: ...e repeated on a weekly basis In the domestic water heating and quiet mode program depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a dail...

Page 14: ...s the button for 5 seconds to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to s...

Page 15: ...step 2 by pressing the pr button 5 Press the and pr buttons simultaneously for 5 seconds After 5 seconds the display will show the next day e g 2 if 1 was selected first This indicates that the day h...

Page 16: ...Press the z button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2...

Page 17: ...10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 D...

Page 18: ...age temperature 70 45 75 1 C 04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation relate...

Page 19: ...yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with relevant local and national legislation Units must b...

Page 20: ...NOTES...

Page 21: ...NOTES...

Page 22: ...NOTES...

Page 23: ......

Page 24: ...4PW60971 1 Copyright 2010 Daikin...

Reviews: