background image

EKEX EKEXDCBAV3
Option kit for combination of Daikin condensing units
with field supplied evaporators
4PW30903-1

Installation and operation manual

2

N

AME

 

AND

 

FUNCTION

 

OF

 

PARTS

 

(See 

figure 1

  and

figure 2

)

B

EFORE

 

INSTALLATION

Cautions for selection of the evaporator (air handling unit)

See table below for applicable units.

Select the evaporator (field supply) according to the technical data
and limitations mentioned below.

Lifetime of the outdoor unit, operation range or operation reliability
may be influenced if you neglect these limitations.

Limits for outdoor unit (expansion valve kit)

Depending on the heat exchanger, a connectable EKEXV (expansion
valve kit) must be selected to these limitations.

Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K,
air temperature = 27°C DB / 19°C WB.

1

Selecting the condensing unit

Depending on necessary capacity of the combination an
outdoor unit needs to be selected (see "Engineering databook"
for capacity).

Each outdoor unit can be connected to a range of
evaporators (air handling units).

The range is determined by the allowed expansion valve kits.

2

Selecting the expansion valve

The corresponding expansion valve needs to be selected for
your evaporator. Select the expansion valve according to the
above limitations.

3

Selecting the capacity setting adaptor (see accessories)

The corresponding capacity setting adaptor needs to be
selected depending on the expansion valve.

Connect the correct selected capacity setting adaptor to
X24A (A1P). (See 

figure 4

 and 

figure 6

)

For the following items, take special care during 
construction and check after installation is finished

S

ELECTING

 

THE

 

INSTALLATION

 

SITE

This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.

Select an installation site where the following conditions are fulfilled
and that meets your customer's approval.

The option boxes (expansion valve and electrical control box)
can be installed inside and outside).

Do not install the option boxes in or on the outdoor unit.

Do not put the option boxes in direct sunlight. Direct sunlight will
increase the temperature inside the option boxes and may
reduce its lifetime and influence its operation.

Choose a flat and strong mounting surface.

Parts and components

1

Outdoor unit

2

Control box (EKEXFCB / EKEXDCB)

3

Air handling unit (field supply)

4

Controller (field supply)

5

Field piping (field supply)

6

Expansion valve kit

Wiring connections

7

Outdoor unit power supply

8

Control box wiring
(Power supply and communication between control box and 
outdoor unit)

9

Evaporator thermistors

10

Communication between controller and control box

11

Power supply and control wiring for evarporator (air handling unit) 
and controller (power supply is separate from the outdoor unit)

12

Air thermistor control for evaporator (air handling unit)

13

Remote controller (

= for service only)

Outdoor 
unit (class)

EKEXV kit

Outdoor 
unit (class)

EKEXV kit

100

EKEXV63~125

200

EKEXV100~250

125

EKEXV63~140

250

EKEXV125~250

140

EKEXV80~140

EKEXV 
class

Allowed heat exchanger 

volume (dm

3

)

Allowed heat exchanger 

capacity (kW)

Minimum

Maximum

Minimum

Maximum

63

0.96

1.22

6.4

7.8

80

1.22

1.53

8.1

9.9

100

1.53

1.91

10.1

12.3

125

1.91

2.14

12.6

15.4

140

2.14

2.67

14.4

17.6

200

3.06

3.82

20.2

24.6

250

3.82

4.78

25.2

30.8

NOTE

If conflicting result, volume selection has
priority over capacity.

The expansion valve is an electronic type, it is
controlled by the thermistors that are added in
the circuit. Each expansion valve can control a
range of evaporators (air handling units) sizes.

The selected evaporator unit must be
designed for R410A.

Extraneous substances (including mineral oils
or moisture) must be prevented from getting
mixed into the system.

SST: saturated suction temperature at exit of
evaporator.

EKEXV kit

Capacity 

setting adaptor 

label 

(indication)

EKEXV kit

Capacity 

setting adaptor 

label 

(indication)

63

J71

140

J160

80

J90

200

J224

100

J112

250

J280

125

J140

Tick 

 

when 

checked

Are the thermistors fixed firmly?

Thermistor may come loose.

Is the freeze-up setting done correctly?

The evaporator (air handling unit) may freeze up.

 Is the control box fixed firmly?

The unit may drop, vibrate or make noise.

Do electrical connections comply with specifications?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Compliance to directive 97/23/EEC (Pressure Equipment
Directive): only connect an evaporator of category I or less.

Summary of Contents for EKEXFCBAV3

Page 1: ...INSTALLATION AND OPERATION MANUAL EKEXFCBAV3 EKEXDCBAV3 Option kit for combination of Daikin condensing units with field supplied evaporators...

Page 2: ...Y1 expansion valve gas liquid N L P1 P2 C5 C6 0 10 V remocon outdoor F2 F1 F1 F2 T1 T2 ON OFF error C1 C2 operation C3 C4 0 10 3 4 6 5 R3T R2T 8 9 3 7 5 6 1 X24A 2 4 3 4 5 1 2 10 1 5 6 3 10 13 11 7 9...

Page 3: ...normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utili...

Page 4: ...t to control the room temperature This system does not require a specific external controller INSTALLATION ACCESSORIES Obligatory accessory Refer to chapter Valve kit installation on page 3 for instal...

Page 5: ...oxes and may reduce its lifetime and influence its operation Choose a flat and strong mounting surface Parts and components 1 Outdoor unit 2 Control box EKEXFCB EKEXDCB 3 Air handling unit field suppl...

Page 6: ...not braze yet 4 Remove the pipe fixing clamp C by unscrewing 2x M5 5 Remove the upper and lower pipe insulations 6 Braze the field piping 7 After brazing put the lower pipe insulation back in place a...

Page 7: ...l wiring refer to paragraph Electric wiring work on page 4 4 Install the screw nuts 5 Close the unnecessary openings with stoppers closing cups 6 Close the lid securely after installation to ensure th...

Page 8: ...lve X1M R1 R2 Thermistor liquid X1M R3 R4 Thermistor gas X1M Y1 6 Expansion valve X2M P1 P2 Communication remote controller X2M C1 C2 Output error status X2M C3 C4 Output operation compressor ON OFF X...

Page 9: ...e X1M P1 P2 Communication remote controller X1M T1 T2 Input ON OFF X1M F1 F2 Communication outdoor unit Field wiring L Live N Neutral Connector Wire clamp Protective earth screw Separate component Opt...

Page 10: ...stor cable or loosening of the thermistor may result in bad contact and incorrect temperature measurement Fixation of the thermistor 1 Fix the thermistor with insulating aluminum tape field supply in...

Page 11: ...Field settings for EKEXDCB Refer to the installation manuals of both the outdoor unit and the remote controller Field settings for EKEXFCB When changing the settings 1 Make the required settings 2 Tu...

Page 12: ...g procedures A Controller voltage output to EKEXFCB Capacity increase area Capacity decrease area Voltage output linear function with T T actual measured temperature target temperature When T 0 the ta...

Page 13: ...alified service person to clean the air filter Check if the doors or the windows are open Shut doors or windows to prevent wind from coming in Check if direct sunlight enters the room Use curtains or...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30903 1...

Reviews: