background image

Installation manual

Daikin Altherma - Low Temperature Split

English

Installation manual

Daikin Altherma - Low Temperature Split

EHVH04S18CA
EHVH08S18CA
EHVH08S26CA
EHVH16S18CA
EHVH16S26CA
EHVX04S18CA
EHVX08S18CA
EHVX08S26CA
EHVX16S18CA
EHVX16S26CA

Summary of Contents for EHVH04S18CA

Page 1: ...aikin Altherma Low Temperature Split English Installation manual Daikin Altherma Low Temperature Split EHVH04S18CA EHVH08S18CA EHVH08S26CA EHVH16S18CA EHVH16S26CA EHVX04S18CA EHVX08S18CA EHVX08S26CA EHVX16S18CA EHVX16S26CA ...

Page 2: ...yny odpovídajínásledujícímnormámnebonormativnímdokumentům uskladusaslijedećimstandardom ima ilidrugimnormativnimdokumentom ima uzuvjetdaseonikoristeuskladusnašimuputama megfelelnekazalábbiszabvány ok nakvagyegyébirányadódokumentum ok nak haazokatelőírásszerinthasználják 17 18 19 20 21 22 23 24 25 spełniająwymoginastępującychnormiinnychdokumentównormalizacyjnych podwarunkiemżeużywanesązgodnieznaszy...

Page 3: ...4 Configuration 11 4 1 Overview Configuration 11 4 2 Basic configuration 12 4 2 1 Quick wizard Language time and date 12 4 2 2 Quick wizard Standard 12 4 2 3 Quick wizard Options 12 4 2 4 Quick wizard Capacities energy metering 14 4 2 5 Space heating cooling control 14 4 2 6 Domestic hot water control 15 4 2 7 Contact helpdesk number 15 4 3 Menu structure Overview installer settings 16 5 Commissio...

Page 4: ...nterface cover 4 Reinstall the top panel 3 Installation 3 1 Opening the units 3 1 1 To open the indoor unit 1 Loosen and remove the screws at the bottom of the unit 2 Slide the front panel of the unit downwards and remove it CAUTION The front panel is heavy Be careful NOT to jam your fingers when opening or closing the unit 3 Loosen and remove the 4 screws that fix the top panel 4 Remove the top p...

Page 5: ...onnect the gas stop valve from the outdoor unit to the refrigerant gas connection of the indoor unit 3 4 Connecting the water piping 3 4 1 To connect the water piping NOTICE Do NOT use excessive force when connecting the piping Deformation of the piping can cause malfunctioning of the unit To facilitate service and maintenance 2 shut off valves are provided Mount the valves on the water inlet and ...

Page 6: ...rk 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 Manually operate the field installed pressure relief valve to ensure that free water flow through the discharge pipe 3 4 4 To insulate the water piping The piping in the complete water circuit must be insulated to prevent condensation during cooling operation and reduction of the heating ...

Page 7: ...able for indoor units with 260 liter tank To access the domestic hot water temperature sensor the switch box can be tilt The switch box should NOT be removed from the unit Routing Possible cables depending on unit type and installed options a Low voltage User interface Power consumption digital inputs field supply Outdoor ambient temperature sensor option Indoor ambient temperature sensor option E...

Page 8: ...ent Zmax Ω 6 kW 3 230 V 15 A b 6 kW 3N 400 V 8 6 A 9 kW 3N 400 V 13 A a Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase b This equipment complies with EN IEC 61000 3 11 European International Technical Standard settin...

Page 9: ...M A2P A2P 2 1 a b a User interface delivered with the unit b Optional user interface 2 Fix the cable with cable ties to the cable tie mountings Fixation of the user interface to the indoor unit 3 Insert a screwdriver into the slots underneath the user interface and carefully separate the faceplate from the wallplate NOTICE The PCB is mounted in the faceplate of the user interface Be careful NOT to...

Page 10: ... X2M 56 7 M2S X1M X2M 5 67 M2S NO NC 2 Fix the cable with cable ties to the cable tie mountings 3 5 7 To connect the electrical meters INFORMATION In case of an electrical meter with transistor output check the polarity The positive polarity MUST be connected to X5M 7 and X5M 9 the negative polarity to X5M 8 and X5M 10 1 Connect the electrical meters cable to the appropriate terminals as shown in ...

Page 11: ...e with cable ties to the cable tie mountings 3 5 12 To connect the power consumption digital inputs 1 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below X1M X2M 1 2 3 4 5 A8P X801M S6S S7S S8S S9S a a Installation of EKRP1AHTA is required 2 Fix the cable with cable ties to the cable tie mountings 3 6 Finishing the indoor unit installa...

Page 12: ...than 4 seconds Result is displayed on the home pages 3 If you do NOT press any button for more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user 4 1 4 To switch between user permission levels End user and Advanced end user 1 Go to 6 or any of its submenus Information 2 Press for more than 4 seconds Result The user permission level switches ...

Page 13: ...nvector can only send a thermo ON OFF condition No separation between heating or cooling demand 2 C H request When the used external room thermostat can send a separate heating cooling thermo ON OFF condition Code Description A 2 2 B C 08 External sensor 0 No NOT installed 1 Outdoor sensor Connected to PCB measuring the outdoor temperature 2 Room sensor Connected to PCB measuring the indoor temper...

Page 14: ...olute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature control A 3 1 1 3 1 00 1 01 1 02 1 03 Weather dependent curve heating 1 03 1 02 Ta Tt 1 00 1 01 Tt Target leaving water temperature main Ta Outdoor temperature Code Description A 3 1 1 4 1 06 1 07 1 08 1 09 Weather dependent curve cooling 1 09 1 08 Ta Tt 1 06 1 0...

Page 15: ...itters type the heat up or cool down of a space can take longer This setting can compensate for a slow or a quick heating cooling system by adjusting the unit capacity during the heat up cool down cycle 4 2 6 Domestic hot water control Code Description A 4 1 6 0D Domestic hot water Setpoint mode 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled heatu...

Page 16: ...emp Space cooling On temp A 3 3 Setpoint mode Scheduled DHW Domestic hot water DHW A 4 Schedule temperatures Storage comfort SP mode Weather dependent curve Scheduled DHW A 4 2 Setpoint readout type Conversion persons Setpoint readout A 4 3 External sensor Demand PCB Disinfection Operation day Start time Temperature target A 4 4 Duration Backup heater Heat sources A 5 Operation mode Auto emergency...

Page 17: ...2 turns The pressure relief valve purges water when opened 5 2 To perform an air purge 1 Go to A 7 3 Installer settings Commissioning Air purge 2 Set the type speed and circuit 3 Select Start air purge and press 4 Select OK and press Result The air purge starts It stops automatically when done To stop it manually press select OK and press 5 3 To perform a test run 1 Go to A 7 1 Installer settings ...

Page 18: ...or the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the CD DVD and the printed documentation and ask him her to keep it for future reference Explain the user how to properly operate the system and what he she has to do in case of problems Show the user what jobs he she has to do in relation to maintenance of the unit Explain ...

Page 19: ...lectrical meter pulse input 2 electrical meter pulse input 1 preferential kWh rate PS contact external indoor or outdoor ambient thermistor domestic hot water thermistor external sensor floor or ambient ambient sensor On OFF thermostat thermal protector booster heater 6T1 3 230 V 6 kW 9WN 3N 400 V 9 kW 6WN 3N 400 V 6 kW 6V3 1N 230 V 6 kW 3V3 1N 230 V 3 kW Backup heater configuration only for 9W Ex...

Page 20: ...for 6V3 1N 230 V 6 kW for 3V3 1N 230 V 3 kW only for 9W only for 3V only for KHWS V3 domestic hot water tank 4D077028 page 3 A4P YC A4P Y2 A4P Y2 X2M 29 S6S S7S S8S S9S S3S BSK S1S S2S B1L X2M 14 X2M 9 X2M 14 X2M 9 X2M 13 t R5T t R6T 2 KHR KHUR KCR KFR t R1T t R1T 2 X18A 1 2 X22A 1 X85A 1 2 3 4 5 6 t R1T F1U F2U 3 CN1 1 6 5 4 3 2 CN2 1 X80A 1 2 7 8 4 X4A 1 2 3 X33A 1 3 4 6 5 3 4 5 6 7 8 9 12 11 10...

Page 21: ...04 and 08 only for 16 DHW pump 3 wire type SPST NO valve only for domestic hot water option 3 wire type SPDT domestic hot water tank only for enamel tank option only for domestic hot water option 1N 50 Hz 230 V AC Normal kWh rate power supply only for domestic hot water tank option A1P Main PCB A2P User interface PCB A3P Solar pump station PCB A3P On OFF thermostat PC power circuit A3P Heat pump c...

Page 22: ... 9W Backup heater configuration only for 9W User installed options User installed options Bottom plate heater Bottom plate heater Domestic hot water tank Domestic hot water tank Domestic hot water tank with solar connection Domestic hot water tank with solar connection Remote user interface Remote user interface Ext indoor thermistor Extended indoor thermistor Ext outdoor thermistor Extended outdo...

Page 23: ...ar input 2 core signal Changeover to ext heat source output Ext heat source eg boiler Only for KRP1HB KSOLHWAV1 NO valve X2M 6 7 NC valve X2M 5 7 2 core 2WAY VALVE M2S KHBX units for cooling mode main X2M 1 2 4 add X2M 1a 2a 4 3 core for C H operation 2 core for H only operation main X2M 1 2 3 4 add X2M 1a 2a 3 4 main X2M 1 4 add X2M 1a 4 4 core Only for KRTW wired room thermostat Only for KRTR wi...

Page 24: ...f pulse 0 1 pulse kWh 1pulse kWh 10pulse kWh 100 pulse kWh 1000 pulse kWh pulse duration minimum On time 40ms minimum OFF time 100ms measurement type depending on installation single phase AC meter three phase AC meter balanced loads three phase AC meter unbalanced loads electrical meter installation guideline General it is the reponsability of the installer to cover the complete power consumption...

Page 25: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 26: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 27: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 28: ...4P313772 1 D 0000000 4P313772 1D 2012 12 Copyright 2012 Daikin ...

Reviews: