4 Configuration
Installation manual
14
EHVH/X04+08+1 EHVH/X08+16S26CA
Daikin Altherma - Low Temperature Split
4P313772-1D – 2012.12
Energy metering
#
Code
Description
[A.2.2.8]
[D-08]
Optional external kWh meter 1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D-09]
Optional external kWh meter 2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
4.2.4
Quick wizard: Capacities (energy
metering)
#
Code
Description
[A.2.3.1]
[6-02]
Booster heater capacity [kW]
[A.2.3.6]
[6-07]
Bottom plate heater capacity [W]
4.2.5
Space heating/cooling control
Leaving water temperature: Main zone
#
Code
Description
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Absolute): Absolute
▪ 1
(Weather
dep.):
Weather
‑
dependent
▪ 2 (Abs + scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD
+
scheduled):
Weather
‑
dependent + scheduled
(only for leaving water temperature
control)
[A.3.1.1.3]
[1-00]
[1-01]
[1-02]
[1-03]
Weather
‑
dependent curve (heating):
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
#
Code
Description
[A.3.1.1.4]
[1-06]
[1-07]
[1
‑
08]
[1-09]
Weather
‑
dependent curve (cooling):
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
Leaving water temperature: Additional zone
#
Code
Description
[A.3.1.2.1]
N/A
Set point mode:
▪ 0 (Absolute): Absolute
▪ 1
(Weather
dep.):
Weather
‑
dependent
▪ 2 (Abs + scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD
+
scheduled):
Weather
‑
dependent + scheduled
(only for leaving water temperature
control)
[A.3.1.2.3]
[0-00]
[0-01]
[0-02]
[0-03]
Weather
‑
dependent curve (heating):
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
[A.3.1.2.4]
[0-04]
[0-05]
[0-06]
[0-07]
Weather
‑
dependent curve (cooling):
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature