Operation
Operating modeReducing
Reduced heating mode (lower set room temperature) in ac-
cordance with the target temperature set for economy mode in
the parameter [T-Reduced] (see section 3.4.4).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating modes Heating, Cooling
Heating or cooling operation in accordance with the room tem-
perature set in the parameter [T-Room 1 Setpoint]
(see section 3.4.3).
A connected outdoor temperature sensor (weather-controlled
flow temperature regulation) or a connected room station will also
influence the set flow temperature regulation (requirements: Pa-
rameter [HC Function] = On).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating modeSummer
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Summer".
Operating mode Automatic 1 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
– [HC Program 1]
– [DHW Program 1]
Operating mode Automatic 2 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
– [HC Program 2]
– [DHW Program 2]
In addition to these operating modes there are various different
temporary heating programmes available (see tab. 3-6), which
run according to priority after they have been activated.
Tab. 3-6 Overview of temporary timer programmes
3.4.3 Temperature setting Daytime room temperature
The set room temperatures for room heating during the day are
determined in the rotary switch setting
.
●
Place the rotary switch in the
"Set Temp Day"
position.
An overview is displayed.
●
Select the temperature block to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Settings are displayed.
●
Set the temperature.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.5.
Fig. 3-8
Standard display in "Standby" operating mode
(above the frost-protection limit)
In the "Standby" operating mode, the heat pump and
any optionally connected backup heaters are isolated
from the power supply (
Energy saving mode
) when
the following conditions are met:
– The outdoor temperature sensor (RoCon OT1) is
connected and correctly parametrised in the system
configuration,
– The outdoor temperature is over 8 °C,
– There is no heating command,
– The frost protection function is not active in any of
the connected heating circuits, and
– Daikin Altherma EHS(X/H) has been switched on
for at least 5 mins.
Temporary
timer
programme
Setting /
activating in
level
Rotary
switch
setting
Note
DHW Install
DHW Install
section
3.4.6
Party
Time Program
section
3.4.7
Away
Holiday
Vacation
If a temporary timer programme (DHW Install, Party,
Away, Holiday, Vacation) is started during the selected
operating mode, the regulation will take place with pref-
erence according to the settings of this timer pro-
gramme.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the associ-
ation with each individual cycle of the timer programme.