COMMUNICATIONS TROUBLESHOOTING CHART

LED

LED 

Status

Indication

Possible Causes

Corrective Action(s)

Notes & Cautions

Off

 

None

 

None

 

None

 

None

1 Flash

  Communications

    Failure

  Communications

    Failure

  Depress Learn Button

 

Verify wiring connection

 

Depress once quickly for 

      a power-up reset

 

Depress and hold for 5 

      seconds for an out-of-box 

      reset

Flashes

  Out-of-box reset

  Control power up

  Learn button 

    depressed

 

None

 

None

Off

 

 No power

  Communications   

    error

  No power to air   

    handler

  Open fuse

  Communications 

    error

  Check fuses and circuit 

    breakers; replace/reset

  Replace blown fuse

  Check for shorts in low 

    voltage wiring in air 

    handler/system

  Reset network by 

    depressing learn button

  Check data 1/data2 

    voltages

 

 Turn power OFF prior to 

    repair

1 Steady 

Flash

 

 No network 

found

  Broken/ disconnected  

    data wire(s)

 Air handler is 

   installed as a non-

   communicating/ 

   traditional system

  Check communications 

    wiring (data 1/data 2 

    wires)

  Check wire connections at 

    terminal block

  Verify air handler 

    installation type (non-

   communicating/

   traditional or 

   communicating)

  Check data 1/data 2 

    voltages

 

 Turn power OFF prior to 

    repair

  Verify wires at terminal 

    blocks are securely twisted 

    together prior to inserting 

    into terminal block

  Verify data 1 and data 

    voltages as described 

    above

Rapid 

Flashing

 

 Normal network 

    traffic

 

 Control is "talking" 

    on network as 

    expected

 

 None

 

 None

On Solid

 

 Data 1/Data 2 

    miss-wire

 

 Data 1/data 2 wires 

    reversed at air 

    handler, thermostat, 
    or ComfortNet

TM 

   compatible outdoor 

   AC/HP

  Short between data 

    1/data 2 wires 

  Short between data 1 

    or data 2 wires and R 

    (24VAC) or C (24VAC 

    common)

 

 Check communications 

    wiring (data 1/data 2 

    wires)

  Check wire connections at 

    terminal block

  Check data 1/data 2 

    voltages

 

 Turn power OFF prior to 

    repair

  Verify wires at terminal 

    blocks are securely twisted 

    together prior to inserting 

    into terminal block

  Verify data 1 and data 

    voltages as described 

    above

Red 

Communications 

LED

Green

Receive

LED

Summary of Contents for EEV Series

Page 1: ...ting 15 16 1 Electrostatic Discharge ESD Precautions 15 16 2 Diagnostic Chart 15 16 3 Fault Recall 15 17 Fully Communicating Daikin System 16 17 1 Overview 16 17 2 Airflow Consideration 16 17 3 Thermo...

Page 2: ...venir si un appareil produisant du monoxyde de carbone continue de fonctionner au sein de la zone confin e Failure to properly reconnect sensor wires may result in Error codes and the unit not operati...

Page 3: ...consult the white busi ness pages the yellow page section of the local telephone book or contact HOMEOWNER SUPPORT DAIKIN NORTH AMERICA LLC 190001 KERMIER ROAD WALLER TEXAS 77484 855 770 5678 5 PRE IN...

Page 4: ...is for the secondary drain line if used 6 2 Horizontal Left Installation No field modifications are permissible for this application Drain port labeled B in Figure 1 is the primary drain for this appl...

Page 5: ...to the corner post using screw mount wire ties 3 Secure the insulated connectors to the corner using two screws and the mounting wire ties provided 2 Connect the junction connectors and slide the ins...

Page 6: ...t in panel damage UPFLOW Figure 3 DOWNFLOW Figure 4 HORIZONTAL LEFT Figure 5 HORIZONTAL RIGHT Figure 6 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel B...

Page 7: ...ep 1 as shown in Figure 10 8 Two drain ports located at the bottom drain pan horizon tally oriented are to be used for upflow and downflow applications and the two on the side drain pan vertically ori...

Page 8: ...s 8 CONDENSATE DRAIN LINES The coil drain pan has a primary and a secondary drain with 3 4 NPT female connections The connectors required are 3 4 NPT male either PVC or metal pipe and should be hand t...

Page 9: ...24x20x1 actual dimension must be less than 23 x20 filter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number Washable versions are available...

Page 10: ...22 27 40 1200 7 11 14 19 22 33 45 56 1400 6 10 12 16 19 29 38 48 1600 5 8 10 14 17 25 33 42 1800 5 7 9 12 15 22 30 37 2000 4 7 8 11 13 20 27 33 208 1 60 SUPPLY VOLTAGE TEMP RISE F Table 6 CFM HEAT KI...

Page 11: ...ckouts on the cabinet sides are used for electrical 208 240 197 253 Nominal Input Minimum Voltage Maximum Voltage ELECTRICAL VOLTAGE Table 7 HIGH VOLTAGE Disconnect ALL power before servicing or insta...

Page 12: ...ayed LEDs on the PCB as there may be a tolerance difference between displayed and actual measured Maximum Measured CFM Allowed Up Flow Down Flow HZ Flow DV24FECB14 910 870 870 DV36FECC14 1450 1390 139...

Page 13: ...seconds normal operation resumes and the error message is removed The switch is closed as part of the default factory setting The error will be maintained in the equipment s fault history See Figures...

Page 14: ...motor is oriented with the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure 15 4 Accessory...

Page 15: ...tatic electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge y...

Page 16: ...ating mode and airflow demand source For example assume the system is a heat pump matched with an air handler With a call for low stage cooling the heat pump will calculate the system s low stage cool...

Page 17: ...e installing this unit Power line terminal C from Indoor unit must connect to terminal C on thermostat and power line terminal R from indoor unit must connect to terminal R on thermostat Verify wires...

Page 18: ...system Check communications wiring data 1 data 2 wires Check wire connections at terminal block Verify air handler installation type non communicating traditional or communicating Check data 1 data 2...

Page 19: ...rminals TB4 and TB5 if not used After recovering the system EF will still be displayed on the indoor PCB about 30 seconds AUXILIARY CONTACTS OPEN will still be displayed on the thermostat within 45 se...

Page 20: ...ck the connections and the rotation of the motor Verify the input voltage at the motor Verify ductwork is appropriately sized for system Resize replace ductwork if needed Replace motor 70 E_70 EEV dis...

Page 21: ...TO MOTOR LOW INDOOR AIRFLOW Minor Error Code without EH mode LOW INDOOR AIRFLOW Major Error Code EH mode only EEV DISCONNECTION DETECTED LIQUID SIDE THERMISTOR ABNORMALITY GAS SIDE THERMISTOR ABNORMA...

Page 22: ...y DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode will allow the user to see t...

Page 23: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Page 24: ...REEN RX LED INDICATES NETWORK TRAFFIC USE LEARN BUTTON TO RESET NETWORK 7 DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT 8 THE POSITION OF SELECTOR SWITCHES DS1 DS6 INDICATE FACTORY SETTING 9...

Page 25: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your furn...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...ranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights For Product Registration please register by following this lin...

Reviews: