background image

11

12  ELECTRICAL AND CONTROL WIRING

IMPORTANT: 

All routing of electrical wiring must be made 

through provided electrical knockouts. When removing the 

electircal knockouts, take care not to damage the PCB.  Do 

not cut, puncture or alter the cabinet for electrical wiring.

12.1 Building Electrical Service Inspection

This unit is designed for single-phase electrical supply 

only.  DO NOT OPERATE AIR HANDLER ON A THREE-

PHASE POWER SUPPLY.  Measure the power supply to 

the unit.  The supply voltage 

must

 be measured and be 

in agreement with the unit nameplate power requirements 

and within the range shown.

 12.2 Wire Sizing

Wire size is important to the operation of your equipment.  

Use the following check list when selecting the appropri-

ate wire size for your unit.

• 

Wire  used  must  be  sized  to  carry  the  Minimum 

Circuit Ampacity (MCA) listed on the equipment’s 

Rating Plate.

• Refer to the NEC (USA) or CSA (Canada) for wire siz-

ing.  The unit MCA for the air handler and the optional 

electric heat kit can be found on the unit Series and 

Rating Plate.

Wire  must  be  sized  to  allow  no  more  than  a  2% 

voltage drop from the building breaker/fuse panel 

to the unit.

•Wires with different insulation temperature rating have 

varying ampacities - be sure to check the temperature 

rating used.

Refer to the latest edition of the National Electric Code or 

in Canada the Canadian Electric Code when determining 

the correct wire size.  

12.3 Maximum Overcurrent Protection (MOP)

Every installation must include an NEC (USA) or CEC 

(Canada) approved overcurrent protection device.  Also, 

check with local or state codes for any special regional 

requirements. Protection can be in the form of fusing or 

HACR style circuit breakers.  The Series and Rating Plate 

provides the maximum overcurrent device permissible.

NOTE: 

Fuses or circuit breakers are to be sized larger 

than the equipment MCA but not to exceed the MOP. 

12.4 Electrical Connections – Supply Voltage 

IMPORTANT NOTE: USE COPPER CONDUCTORS 

ONLY.

Knockouts are provided on the air handler top panel 

and sides of the cabinet to allow for the entry of the 

supply voltage conductors, as shown in Figure 14. If the 

knockouts on the cabinet sides are used for electrical 

208-240

197

253

Nominal          

Input

Minimum 

Voltage

Maximum 

Voltage

ELECTRICAL VOLTAGE

Table 7

HIGH VOLTAGE!

 

Disconnect ALL power before servicing or 

installing this unit. Multiple power sources may 

be present. Failure to do so may cause property 

damage, personal injury or death.

 

HIGH VOLTAGE!
To avoid  property  damage,  personal  injury or  death  due 

to electrical shock, this unit MUST have an uninterrupted, 

unbroken electrical ground. The electrical ground circuit may 

consist of an appropriately sized electrical wire connecting 

the ground lug in the unit control box to the building electrical 

service panel.
Other methods of grounding are permitted if performed in 

accordance with the National Electric Code (NEC)/American 

National Standards Institute (ANSI)/National Fire Protection 

Association (NFPA) 70 and local/state codes. In Canada, 

electrical grounding is to be in accordance with the Canadian 

Electric Code  (CSA) C22.1.

FIRE HAZARD! To avoid the risk of property damage, 

personal injury or fire, use only copper conductors.

CAUTION

Table 8

conduit, an adapter ring must be used in order to meet 

UL1995 safety requirements.  An NEC or CEC approved 

strain relief is to be used at this entry point.  Some codes/

municipalities require the supply wire to be enclosed in 

conduit.  Consult your local codes.

12.4.1 Air Handler Only (Non-Heat Kit Models)

 

The power supply connects to the stripped black and 

red wires contained in the air handler electrical com-

partment.  Attach the supply wires to the  air handler 

conductors as shown in the unit wiring diagram using 

appropriately sized solderless connectors or other NEC 

or CEC approved means. A ground lug is also provided 

in the electrical compartment. The ground wire from the 

power supply must be connected to this ground lug.

12.4.2 Air Handler - Non-Circuit Breaker Heat Kits

 

A terminal block is provided with the HKS kit to attach 

the power supply and air handler connections. Follow 

the HKS Installation Manual and wiring diagram for 

complete wiring details. 

12.4.3 Air Handler With Circuit Breaker Heat Kit

 

The air handler has a soft plastic cover on the upper 

access panel and can be removed to allow the heater 

kit circuit breaker to be installed.  The circuit breakers 

have lugs for power supply connection. See the HKS 

Installation Instructions for further details. 

Summary of Contents for EEV Series

Page 1: ...ting 15 16 1 Electrostatic Discharge ESD Precautions 15 16 2 Diagnostic Chart 15 16 3 Fault Recall 15 17 Fully Communicating Daikin System 16 17 1 Overview 16 17 2 Airflow Consideration 16 17 3 Thermo...

Page 2: ...venir si un appareil produisant du monoxyde de carbone continue de fonctionner au sein de la zone confin e Failure to properly reconnect sensor wires may result in Error codes and the unit not operati...

Page 3: ...consult the white busi ness pages the yellow page section of the local telephone book or contact HOMEOWNER SUPPORT DAIKIN NORTH AMERICA LLC 190001 KERMIER ROAD WALLER TEXAS 77484 855 770 5678 5 PRE IN...

Page 4: ...is for the secondary drain line if used 6 2 Horizontal Left Installation No field modifications are permissible for this application Drain port labeled B in Figure 1 is the primary drain for this appl...

Page 5: ...to the corner post using screw mount wire ties 3 Secure the insulated connectors to the corner using two screws and the mounting wire ties provided 2 Connect the junction connectors and slide the ins...

Page 6: ...t in panel damage UPFLOW Figure 3 DOWNFLOW Figure 4 HORIZONTAL LEFT Figure 5 HORIZONTAL RIGHT Figure 6 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel B...

Page 7: ...ep 1 as shown in Figure 10 8 Two drain ports located at the bottom drain pan horizon tally oriented are to be used for upflow and downflow applications and the two on the side drain pan vertically ori...

Page 8: ...s 8 CONDENSATE DRAIN LINES The coil drain pan has a primary and a secondary drain with 3 4 NPT female connections The connectors required are 3 4 NPT male either PVC or metal pipe and should be hand t...

Page 9: ...24x20x1 actual dimension must be less than 23 x20 filter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number Washable versions are available...

Page 10: ...22 27 40 1200 7 11 14 19 22 33 45 56 1400 6 10 12 16 19 29 38 48 1600 5 8 10 14 17 25 33 42 1800 5 7 9 12 15 22 30 37 2000 4 7 8 11 13 20 27 33 208 1 60 SUPPLY VOLTAGE TEMP RISE F Table 6 CFM HEAT KI...

Page 11: ...ckouts on the cabinet sides are used for electrical 208 240 197 253 Nominal Input Minimum Voltage Maximum Voltage ELECTRICAL VOLTAGE Table 7 HIGH VOLTAGE Disconnect ALL power before servicing or insta...

Page 12: ...ayed LEDs on the PCB as there may be a tolerance difference between displayed and actual measured Maximum Measured CFM Allowed Up Flow Down Flow HZ Flow DV24FECB14 910 870 870 DV36FECC14 1450 1390 139...

Page 13: ...seconds normal operation resumes and the error message is removed The switch is closed as part of the default factory setting The error will be maintained in the equipment s fault history See Figures...

Page 14: ...motor is oriented with the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure 15 4 Accessory...

Page 15: ...tatic electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge y...

Page 16: ...ating mode and airflow demand source For example assume the system is a heat pump matched with an air handler With a call for low stage cooling the heat pump will calculate the system s low stage cool...

Page 17: ...e installing this unit Power line terminal C from Indoor unit must connect to terminal C on thermostat and power line terminal R from indoor unit must connect to terminal R on thermostat Verify wires...

Page 18: ...system Check communications wiring data 1 data 2 wires Check wire connections at terminal block Verify air handler installation type non communicating traditional or communicating Check data 1 data 2...

Page 19: ...rminals TB4 and TB5 if not used After recovering the system EF will still be displayed on the indoor PCB about 30 seconds AUXILIARY CONTACTS OPEN will still be displayed on the thermostat within 45 se...

Page 20: ...ck the connections and the rotation of the motor Verify the input voltage at the motor Verify ductwork is appropriately sized for system Resize replace ductwork if needed Replace motor 70 E_70 EEV dis...

Page 21: ...TO MOTOR LOW INDOOR AIRFLOW Minor Error Code without EH mode LOW INDOOR AIRFLOW Major Error Code EH mode only EEV DISCONNECTION DETECTED LIQUID SIDE THERMISTOR ABNORMALITY GAS SIDE THERMISTOR ABNORMA...

Page 22: ...y DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode will allow the user to see t...

Page 23: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Page 24: ...REEN RX LED INDICATES NETWORK TRAFFIC USE LEARN BUTTON TO RESET NETWORK 7 DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT 8 THE POSITION OF SELECTOR SWITCHES DS1 DS6 INDICATE FACTORY SETTING 9...

Page 25: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your furn...

Page 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 28: ...ranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights For Product Registration please register by following this lin...

Reviews: