6
|
Application guidelines
Installer reference guide
53
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
6.5 Setting up the energy metering
▪
Via the user interface, you can read out the following energy data:
-
Produced heat
-
Consumed energy
▪
You can read out the energy data:
-
For space heating
-
For space cooling
-
For domestic hot water production
▪
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
6.5.1 Produced heat
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
INFORMATION
If glycol is present in the system ([E‑0D]=1]), then the produced heat will NOT be
calculated, nor will it be displayed on the user interface.
▪
The produced heat is calculated internally based on:
-
The leaving and entering water temperature
-
The flow rate
-
The power consumption of the booster heater (if applicable) in the domestic
hot water tank
▪
Setup and configuration:
-
No additional equipment needed.
-
Only in case a booster heater is present in the system, measure its capacity
(resistance measurement) and set the capacity via the user interface.
Example:
If you measure a booster heater resistance of 17.1Ω, the capacity of the heater
at 230 V is 3100 W.
6.5.2 Consumed energy
You can use the following methods to determine the consumed energy:
▪
Calculating
▪
Measuring