3TW58019-5A

Bivalent system

Space heating with an auxiliary boiler (alternating operation)

Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.

Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.

The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.

1

Compressor module

2

Hydro module

3

Heat exchanger

4

Pump

5

Shut-off valve

6

Collector (field supply)

7

Motorised 3-way valve (field supply)

8

Booster heater

9

Heat exchanger coil

10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I

User interface

Field wiring

Boiler thermostat

Boiler thermostat

Boiler thermostat

C

Auxiliary contact (normal closed)

th

Heating only room thermostat

K1A

Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)

K2A

Auxiliary relay for activation of boiler
(field supply)

Operation

When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )

Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.

During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.

Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.

Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.

Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.

(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.

Auto / Boiler

1

2

3

4

B

Summary of Contents for EBHQ011BA6V3

Page 1: ...s 87 4 Capacity tables 89 Heating capacity tables 89 Cooling capacity tables 90 5 Dimensional drawing centre of gravity 91 Dimensional drawing 91 6 Piping diagram 92 Piping diagram 92 7 Wiring diagram...

Page 2: ...B A M o n o b l o c D a i k i n A l t h Reversible monobloc H2O piping between outdoor unit and indoor heating appliances Freeze protection of hydraulic parts Cost effective alternative to a fossil fu...

Page 3: ...S EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3 Casing Colour Ivory white Material Painted galvanised steel Dimensions Unit Height mm 1 418 Width mm 1 435 Depth mm 382 382 382 Packing Height mm 1 557 Width m...

Page 4: ...tisfying result In critical processes or in rooms with a high heat load through extra water volume might be required 2 3 MAIN COMPONENTS EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3 Air heat exchanger Speci...

Page 5: ...FICATIONS EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3 Power supply compressor component Main Power Name V3 Phase 1 1 1 Frequency Hz 50 50 50 Voltage V 230 230 230 Voltage range Minimum V 10 Maximum V 10 Cu...

Page 6: ...ype for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V Maximum current 100mA Minimum 0 75m...

Page 7: ...WLRQV DUH H SHFWHG WKH H PXVW EH LQVWDOOHG LQVWHDG LW DYDLODELOLW IRU 4 OWKHUPD 0RQREORFN RZ WHPSHUDWXUH SKDVH SKDVH RQH RQH RQH RQH 4 9 4 9 4 4 4 9 4 9 4 4 5HIHUHQFH HVFULSWLRQ 53 LJLWDO 2 3 3 7 RWWR...

Page 8: ...as to avoid frequent changeover between the E D B H L Q unit and the boiler If the auxiliary contact C is an outdoor temperature thermostat make sure to install the thermostat in the shade so that it...

Page 9: ...y is according to Eurovent rating standard 6 C 003 2006 and valid for chilled water range Dt 3 8 C Capacity values may not be extrapolated below 7 C leaving water temperature 2 Heating capacity Capaci...

Page 10: ...ing standard 6 C 003 2006 and valid for chilled water range Dt 3 8 C Capacity values may not be extrapolated below 7 C leaving water temperature 2 Heating capacity Capacity is according to Eurovent ra...

Page 11: ...et 10 Pump 18 Expansion vessel 18a nipple 3 Waterpiping inlet 11 Remocon kit to be installed indoors 19 Switchbox terminals 4 Entry low voltage cables 30V 12 Air purge 20 Switchbox terminals option sa...

Page 12: ...WOHW ZDWHU EDFNXS KHDWHU WKHUPLVWRU OHFWURQLF H SDQVLRQ YDOYH 5 7 5HIULJHUDQW OLTXLG VLGH WKHUPLVWRU UDQNFDVH KHDWHU 5 7 QOHW ZDWHU WKHUPLVWRU 7 1 22 1 6WRS YDOYH ZLWK VHUYLFH SRUW C IODUH SDQVLRQ YHV...

Page 13: ...RWWRPSODWH KHDWHU 0 0RWRU IDQ ORZHU 9 5 9 5 LRGH PRGXOH UDQNFDVH KHDWHU 36 6ZLWFKLQJ SRZHU VXSSO 9 7 7 8 8 8 XVH 7 9 4 DUWK OHDNDJH FLUFXLW EUHDNHU 0 7HUPLQDO VWULS SRZHU VXSSO 8 XVH 7 9 5 5HVLVWRU O...

Page 14: ...7KHUPDO SURWHFWRU ERRVWHU KHDWHU 75 7UDQVIRUPHU 9 IRU 3 XVH EDFNXS KHDWHU 5 575 XPLGLW VHQVRU 9 6 9 6 6SDUN VXSSUHVVLRQ 7 7KHUPDO IXVH EDFNXS KHDWHU 5 7 57 5 PELHQW VHQVRU 0a 0 a 7HUPLQDO VWULSV FRQQH...

Page 15: ...GRPHVWLF KRW ZDWHU RRUKHDWLQJ VRODU SXPS RU FRUH FRUH 0 0 0 HDUWK RU 1 HDUWK 0 HDUWK RU 1 HDUWK 0 0 HDUWK RQO IRU 68 9 0 3 3 3 0 2QO IRU 62 9 6367 0 0 D 5RRP WKHUPRVWDW 0 D 3 0 ODUP RXWSXW 3 0 RROLQJ...

Page 16: ...conditions the measured value will be higher due to environmental noise and sound reflections Measuring location discharge side EBHQ011 016 A6V3 B 3TW58017 1 E D B H L Q011 COOLING E D B H L Q014 COO...

Page 17: ...tion conditions the measured value will be higher due to environmental noise and sound reflections Measuring location discharge side EBHQ011 016 A6V3 B 3TW58017 3 E D B H L Q011 COOLING E D B H L Q014...

Page 18: ...HQVLRQ IRU OD LQJ WKH XSSHU RXWGRRU XQLW V GUDLQ SLSH HW WKH SRUWLRQ VHDOHG VR WKDW DLU IURP WKH RXWOHW GRHV QRW E SDVV 6XFWLRQ VLGH REVWDFOH LVFKDUJH VLGH REVWDFOH HIW VLGH REVWDFOH 5LJKW VLGH REVWDF...

Page 19: ...such conditions the E D B H models may experience problems with severe ice build up on the aircooled coil In case such conditions are expected the E D B L must be installed instead Both E D B L and E...

Page 20: ...ssure drop unit 4 9 7 KLJK VSHHG PHGLXP VSHHG 63 H WHUQDO VWDWLF SUHVVXUH ORZ ZDWHUIORZ WKURXJK WKH XQLW DXWLRQ 6HOHFWLQJ D IORZ RXWVLGH WKH FXUYHV FDQ FDXVH GDPDJH WR RU PDOIXQFWLRQ RI WKH XQLW 6HH D...

Reviews: