SiAU18-715
Basic Control
Function
81
2.3
Electronic Expansion Valve PI Control
Main Electronic Expansion Valve EV1 Control
Carries out the electronic expansion valve (Y1E) PI control to maintain the evaporator outlet
superheated degree (SH) at constant during heating operation to make maximum use of the
outdoor unit heat exchanger (evaporator).
The optimum initial value of the evaporator outlet superheated degree is 3°C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
Subcooling Electronic Expansion Valve EV3 Control
Makes PI control of the electronic expansion valve (Y3E) to keep the superheated degree
(SH)
of the outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger.
SH = Ts1 - Te
SH : Evaporator outlet superheated degree (°C)
Ts1 : Suction pipe temperature detected by
thermistor R3T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
SH = Tsh
-Te
SH : Outlet superheated degree of evaporator (
°
C)
Tsh : Suction pipe temperature detected with the
thermistor R6T (
°
C)
Te : Low pressure equivalent saturation temperature
(
°
C)
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...