35
SERVICING
S
ET
T
HERMOSTAT
TO
C
HECK
SYSTEM STATUS
1. Follow the sequence 1. to 5. of
S
ET
T
HERMOSTAT
TO
A
DJUST
I
NDOOR
A
IR
CFM
TRIM
.
2. Select STATUS.
3. Follow screen for System Status.
TS
Time Stamp (Compressor run time)
MD
Current system operational Mode
(cooling, cooling startup, heating, heating startup, oil
return, defrost, stop)
CRM
Compressor Reduction Mode
RAD
Requested and Actual percentage Demand
(Requested Demand, Actual cooling/heating provided)
RAF
Requested and Reported ID airflow
(Requested CFM, Actual CFM)
ATOF
Outdoor Air Temperature and Outdoor Fan STATUS
DCT
Discharge Temperature, Outdoor Coil Temperature
DLT
Defrost sensor temperature, Outdoor Liquid
Temperature
PSDST
Pressure Sensor and Outdoor Suction Temperature
H
EAT
P
UMP
W
ITH
O
UTDOOR
T
EMPERATURE
L
OCKOUTS
It is recommended to set the outdoor temperature lockouts during
the initial thermostat set up. This will enable the compressor to
be turned off and switch heating source from refrigeration to aux-
iliary/secondary heating under low ambient conditions.
Backup heat lockout temperature will enable auxiliary/second-
ary heating to be turned on when outdoor temperature is much
higher than indoor temperature, compressor might stop operat-
ing under this circumstance.
Backup Heat Lockout
Temperature
Compressor Lockout
Temperature
(-)
(F°)
OFF
15
In order to access the compressor lockout temperature, Press
MENU
and scroll down to press
INSTALLER OPTIONS
. Enter the
date code (password) when prompted. Choose
VIEW / EDIT CUR-
RENT SETUP
and
COMPRESSOR LOCKOUT / BALANCE POINT
will be
under
HEAT / COOL CONTROL OPTIONS
. For more information
please refer to COMFORTNET
™
CTK04 Communicating Thermostat
SYSTEM INSTALLATION GUIDE.