![background image](http://html1.mh-extra.com/html/daikin/dx13sa0181a-series/dx13sa0181a-series_manual_4699511003.webp)
SS-
DX13SA
www.
daikincomfort
.com
3
DX13SA
0181A*
DX13SA
0241A*
DX13SA
0301A*
DX13SA
0361A*
DX13SA
0421A*
DX13SA
0481A*
DX13SA
0601A*
DX13SA
0611A*
Capacities
Nominal Cooling (BTU/h)
18,000
24,000
30,000
36,000
42,000
48,000
60,000
60,000
Decibels
71
71
72
74
74
74
77
72
Compressor
RLA
9.0
13.5
12.8
14.1
17.9
19.9
25.0
26.4
LRA
48
58.3
64
77
112
109
134
134
Condenser Fan Motor
Horsepower
1/8
1/8
1/8
1/4
1/4
1/4
1/4
1/4
FLA
0.7
0.7
0.7
1.4
1.3
1.3
1.3
1.3
Refrigeration System
Refrigerant Line Size
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
⅞"
1⅛"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.) ⁴ ⁵
¾"
¾"
¾"
¾"
⁴
⅞"
⁵
⅞"
⁵
⅞"
⁵
⅞"
⁵
Valve Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge (oz.)
69
60
60
62
80
91
94
111
Shipped with Orifice Size (in.)
0.051
0.057
0.061
0.070
0.076
0.080
0.086
0.086
Electrical Data
Voltage-Phase (60 Hz)
208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Minimum Circuit Ampacity²
12
17.6
16.7
19.0
23.7
26.2
32.6
34.3
Max. Overcurrent Protection³
20
30
25
30
40
45
50
60
Min / Max Volts
197/253
197/253
197/253
197/253
197/253
197/253
197/253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Equipment Weight (lbs)
102
115
115
118
171
175
184
211
Ship Weight (lbs)
117
128
132
135
189
193
202
233
¹ Line sizes denoted for 25’ line sets, tested and rated in accordance with AHRI Standard 210/240. For other line-set lengths or sizes, refer to the installation & Operating instructions
and/or the long line-set guidelines.
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
⁴ Installer will need to supply ¾” to ⅞” adapters for suction line connections.
⁵ Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
Notes
•
Always check the S&R plate for electrical data on the unit being installed.
•
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
Product Specifications