D
–EIMWC00803-21_01EN - 55/57
14.10.2 Modbus Parameters
Main data exchanged through Modbus are:
Description
Par
Address hex
Address
scale
Type
Active current limitation
0x2000
48192
1
R
Warning status word
0x2001
48193
1
R
STO status word
0x2002
48194
1
R
VFD status word
0x2003
48195
1
R
Allarmi
0x2004
48196
1
R
Regulation Card Temperature
D40
0x2005
48197
16
R
Motor Current
D84
0x2006
48198
10
R
DC Bus Voltage
D67
0x2007
48199
10
R
Actual speed
D21
0x2008
48200
1
R
NTC1 Resistance
D68
0x2009
48201
10
R
NTC1 Temperature
D69
0x200A
48202
10
R
NTC2 Resistance
D70
0x200B
48203
10
R
NTC2 Temperature
D71
0x200C
48204
10
R
PRS1 Voltage
D74
0x200D
48205
100
R
PRS1 Pression
D75
0x200E
48206
100
R
PRS2 Voltage
D76
0x200F
48207
100
R
PRS2 Pression
D77
0x2010
48208
100
R
PRS3 Voltage
D78
0x2011
48209
100
R
PRS3 Pression
D79
0x2012
48210
100
R
Radiator Temperature
D25
0x2013
48211
16
R
EV pulse
D37
0x2014
48212
1
R
Number of Power Holes
D46-D47
0x2015
48213
1
R
Number of solenoid cycles
D38-D39
0x2017
48215
1
R
Motor power
D01
0x2019
48217
16
R
Run command
C21
0x201A
48218
1
R/W
Speed reference
P230
0x201B
48219
1
R/W
DC Min warning threshold
P232
0x201C
48220
10
R/W
DC Max warning threshold
P233
0x201D
48221
10
R/W
VFD Cooling Temp. Reference
P159
0x201F
48223
10
R/W
VFD Start Temperature
P119
0x2020
48224
10
R/W
Capacitors Current
D54
0x2021
48225
40.96
R
VFD Cooling Ripple Reference
P140
0x2022
48226
100
R/W
Max grid amplitude warning
P247
0x2023
48227
10
R/W
Max grid frequency drift warning
P248
0x2024
48228
10
R/W
Max grid unbalance warning
P249
0x2025
48229
10
R/W
Max DC Bus 100 Hz Ripple warning
P250
0x2026
48230
10
R/W
Max Regulation card temperature
P251
0x2027
48231
10
R/W
Grid Amplitude
N50
0x2028
48232
10
R
Grid unbalance
N73
0x2029
48233
10
R
Grid frequency
N51
0x202A
48234
100
R
DC Bus 100Hz ripple
N79
0x202B
48235
16
R
Average Radiator Temperature
N81
0x202C
48236
200
R
Radiator Temperature Ripple
D43
0x202D
48237
100
R
Radiator Cooling Period
N80
0x202E
48238
10
R
Modulation index
D19
0x202F
48239
40.96
R